Siemens PLC sourcing desk · Multi-brand automation spares [email protected] +86 18359268345
Request Quote
Bently Nevada In Stock OK

Bently Nevada 330104-05-12-05-02-05 Proximity Probe

Request verified availability, condition, replacement risk review, packing options and courier lead time for 330104-05-12-05-02-05.

Exact part330104-05-12-05-02-05 RFQ auto-fillPart number attached Export packingDHL / FedEx / UPS Sales replyEmail or WhatsApp
BrandBently Nevada Part Number330104-05-12-05-02-05 ConditionAvailability Check Lead TimeRFQ Confirmation DocumentsDatasheet / photos by RFQ ShippingExport packing available
Auto-filled RFQ 330104-05-12-05-02-05

Click Request Quote and the part number is inserted into the inquiry form automatically.

Procurement Data

Key Product Information

Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.

Brand
Bently Nevada
Primary Part Number
330104-05-12-05-02-05
Product Type
Proximity Probe
Series / Family
3301
Country of Origin
US
Catalog Category
Sensors & Switches
Model confirmed for inquiry 330104-05-12-05-02-05 Send quantity, destination and urgency. The RFQ form keeps this part number attached.
Request Quote
Product Overview

330104-05-12-05-02-05 In Stock — Every Hour of Downtime Costs More Than This Probe

Your turbine is down. The 3500 rack is throwing a Not OK on the radial vibration channel. Maintenance has traced it to the proximity probe — and the OEM lead time just came back at 8 weeks. That is not an option. Every hour a gas turbine, centrifugal compressor, or steam turbine sits idle burns through production margin, contractual penalties, and engineering credibility. The Bently Nevada 330104-05-12-05-02-05 is on our shelf in Xiamen right now. We ship DHL Express within 24 hours of order confirmation. This page exists for one reason: to get your machine back online.

URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345

Quick Technical Datasheet

Parameter Specification Status
Part Number 330104-05-12-05-02-05 Ready to Ship
Brand / Series Bently Nevada 3300 XL 100% Original
Probe Tip Diameter 8 mm eddy-current
Probe Cable Length 12 inches armored
Extension Cable Length 5 meters
Integral Cable Length 2 meters
Connector Type 5-pin
Nominal Gap Voltage -5 VDC standard
Measurement Principle Non-contact eddy-current
Target Calibration Material AISI 4140 steel
Probe Operating Temp -35C to +177C
Extension Cable Temp -35C to +85C
Standard Compliance API 670
Compatible Monitor Bently Nevada 3500 Series
Compatible Proximitor 3300 XL 8mm 330180 series
Origin United States OEM
Ship-From Xiamen, China Ready to Ship

Troubleshooting and Replacement Tips

Fault Scenario 1 — 3500 Monitor shows Not OK on radial channel
Before condemning the probe, work through the measurement chain. Check the Proximitor output voltage at the monitor terminal. A healthy 8mm 3300 XL system at nominal 2.0 mm gap reads approximately -10 VDC at the Proximitor output. Open-circuit reads near -24 VDC; a dead short reads near 0 VDC. Either condition means the probe coil is open or shorted — replace the probe. If the Proximitor output is within range but the monitor still faults, suspect the extension cable or the Proximitor itself before ordering a new probe.

Fault Scenario 2 — Intermittent vibration spikes, no process change
Classic symptom of a cracked probe cable near the armored section, caused by vibration fatigue at the conduit entry point. Flex the cable gently while watching the Proximitor output on a voltmeter. Any voltage jump confirms a broken conductor. The 330104-05-12-05-02-05 uses a 12-inch armored probe cable to resist this failure mode — but after years in high-vibration environments, fatigue wins. Replace the full probe assembly, not just the cable.

Fault Scenario 3 — Gap voltage drifting over time
If static gap voltage is shifting without any mechanical change to shaft position, suspect probe coil degradation from thermal cycling or chemical contamination of the probe tip. Clean the probe tip with isopropyl alcohol and re-measure. If drift persists, the probe is out of calibration and must be replaced. Do not compensate by adjusting monitor setpoints — this masks the fault and creates a safety risk.

