Siemens PLC sourcing desk · Multi-brand automation spares [email protected] +86 18359268345
Request Quote
Mitsubishi Electric In Stock OK

Mitsubishi S-K25 AC Magnetic Contactor

Request verified availability, condition, replacement risk review, packing options and courier lead time for S-K25.

Exact partS-K25 RFQ auto-fillPart number attached Export packingDHL / FedEx / UPS Sales replyEmail or WhatsApp
BrandMitsubishi Electric Part NumberS-K25 ConditionAvailability Check Lead TimeRFQ Confirmation DocumentsDatasheet / photos by RFQ ShippingExport packing available
Auto-filled RFQ S-K25

Click Request Quote and the part number is inserted into the inquiry form automatically.

Procurement Data

Key Product Information

Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.

Brand
Mitsubishi Electric
Primary Part Number
S-K25
Product Type
AC Magnetic Contactor
Series / Family
25A 3-Pole S-K Series
Country of Origin
JP
Catalog Category
Relays & Protection
Model confirmed for inquiry S-K25 Send quantity, destination and urgency. The RFQ form keeps this part number attached.
Request Quote
Product Overview

Mitsubishi S-K25 Down? Every Minute of Downtime Costs You Money — We Ship Today

Your line stopped. The S-K25 contactor burned out at 2 AM, and your maintenance team is standing by waiting for a part. We’ve been there — and that’s exactly why siemensplc.com stocks the Mitsubishi S-K25 AC Magnetic Contactor for same-day dispatch. One call, one email, and your replacement is on a DHL flight out of Xiamen before your next shift starts. No broker delays, no grey-market risk — just a genuine S-K Series unit with full traceability, heading straight to your plant floor.

The S-K25 is a 25A, 3-pole AC magnetic contactor from Mitsubishi Electric’s compact S-K Series, designed for motor switching, conveyor control, pump circuits, and PLC-driven output loads. It is a direct drop-in replacement for any existing S-K25 installation — same footprint, same terminal pitch, same auxiliary contact interface. No rewiring. No re-engineering. Bolt it in, wire it up, close the panel door.

⚡ URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345

Quick Technical Datasheet

Parameter Specification
Model S-K25
Brand Mitsubishi Electric
Series S-K Series
Type AC Magnetic Contactor
Rated Current 25 A
Main Poles 3-pole
Coil Voltage Options AC 100V / 110V / 200V / 220V / 380V / 440V (specify at order)
Frequency 50 / 60 Hz
Insulation Class Class E
Mounting DIN rail (35 mm) or direct panel mount
Country of Origin Japan
Certifications CE, UL, RoHS, IEC 60947-4-1
HS Code 8536.49
Stock Status ✔ Ready to Ship — Xiamen Warehouse

Troubleshooting & Replacement Tips

After ten years of field work, the S-K25 fails in predictable ways. Here’s what to check before you order a second unit and what to watch during swap-out:

Common Failure Modes:

  • Coil burnout (most frequent): Caused by sustained overvoltage, voltage fluctuation above ±10% of rated coil voltage, or coil energized without load. Symptom: contactor hums but does not pull in, or pulls in intermittently. Measure coil resistance — an open circuit or significantly lower-than-spec resistance confirms burnout. Order the replacement with the exact coil voltage your control circuit supplies; do not substitute 220V for 200V coil without verifying your transformer tap.
  • Contact welding: Occurs under high inrush current from large motor loads or frequent jogging cycles. Symptom: contactor does not drop out when de-energized, motor runs continuously. Do not attempt to pry contacts apart — replace the unit. Check your motor’s locked-rotor current against the S-K25’s rated making capacity before reinstalling.
  • Auxiliary contact failure: The 1a1b auxiliary block is a common wear item in high-cycle applications. If your PLC is losing feedback signals but the main contacts are still switching, isolate the auxiliary block first. The SK-1A1B auxiliary block is field-replaceable without removing the main contactor body.
  • Mechanical wear / chattering: Caused by low coil voltage (check for voltage drop under load), contaminated contact surfaces, or worn return spring. Chattering accelerates contact erosion rapidly — address immediately.

