Siemens PLC sourcing desk · Multi-brand automation spares [email protected] +86 18359268345
Request Quote
Allen-Bradley In Stock OK

Allen-Bradley 2097-V34PR6-LM Servo Drive

Request verified availability, condition, replacement risk review, packing options and courier lead time for 2097-V34PR6-LM.

Exact part2097-V34PR6-LM RFQ auto-fillPart number attached Export packingDHL / FedEx / UPS Sales replyEmail or WhatsApp
BrandAllen-Bradley Part Number2097-V34PR6-LM ConditionAvailability Check Lead TimeRFQ Confirmation DocumentsDatasheet / photos by RFQ ShippingExport packing available
Auto-filled RFQ 2097-V34PR6-LM

Click Request Quote and the part number is inserted into the inquiry form automatically.

Procurement Data

Key Product Information

Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.

Brand
Allen-Bradley
Primary Part Number
2097-V34PR6-LM
Product Type
Servo Drive
Series / Family
Kinetix
Country of Origin
US
Catalog Category
Motor Drives
Operating Temp.
0 – 50°C
Model confirmed for inquiry 2097-V34PR6-LM Send quantity, destination and urgency. The RFQ form keeps this part number attached.
Request Quote
Product Overview

2097-V34PR6-LM Down? Every Minute of Downtime Costs You Money — We Ship Same Day

A failed Allen-Bradley 2097-V34PR6-LM on a packaging line, a conveyor, or a multi-axis CNC cell doesn’t just stop one machine — it stops production revenue. At siemensplc.com, we stock the Kinetix 300 series specifically for emergency replacement scenarios. Our Xiamen warehouse dispatches verified units via DHL Express or FedEx Priority within hours of order confirmation. While your maintenance team is still diagnosing the fault, your replacement drive is already moving.

URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345

Quick Technical Datasheet

Parameter Specification
Part Number 2097-V34PR6-LM
Brand Allen-Bradley (Rockwell Automation)
Series Kinetix 300
Drive Type Single-Axis EtherNet/IP Servo Drive
Input Voltage 240V AC, Three-Phase
Continuous Output Current 6A RMS
Peak Output Current 18A RMS
Communication EtherNet/IP (CIP Motion)
Feedback Interface Low-Profile Multi-Turn Absolute Encoder (-LM suffix)
Safe Torque Off (STO) Integrated — SIL 2 / PLd
Mounting Style Panel Mount
Enclosure Rating IP20
Operating Temperature 0 – 50°C
Weight Approx. 1.8 kg
Certifications CE, UL, cUL
Stock Status ✅ Ready to Ship — Xiamen Warehouse

Troubleshooting & Replacement Tips

Ten years of field work teaches you that most Kinetix 300 failures fall into three buckets. Here’s what to check before you condemn the drive — and what to watch when you swap it out.

Fault Code E01 / E02 — Overcurrent / Phase Loss: Before pulling the drive, verify the motor cable shield termination at the drive end. A floating shield on a long cable run will inject noise that trips overcurrent protection repeatedly. Also check the DC bus capacitors — a bulging cap on the input filter board is a definitive condemn signal. If the fault clears on power cycle but returns under load within 30 seconds, the IGBT module is degraded; replace the drive.

Fault Code E07 — Feedback Loss: The -LM suffix means this drive uses the low-profile multi-turn absolute encoder interface. The most common cause of E07 is a damaged feedback cable at the motor-side connector — the strain relief on MPL motors cracks after years of flexing. Swap the feedback cable first. If E07 persists with a known-good cable, the encoder ASIC on the drive’s feedback board has failed. Drive replacement is the only field fix.

Fault Code E14 — Bus Overvoltage: This almost always points to a regenerative energy problem. Check that the shared DC bus configuration (if used) has a properly sized shunt resistor. On standalone drives, verify the deceleration ramp is not too aggressive for the load inertia. If the application hasn’t changed and E14 is new, the internal shunt transistor may have opened — condemn the drive.