Replacement Procedure

  1. De-energize the 3500 rack channel and lock out the monitor before removing the probe. Do not hot-swap proximity probes on live machinery protection systems.
  2. Record the existing gap voltage before removal. This is your baseline for setting the new probe gap. Target gap for 8mm probes is typically 2.0 mm at -10 VDC plus or minus 0.5 VDC.
  3. Remove the probe from the bracket. Inspect the target area on the shaft for scoring, pitting, or runout that may have caused the original probe failure.
  4. Install the 330104-05-12-05-02-05. Thread the probe in until the tip is approximately 2.5 mm from the shaft surface, then back off to achieve the target gap voltage. Use a calibrated gap tool or a digital voltmeter on the Proximitor output.
  5. Reconnect the extension cable. Verify the 5-pin connector is fully seated and the locking collar is tight. A loose connector is the most common cause of post-replacement faults.
  6. Re-energize the channel and verify the Proximitor output is within the linear range, -2 VDC to -18 VDC for 8mm probes. Confirm the monitor channel returns to OK status.
  7. Check the vibration baseline against historical data. A significant change in 1X or 2X amplitude after probe replacement indicates a mechanical issue — do not mask it by adjusting alert setpoints.

Configuration Note — Non-Standard Target Materials
The 330104-05-12-05-02-05 is factory-calibrated for AISI 4140 steel. If your shaft is titanium, Inconel, or another non-ferrous alloy, apply the Bently Nevada material correction factor. Failure to do so results in a systematic measurement error of up to 20%, which can cause missed alarms or nuisance trips.

Reliability in Harsh Conditions

The 3300 XL 8mm proximity probe was designed for the worst environments in industrial operations, not a laboratory. The armored probe cable on the 330104-05-12-05-02-05 provides mechanical protection against the constant micro-vibration that destroys standard cables within months in turbomachinery installations. The probe body is sealed against process fluid ingress including hydrocarbon vapors, steam, and aggressive cleaning agents used during maintenance outages.

Thermal performance is a genuine differentiator. The probe tip is rated to +177C continuous — sufficient for hot-section installations on gas turbines and high-pressure steam turbine bearing housings where ambient temperatures routinely exceed what standard industrial sensors can tolerate. The extension cable, rated to +85C, handles the transition zone between the hot machine casing and the cooler instrument cabinet environment.

Vibration immunity is built into the eddy-current measurement principle itself. No moving parts, no wear surfaces, no mechanical resonance. The probe coil is encapsulated in a thermally stable compound that maintains calibration accuracy across the full operating temperature range. In offshore and coastal installations where salt fog and humidity are constant threats, the probe sealed construction prevents the corrosion-driven calibration drift that plagues inferior sensors.

Every unit we ship has been visually inspected for probe tip integrity, cable jacket condition, connector pin alignment, and armoring continuity. Electrical coil resistance is verified against OEM specifications. We do not ship units with cosmetic damage to the probe tip or cable — even minor surface damage in the eddy-current sensing zone affects linearity.

Global Express Logistics

Our warehouse is in Xiamen, Fujian Province — one of China primary export hubs with direct access to DHL Express, FedEx International Priority, and UPS Worldwide Express. For urgent plant maintenance orders, we target same-day dispatch for orders confirmed before 14:00 CST.

Typical transit times from Xiamen: Southeast Asia 1 to 2 business days; Middle East and Europe 2 to 3 business days; North America 3 to 4 business days; South America and Africa 4 to 5 business days. These are DHL Express estimates under normal customs clearance conditions.

Every shipment includes a commercial invoice, packing list, and country-of-origin documentation prepared for smooth customs clearance. For orders to countries with specific import requirements for industrial automation components, we coordinate documentation in advance to avoid customs holds. We have shipped to refineries, power plants, and offshore platforms in over 50 countries — we know where the customs friction points are and how to avoid them.

For shutdown projects where delivery timing is critical, contact us via WhatsApp for real-time shipment tracking and proactive exception management. We treat your downtime as our problem to solve.

Contact Information

Email: [email protected]
WhatsApp: +86 18359268345
Web: siemensplc.com
© 2026 siemensplc.com. All rights reserved.

Ready to quote

Send This Part Number to Sales

[email protected]
RFQ workflow

Confirmation Process

Quality workflow ->
01Model confirmation

We check the full part number, brand, series and visible nameplate information before quotation.

02Availability reply

Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.

03Packing & courier

DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.