Replacement Procedure (field-verified steps):

  1. Isolate and lock out the circuit. Verify zero voltage with a calibrated meter — do not rely on the upstream breaker alone.
  2. Photograph the existing wiring before disconnecting. The S-K25 terminal layout is standard, but coil polarity and auxiliary wiring vary by installation.
  3. Disconnect main power terminals (L1/L2/L3, T1/T2/T3) and coil terminals (A1/A2). Note the coil voltage label on the old unit — confirm your replacement matches.
  4. Release the DIN rail latch or remove panel-mount screws. The S-K25 body slides off the rail with a flat-blade screwdriver on the latch tab.
  5. Mount the new unit. Torque main terminals to 2.5–3.0 N·m; auxiliary terminals to 1.2–1.5 N·m. Under-torqued terminals are the leading cause of premature contact failure in the field.
  6. Restore power and test: energize the coil, verify pull-in, check main contact continuity under load, confirm auxiliary feedback to PLC.
  7. Log the replacement date and coil voltage in your maintenance record. The S-K25 has a rated mechanical life of 10 million operations — track cycle counts if your application is high-frequency.

Reliability in Harsh Conditions

The S-K Series was not designed for a climate-controlled server room. It was built for the kind of environments where your panel is mounted next to a press, a furnace, or a coastal pump station. The S-K25 carries an operating temperature range of -10°C to +60°C and is rated for humidity up to 85% RH non-condensing — covering the majority of industrial and marine-adjacent installations without derating.

The coil assembly uses a laminated silicon-steel core with a shading ring to suppress AC hum, which also reduces mechanical vibration fatigue on the coil bobbin. In high-vibration environments — stamping presses, compressors, mobile equipment — the S-K25’s compact, low-mass armature reduces the risk of nuisance dropout compared to larger frame contactors. The contact carrier is glass-fiber reinforced, maintaining dimensional stability under thermal cycling that would warp lesser materials.

For installations in dusty or chemically aggressive atmospheres, the S-K25 can be enclosed in an IP54 or higher rated enclosure without derating — the contactor itself does not require forced ventilation at rated current. In high-altitude installations above 2,000 m, apply a derating factor per IEC 60947-4-1 Annex B; contact us if you need application-specific guidance.

Global Express Logistics

Our dispatch hub is in Xiamen, Fujian — one of China’s primary export ports with direct DHL, FedEx, and UPS gateway access. When you place an urgent order before 15:00 CST, your S-K25 ships the same business day. Here’s what the logistics chain looks like from our warehouse to your receiving dock:

  • Order confirmation: Within 2 hours of payment or PO receipt. Proforma invoice issued immediately for customs pre-clearance preparation.
  • Pick & pack: Each unit is individually bubble-wrapped, placed in a rigid outer carton with foam inserts, and labeled with the correct HS code (8536.49) and country of origin documentation.
  • Export documentation: Commercial invoice, packing list, and certificate of origin prepared in parallel with packing — no delays at customs.
  • Carrier handoff: DHL Express or FedEx International Priority, depending on destination. Tracking number sent to your email within 1 hour of carrier pickup.
  • Transit times (typical): Southeast Asia 2–3 days | Europe 3–5 days | North America 4–6 days | Middle East 3–5 days | Australia 3–4 days.
  • Bulk orders: For 10+ units, sea freight consolidation via Xiamen port is available with full FCL/LCL documentation support.

Every shipment includes a packing list, commercial invoice, and certificate of conformity. Import duty classification support is available on request — we have handled customs clearance documentation for buyers in over 40 countries.

Contact Information

📧 Email: [email protected]
📱 WhatsApp: +86 18359268345
🌐 Web: siemensplc.com

© 2026 siemensplc.com. All rights reserved. Specifications subject to manufacturer revision without notice.

Ready to quote

Send This Part Number to Sales

[email protected]
RFQ workflow

Confirmation Process

Quality workflow ->
01Model confirmation

We check the full part number, brand, series and visible nameplate information before quotation.

02Availability reply

Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.

03Packing & courier

DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.