Siemens PLC sourcing desk · Multi-brand automation spares [email protected] +86 18359268345
ABB In Stock OK

ABB RBIP-01 3AUA0000030932 BACnet/IP Module

Request verified availability, condition, replacement risk review, packing options and courier lead time for RBIP-01.

Exact partRBIP-01 RFQ auto-fillPart number attached Export packingDHL / FedEx / UPS Sales replyEmail or WhatsApp
BrandABB Part NumberRBIP-01 ConditionAvailability Check Lead TimeRFQ Confirmation DocumentsDatasheet / photos by RFQ ShippingExport packing available
Auto-filled RFQ RBIP-01

Click Request Quote and the part number is inserted into the inquiry form automatically.

Procurement Data

Key Product Information

Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.

Brand
ABB
Primary Part Number
RBIP-01
Product Type
Drive Communication Module
Series / Family
S800
Country of Origin
SE
Catalog Category
Motor Drives
Operating Temp.
0 °C to +55 °C
Model confirmed for inquiry RBIP-01 Send quantity, destination and urgency. The RFQ form keeps this part number attached.
Request Quote
Product Overview

ABB RBIP-01 3AUA0000030932 — Stop the Clock on Your BACnet Downtime

Your ACS-series drive went silent on the BACnet network at 02:14. The BAS lost visibility. HVAC loops drifted. The shift supervisor is on the phone. Every minute of that silence costs real money — in lost production, in emergency labor, in SLA penalties. The ABB RBIP-01 (order code 3AUA0000030932) is the exact module that restores that link. We stock it in Xiamen. It ships today.

The RBIP-01 is ABB’s dedicated BACnet/IP routing adapter for the ACS drive family. It slots directly into the drive’s option bay, presents the drive’s full parameter set as native BACnet objects, and hands control back to your building automation system — no gateway box, no protocol converter, no additional power supply. When this module fails, there is no workaround. You need the part.

URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345

Quick Technical Datasheet

Parameter Value
Part Number RBIP-01
ABB Order Code 3AUA0000030932
Protocol BACnet/IP — ANSI/ASHRAE 135 compliant
Physical Interface Ethernet RJ-45, 10/100 Mbps
Drive Compatibility ACS355, ACS550, ACS800, ACS880 (verify option slot per drive revision)
Mounting Direct drive option slot insertion
Power Source Drawn from drive option slot — no external PSU required
Operating Temperature 0 °C to +55 °C
Storage Temperature −40 °C to +70 °C
Weight ~120 g
Certifications CE, UL
Stock Status ✅ Ready to Ship — Xiamen warehouse

Troubleshooting & Replacement Tips

Fault Code 7 / Communication Loss (ACS800 / ACS880): This is the most common field failure mode. The drive raises a COMM FAULT or EXT FAULT 1 alarm when the RBIP-01 stops responding on the BACnet network. Before condemning the module, check the following in sequence:

  1. Option slot seating: Power down the drive fully (wait for DC bus discharge — minimum 5 minutes after mains isolation). Re-seat the RBIP-01 firmly. Connector oxidation on humid sites causes intermittent contact failures that mimic module death.
  2. IP address conflict: The RBIP-01 ships with DHCP enabled by default. If your BAS network runs static addressing, the module may have grabbed a conflicting lease. Connect a laptop directly via Cat5e, open a browser to the module’s default IP (check the label — typically 192.168.0.1 on factory reset), and assign a static address that matches your BACnet/IP subnet.
  3. BACnet Device Instance conflict: Two devices sharing the same BACnet Device Instance on the same IP network will cause both to drop off. Verify the Device Instance configured in the RBIP-01 web interface is unique across your entire BACnet/IP network segment.
  4. Firmware mismatch: ACS880 drives running firmware ≥ 2.80 require RBIP-01 firmware ≥ 1.10. Older module firmware will connect but silently drop write commands. Download the latest firmware from ABB’s drive portal and update via the module’s built-in web server before commissioning.
  5. Drive parameter 98.02 (COMM MODULE LINK): On ACS800, this parameter must be set to the correct option slot (typically slot 1 or 2 depending on physical installation). A factory-reset drive defaults to NONE — the module will enumerate on the network but the drive will ignore all BACnet write commands until this is set correctly.

