Siemens PLC sourcing desk · Multi-brand automation spares [email protected] +86 18359268345
ABB In Stock OK

ABB DSSB-01C 68300746C DSU Control Board

Request verified availability, condition, replacement risk review, packing options and courier lead time for DSSB-01C.

Exact partDSSB-01C RFQ auto-fillPart number attached Export packingDHL / FedEx / UPS Sales replyEmail or WhatsApp
BrandABB Part NumberDSSB-01C ConditionAvailability Check Lead TimeRFQ Confirmation DocumentsDatasheet / photos by RFQ ShippingExport packing available
Auto-filled RFQ DSSB-01C

Click Request Quote and the part number is inserted into the inquiry form automatically.

Procurement Data

Key Product Information

Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.

Brand
ABB
Primary Part Number
DSSB-01C
Product Type
PLC Control Board
Series / Family
S800
Manufacturer
ABB
Country of Origin
SE
Model Function
Supervisory control, grid sync, DDCS communication — ACS800 DSU / AFE
Catalog Category
Motor Drives
Operating Temp.
0°C to +55°C continuous (adequate cabinet airflow required)
Compliance
CE, IEC 61800-3, IEC 61800-5-1, RoHS, UL (within ACS800 system)
Model confirmed for inquiry DSSB-01C Send quantity, destination and urgency. The RFQ form keeps this part number attached.
Request Quote
Product Overview

ABB DSSB-01C 68300746C — Cut the Downtime Before It Cuts Your Margin

Your ACS800 Drive Supply Unit is offline. The DDCS link is dead, the panel is blank, or the synchronization fault won’t clear. You’ve already checked the fibers, verified the incoming grid, and confirmed the DC bus is discharged. The DSSB-01C control board is the culprit — and every hour it stays that way costs real money. Production lines don’t pause for OEM lead times. We exist precisely for this moment.

The ABB DSSB-01C (Order Code: 68300746C) is the supervisory control board at the heart of the ACS800 Active Front End topology. It manages grid synchronization, DDCS fiber communication, protection sequencing, and the 24 VDC logic rail that keeps the entire DSU alive. When it fails, nothing downstream works — not the inverter section, not the motor, not your process. We stock verified units in Xiamen and dispatch same-day for orders confirmed before 15:00 CST. DHL Express puts it on your bench in 2–4 business days, anywhere on the planet.

⚡ URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345

Quick Technical Datasheet

Manufacturer ABB
Part Number DSSB-01C
ABB Order Code 68300746C
Function Supervisory control, grid sync, DDCS communication — ACS800 DSU / AFE
Compatible Platform ABB ACS800 Series — Drive Supply Unit (DSU) / Active Front End (AFE)
Communication Interface DDCS Fiber Optic (RDCO link) + DSU internal backplane connector
Supply Voltage 24 VDC via DSU internal power rail
Operating Temperature 0°C to +55°C continuous (adequate cabinet airflow required)
Storage Temperature -40°C to +70°C
Humidity Rating 5–95% RH, non-condensing
PCB Protection Conformal coating — IEC 60068-2-78 damp heat, IEC 60068-2-11 salt mist
Compliance CE, IEC 61800-3, IEC 61800-5-1, RoHS, UL (within ACS800 system)
Packaged Weight ~3.0 kg (ESD-safe inner bag + double-wall export carton)
Stock Status ✔ Ready to Ship — Xiamen Warehouse
Dispatch Cutoff Same-day for orders confirmed before 15:00 CST

Troubleshooting & Replacement Tips

The DSSB-01C fails in predictable ways. Knowing the fault signature before you pull the board saves time and prevents misdiagnosis.

Fault Codes That Implicate the DSSB-01C

  • FF8E / FF8F — DDCS Link Lost: The board’s fiber optic transceiver handles the DDCS ring between the DSU and inverter sections. Swap the fiber patch cables first — a cracked ferrule or dirty connector face is the most common cause. If the fault persists with known-good fibers, the transceiver on the DSSB-01C has degraded. This is a board-swap scenario.
  • FF52 — Control Power / DSU Not Ready: The DSSB-01C regulates the internal 24 V logic rail. Capacitor aging or a transient overvoltage event can collapse this rail. Measure at the board connector before condemning it — a failed external SMPS produces an identical symptom. If the rail is present and stable, the board’s internal regulation circuit has failed.
  • FF61 — Grid Synchronization Fault: The board samples L1/L2/L3 voltage to generate firing pulses for the IGBT front end. Confirm incoming phase balance first (a single-phase loss upstream will trigger this). If the grid is clean and balanced, the board’s voltage measurement circuit has drifted out of tolerance — replace the board.
  • Blank Panel / No Boot: If the ACS800 control panel shows nothing after confirmed power-up, and the DSU section is energized, the DSSB-01C processor has either lost firmware or suffered a hard fault. There is no field-level recovery path without ABB service tools. Order the replacement board.

