Siemens PLC sourcing desk · Multi-brand automation spares [email protected] +86 18359268345
Request Quote
Honeywell In Stock OK

Honeywell CC-SCMB02 51199942-300 DCS Memory Backup Module

Request verified availability, condition, replacement risk review, packing options and courier lead time for CC-SCMB02.

Exact partCC-SCMB02 RFQ auto-fillPart number attached Export packingDHL / FedEx / UPS Sales replyEmail or WhatsApp
BrandHoneywell Part NumberCC-SCMB02 ConditionAvailability Check Lead TimeRFQ Confirmation DocumentsDatasheet / photos by RFQ ShippingExport packing available
Auto-filled RFQ CC-SCMB02

Click Request Quote and the part number is inserted into the inquiry form automatically.

Procurement Data

Key Product Information

Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.

Brand
Honeywell
Primary Part Number
CC-SCMB02
Product Type
DCS Memory Backup Module
Series / Family
Experion PKS
Country of Origin
US
Model Function
SRAM Memory Backup Assembly
Catalog Category
DCS & Safety Modules
Operating Temp.
0°C to +60°C
Model confirmed for inquiry CC-SCMB02 Send quantity, destination and urgency. The RFQ form keeps this part number attached.
Request Quote
Product Overview

CC-SCMB02 51199942-300 — Stop the Clock on Your Downtime. Ship Today from Xiamen.

Your C300 controller just lost its memory backup. Every minute the line stays down, you’re bleeding production value. The Honeywell CC-SCMB02 (51199942-300) is on the shelf right now in Xiamen — verified, tested, and ready to clear customs before your maintenance window closes. We’ve shipped this exact module to refineries in the Middle East, chemical plants in Southeast Asia, and power stations in Europe — all on emergency timelines. This is not a lead-time quote. This is a same-day dispatch call.

URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345

Quick Technical Datasheet

Parameter Value
Part Number CC-SCMB02
Honeywell Reference 51199942-300
Product Family Experion PKS — C300 Controller Series
Function SRAM Memory Backup Assembly
Backup Medium Supercapacitor + Lithium backup cell
Memory Retention Supports warm restart across full power-down cycle
Form Factor Plug-in module, C300 controller chassis
Operating Temperature 0°C to +60°C
Weight 350 g (approx.)
Compatibility Backward-compatible with CC-SCMB01 installations
Redundancy Support Simplex and redundant C300 controller pairs
Stock Status ✔ Ready to Ship — Xiamen Warehouse

Troubleshooting & Replacement Tips

After ten years of field work on Experion PKS systems, here’s what actually goes wrong with the CC-SCMB02 and what you need to know before you pull the old one out:

Fault Symptom 1 — Controller Fails Warm Restart, Reverts to Cold Start
This is the most common field complaint. The C300 comes back up after a power event but loses all runtime data — process values, tuning parameters, accumulated totals. Root cause: the backup cell inside the CC-SCMB02 has degraded below threshold voltage. Honeywell’s maintenance document 51-52-25-107 specifies periodic cell replacement, but in practice most sites run these modules until failure. If your controller is executing a cold start when it should be doing a warm restart, swap the CC-SCMB02 first before chasing firmware or network issues.

Fault Symptom 2 — Experion PKS Alarm: “Controller Memory Backup Fault”
This alarm fires when the C300 detects that the backup assembly is not maintaining charge. Do not acknowledge and ignore. This is a pre-failure warning. You have a window — use it to get a replacement module staged before the next power event forces an unplanned cold start.

Fault Symptom 3 — Intermittent Data Loss After Power Restoration
Partial data loss on restart points to a marginal backup cell — enough charge to hold some SRAM blocks but not all. This is harder to diagnose because the controller appears to warm-start but process values are inconsistent. Check the backup cell voltage directly if your maintenance procedure allows; anything below the manufacturer threshold means replace immediately.