Module confirmed failed? The RBIP-01 has no field-serviceable components. The correct action is direct replacement. Document the existing IP address, Device Instance, and any custom BACnet object mappings before removal — these are not stored in the drive and will be lost when the module is swapped.

Post-replacement commissioning checklist:

  • Assign static IP / verify DHCP lease reservation at router
  • Set BACnet Device Instance (unique, documented in your BAS database)
  • Set ACS800 parameter 98.02 to correct option slot
  • Verify firmware version matches drive firmware generation
  • Confirm BACnet objects appear in BAS discovery scan before closing the panel
  • Run a 15-minute soak test under live BAS polling before returning the system to automatic control

Reliability in Harsh Conditions

Drive rooms are not server rooms. The RBIP-01 is engineered for the environment it actually lives in — not the environment the datasheet assumes.

The module’s PCB carries a conformal coating that resists condensation ingress on sites where ambient humidity swings between 20% and 95% RH non-condensing — common in coastal industrial facilities, food processing plants, and water treatment stations. The RJ-45 connector is rated for repeated mating cycles without contact degradation, which matters on sites where the module is pulled for inspection during annual drive maintenance.

Vibration tolerance is validated to IEC 60068-2-6 test profile, covering the 5–150 Hz range that encompasses both structural building vibration and the harmonic frequencies generated by the drive itself during operation. Modules mounted in drives running at 50 Hz output will see continuous low-amplitude vibration at the fundamental and its harmonics — the RBIP-01’s board-level component selection and PCB layout account for this.

Thermal cycling is the silent killer of drive communication modules. The RBIP-01 is qualified across the full −40 °C to +70 °C storage range, meaning it survives the temperature swings that occur in unheated equipment rooms between winter shutdown and summer restart — a failure mode that catches cheaper third-party alternatives off guard.

EMC immunity is rated to EN 61800-3 Category C3, appropriate for industrial power drive systems operating in second environment (industrial) networks. The module will not drop off the BACnet network due to conducted or radiated interference from adjacent VFDs, contactors, or switching power supplies sharing the same panel.

Global Express Logistics

Stock is held at our Xiamen warehouse, positioned for rapid dispatch to Asia-Pacific, Middle East, Europe, and the Americas. Our logistics workflow is built around one objective: getting the module into your hands before the next production shift.

Same-day dispatch: Orders confirmed before 15:00 CST ship the same business day. Orders confirmed after 15:00 ship the following morning. No exceptions, no queuing behind bulk orders.

Carrier selection: DHL Express and FedEx International Priority are our primary carriers for urgent shipments. Both provide door-to-door tracking from Xiamen to your facility. Typical transit times: Southeast Asia 1–2 days, Middle East 2–3 days, Europe 3–4 days, North America 3–5 days. These are working-day estimates under normal customs clearance conditions.

Export documentation: Commercial invoice, packing list, and certificate of origin are prepared at dispatch. For shipments requiring an ECCN classification or end-user declaration, notify us at order confirmation and we will prepare the documentation in parallel with packing — no delays.

Customs clearance: We declare goods accurately under the correct HS code for drive communication modules. We do not under-declare value. Accurate documentation is the single most reliable way to avoid customs holds that turn a 3-day shipment into a 10-day ordeal.

Tracking: AWB number is emailed within 2 hours of dispatch. For urgent shipments, our logistics team monitors the shipment through the first customs clearance event and proactively contacts you if any documentation is requested by customs authorities.

Contact Information

📧 Email: [email protected]
📱 WhatsApp: +86 18359268345
🌐 Web: siemensplc.com
© 2026 siemensplc.com. All rights reserved.

Ready to quote

Send This Part Number to Sales

[email protected]
RFQ workflow

Confirmation Process

Quality workflow ->
01Model confirmation

We check the full part number, brand, series and visible nameplate information before quotation.

02Availability reply

Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.

03Packing & courier

DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.