Replacement Procedure — Field-Tested Sequence

  1. Back Up Parameters: Connect ABB DriveWindow or DriveComposer. Upload the full parameter set to a .dpa file and store it on a laptop that stays on-site. If the replacement board carries a different firmware revision, this file is your only recovery path.
  2. LOTO and DC Bus Discharge: Open the main incoming breaker and apply lockout/tagout. The ACS800 DC bus holds charge for several minutes after power removal. Verify below 50 V with a calibrated meter before touching anything inside the cabinet.
  3. Label Fiber Connections: The DDCS fiber connectors are push-pull type — no twisting. Label TX and RX before disconnecting. Orientation errors on reconnection will generate immediate DDCS faults at power-up.
  4. Check DIP Switch Positions: The replacement DSSB-01C ships with factory-default DIP switch settings. Photograph the removed board’s switch positions before extraction and replicate them exactly on the new board. Node address mismatches cause DDCS communication failures that look like a second board fault.
  5. Seat and Reconnect: Slide the new board into the DSU chassis slot until the backplane connector fully engages — you will feel positive seating. Reconnect fiber cables with TX-to-RX cross-connection per the DSU wiring diagram.
  6. Firmware Verification Before Parameter Restore: Power the DSU section only. Check the firmware version on the ACS800 panel. If it differs from the original board, confirm parameter set compatibility before downloading the saved file — incompatible parameter sets can corrupt drive configuration.
  7. DSU Identification Routine: After parameter restore, run the DSU identification routine (parameter 99.15 or equivalent for your firmware). Verify DDCS link status and grid synchronization before enabling the inverter section and returning the drive to service.

Reliability in Harsh Conditions

The DSSB-01C is not a commercial-grade board repackaged for industrial use. ABB’s manufacturing process for ACS800-series control boards applies conformal coating to the fully assembled PCB — a polymer barrier that blocks moisture, condensation, and airborne contaminants including the sulfur compounds prevalent in pulp mills, wastewater treatment plants, and oil refineries. Coating integrity is validated per IEC 60068-2-78 (damp heat, 40°C/93% RH, 56 days) and IEC 60068-2-11 (salt mist).

Mechanical robustness is validated to IEC 60068-2-6 (sinusoidal vibration, 10–150 Hz) and IEC 60068-2-64 (random vibration), covering the spectral profiles of compressor rooms, marine engine rooms, and heavy rolling mill environments. The board’s backplane connector uses gold-plated contacts with a positive retention force that maintains stable contact resistance across thousands of thermal expansion and contraction cycles.

All components on the DSSB-01C are industrial-grade with extended temperature ratings and full supply chain traceability. The protection architecture is designed to generate a fault code and execute a controlled shutdown rather than sustain damage from an abnormal operating condition — meaning the board protects itself and the drive, and gives you a diagnostic starting point rather than a silent failure.

Units supplied by us as tested-refurbished complete a 48-hour elevated-temperature burn-in cycle before shipment. Any board exhibiting parameter drift, communication instability, or anomalous current draw during burn-in is rejected from stock. The unit that ships is the unit that passed every test.

Global Express Logistics

Our dispatch hub is in Xiamen, Fujian Province — a primary export gateway with direct access to DHL, FedEx, and UPS international facilities. Transit times to major industrial regions:

  • Southeast Asia (SG, MY, TH, ID): 1–2 business days via DHL Express
  • Middle East (AE, SA, QA, KW): 2–3 business days via DHL Express
  • Europe (DE, NL, FR, PL, SE): 3–4 business days via DHL Express or FedEx IP
  • North America (US, CA, MX): 3–5 business days via FedEx International Priority
  • South Asia (IN, PK, BD): 2–4 business days via DHL Express

Every shipment includes: commercial invoice with HS code 8537.10, packing list with part number and condition declaration, certificate of origin (on request), test report for refurbished units, and ESD-safe inner packaging inside a double-wall export carton. For customers in India, Brazil, Saudi Arabia, and EU member states with specific import compliance requirements — send your documentation checklist before the order is placed and we will prepare accordingly. Tracking numbers are issued within 2 hours of dispatch.

Contact Information

Email: [email protected]
WhatsApp: +86 18359268345
Web: siemensplc.com
© 2026. All rights reserved.

Ready to quote

Send This Part Number to Sales

[email protected]
RFQ workflow

Confirmation Process

Quality workflow ->
01Model confirmation

We check the full part number, brand, series and visible nameplate information before quotation.

02Availability reply

Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.

03Packing & courier

DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.