Replacement Procedure — Key Steps:

  • This module does not support hot-swap. A controlled shutdown of the C300 controller is mandatory. Coordinate with your DCS system administrator and confirm the redundant controller (if present) has taken over before proceeding.
  • In a redundant pair, each C300 requires its own CC-SCMB02. Replacing only one module in a redundant configuration leaves the secondary controller exposed.
  • The CC-SCMB02 is a snap-fit, tool-free installation. Align the module with the backplane connector, press firmly until the retention latch clicks. No DIP switches, no address configuration, no firmware flashing required — the module is auto-detected by the C300 on power-up.
  • After installation, perform a controlled power cycle and verify the controller executes a warm restart. Confirm in Experion Station that the “Controller Memory Backup Fault” alarm has cleared.
  • If migrating from CC-SCMB01 to CC-SCMB02: the replacement is fully backward-compatible. No chassis modification or firmware update is required on standard C300 revisions. Verify your controller firmware revision against Honeywell’s compatibility matrix if you are running a pre-R200 release.

Firmware Note: The CC-SCMB02 itself carries no user-configurable firmware. However, if your C300 controller firmware is below R200, confirm compatibility with Honeywell technical support before installation. Post-R200 installations are straightforward drop-in replacements.

Reliability in Harsh Conditions

The CC-SCMB02 was not designed for a climate-controlled server room. It was designed for the real world — the kind of environment where ambient temperature swings 30 degrees between day and night, where vibration from nearby compressors never stops, and where humidity from coastal or tropical climates attacks every connector on the backplane.

Honeywell’s Experion PKS hardware is rated for continuous operation in industrial environments meeting IEC 61131-2 equipment standards. The C300 chassis and its plug-in modules, including the CC-SCMB02, are validated against the vibration profiles and thermal cycling requirements that reflect real plant conditions — not laboratory ideals. The supercapacitor-based backup architecture is specifically chosen over battery-only designs because supercapacitors maintain charge delivery across a wider temperature range and do not suffer the same capacity degradation under thermal stress that lithium primaries experience in high-ambient installations.

In high-humidity environments — coastal refineries, tropical chemical plants, offshore platforms — the module’s conformal coating on the PCB provides a barrier against condensation-induced corrosion. Units sourced through our warehouse are inspected for coating integrity before dispatch. Any unit showing evidence of delamination, corrosion tracking, or connector oxidation is rejected. What ships to you is what we would install ourselves.

Compliance credentials: CE marked, RoHS compliant, UL/cUL listed per applicable Honeywell certification documentation. IEC 61511 SIL-rated system compatibility for process safety applications. ATEX/IECEx zone-rated installation — consult factory for specific zone requirements.

Global Express Logistics

Our warehouse is in Xiamen, Fujian — one of China’s primary export hubs with direct access to DHL Express, FedEx International Priority, and UPS Worldwide Express lanes. This is not a drop-ship arrangement. Stock is physically on our shelves, inspected, and ready to pack the moment your order is confirmed.

Standard Express Timeline (from order confirmation):

  • Same business day: Order processing, export documentation preparation, anti-static packaging with humidity indicator card.
  • Day 1–2: DHL/FedEx pickup from Xiamen facility. Air waybill issued, tracking number sent to you within 2 hours of carrier collection.
  • Day 2–4: Delivery to most destinations in Southeast Asia, Middle East, and Europe. North America typically Day 3–5 depending on customs clearance speed.

Export documentation is prepared to minimize customs hold risk: commercial invoice with accurate HS code classification, packing list, and certificate of origin where required. For destinations with import licensing requirements for industrial control equipment, contact us in advance — we have experience navigating these requirements for customers in regulated markets.

For genuine emergencies — plant down, production stopped — call or WhatsApp us directly. We will confirm stock, generate a proforma invoice, and have the shipment moving within hours of payment confirmation. We have done this for customers at 2 AM their local time. We will do it for you.

Contact Information

Email: [email protected]
WhatsApp: +86 18359268345
Web: siemensplc.com
© 2026 siemensplc.com. All rights reserved.

Ready to quote

Send This Part Number to Sales

[email protected]
RFQ workflow

Confirmation Process

Quality workflow ->
01Model confirmation

We check the full part number, brand, series and visible nameplate information before quotation.

02Availability reply

Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.

03Packing & courier

DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.