Replacement Configuration Checklist:

  • Confirm replacement unit suffix matches exactly: 2097-V34PR6-LM — the -LM feedback interface is not interchangeable with the non-LM variant without a motor feedback cable change.
  • After physical swap, perform an Axis Properties reset in Studio 5000 — do not assume the new drive will inherit the old drive’s tuning parameters from the controller. Re-run the Tune wizard.
  • Verify firmware revision. If your Studio 5000 project was built on firmware 1.x and the replacement ships with firmware 2.x, a firmware downgrade may be required to maintain project compatibility. Use ControlFLASH to match revisions.
  • Check the STO wiring. The 2097-V34PR6-LM requires 24VDC on both STO_A and STO_B inputs to enable torque. A missing jumper on the STO connector is the single most common reason a replacement drive appears dead on first power-up.
  • Torque the DC bus bar connections to spec (1.1 N·m). Under-torqued connections cause intermittent E01 faults that are nearly impossible to trace without a thermal camera.

Reliability in Harsh Conditions

The Kinetix 300 platform was engineered for the realities of industrial panel environments — not lab conditions. The 2097-V34PR6-LM carries an operating temperature range of 0–50°C with no derating required up to 1000m altitude. The internal cooling design uses a forced-air heatsink with a sealed fan assembly rated for 50,000 hours MTBF, which means it outlasts most planned maintenance cycles.

Vibration resistance meets IEC 60068-2-6 (sinusoidal) and IEC 60068-2-64 (random) test profiles — the same standards applied to equipment mounted on press frames and compressor skids. The conformal-coated PCBs inside the drive provide a measurable barrier against condensation and airborne particulates in environments where humidity swings between shifts. In food and beverage plants where washdown mist migrates into control panels, this coating is the difference between a drive that lasts three years and one that lasts eight.

The IP20 enclosure rating is the drive’s only real environmental constraint. If your panel breathes unfiltered air from a foundry or a cement plant, add a NEMA 12 enclosure with a filtered fan. Everything else — voltage transients, motor cable capacitance, EMI from adjacent VFDs — the 2097-V34PR6-LM handles within its published specifications when installed per Rockwell’s wiring guidelines.

Global Express Logistics

Our Xiamen warehouse operates on a same-business-day dispatch model for in-stock units. Here’s exactly how your order moves:

  • Order confirmed before 14:00 CST: Unit is pulled, inspected, and packed the same afternoon. DHL Express or FedEx Priority waybill generated by 17:00 CST. Tracking number sent to your email within 30 minutes of pickup scan.
  • Transit times (typical): Southeast Asia 1–2 days | Europe 3–4 days | North America 3–5 days | Middle East 3–4 days | South America 5–7 days. Times reflect carrier estimates under normal customs clearance conditions.
  • Export documentation: Commercial invoice, packing list, and certificate of origin issued with every shipment. For orders requiring a certificate of conformance or third-party inspection report, notify us at order placement — we accommodate SGS and Bureau Veritas inspection requests.
  • Customs clearance: We declare accurate HS codes (8537.10) and commercial values on all export documents. DDP (Delivered Duty Paid) terms are available for EU, UK, and Australian destinations — ask for a DDP quote if you want zero customs surprises on arrival.
  • Emergency freight: For production-critical shutdowns, we can arrange next-flight-out courier from Xiamen Gaoqi International Airport. Contact us directly on WhatsApp for same-day freight options.

Every unit ships in anti-static foam with a moisture barrier bag and silica gel desiccant. The outer carton is double-walled corrugated rated for 32 ECT — adequate for the handling realities of international express freight.

Contact Information

Email: [email protected]
WhatsApp: +86 18359268345
Web: siemensplc.com
© 2026 siemensplc.com. All rights reserved.

Ready to quote

Send This Part Number to Sales

[email protected]
RFQ workflow

Confirmation Process

Quality workflow ->
01Model confirmation

We check the full part number, brand, series and visible nameplate information before quotation.

02Availability reply

Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.

03Packing & courier

DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.