Siemens PLC sourcing desk · Multi-brand automation spares [email protected] +86 18359268345
GE In Stock OK

GE UR73FH Protection Relay

Request verified availability, condition, replacement risk review, packing options and courier lead time for UR73FH.

Exact partUR73FH RFQ auto-fillPart number attached Export packingDHL / FedEx / UPS Sales replyEmail or WhatsApp
BrandGE Part NumberUR73FH ConditionAvailability Check Lead TimeRFQ Confirmation DocumentsDatasheet / photos by RFQ ShippingExport packing available
Auto-filled RFQ UR73FH

Click Request Quote and the part number is inserted into the inquiry form automatically.

Procurement Data

Key Product Information

Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.

Brand
GE
Primary Part Number
UR73FH
Product Type
Protection Relay
Series / Family
UR Series
Manufacturer
General Electric (GE Grid Solutions)
Country of Origin
US
Catalog Category
Relays & Protection
Operating Temp.
-20°C to +60°C
Model confirmed for inquiry UR73FH Send quantity, destination and urgency. The RFQ form keeps this part number attached.
Request Quote
Product Overview

GE UR73FH Universal Relay — Stop the Clock on Your Downtime

Every minute your protection system is offline, you’re bleeding money. A tripped substation, a failed relay module, an unplanned outage at 2 AM — we’ve been there. The GE UR73FH is one of the most widely deployed protection relay modules in the UR Series platform, and when it fails, you need a verified replacement on your bench today, not in six weeks. We stock it in Xiamen. We ship it globally. DHL or FedEx, door to door, with full export documentation.

This is not a listing. This is a lifeline.

URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345

Quick Technical Datasheet

Parameter Specification
Manufacturer General Electric (GE Grid Solutions)
Part Number / SKU UR73FH
Series UR Universal Relay Platform
Form Factor 19″ rack-mount chassis module
Protection Functions Overcurrent, differential, distance, frequency, voltage (config-dependent)
Communication Ethernet (IEC 61850 GOOSE/MMS), RS-485 Modbus RTU, DNP3
Power Supply Input 24–250 V DC / 100–240 V AC
Operating Temperature -20°C to +60°C
Mounting Panel / 19″ rack
Approvals CE, UL, IEC 60255
Weight ~400 g (module only)
Origin China (Xiamen stocking point)
Availability ✅ Ready to Ship

Troubleshooting & Replacement Tips

The UR73FH sits at the heart of your protection scheme. When it goes down, the failure mode matters — because a blind swap without checking configuration will cost you another outage. Here’s what ten years of field work has taught us:

Common Failure Indicators

  • SELF-TEST FAIL alarm on HMI: Usually points to internal watchdog timeout or corrupted firmware. Before condemning the module, attempt a cold reboot via the front panel reset. If the alarm persists across two power cycles, the module is suspect.
  • Loss of GOOSE messaging / IEC 61850 link drop: Check Ethernet port LEDs first. If the link is physically up but GOOSE is silent, the issue is often a firmware mismatch after a substation-wide upgrade. Confirm the UR73FH firmware version matches the IED configuration tool (EnerVista UR Setup) project file.
  • Relay output chatter or spurious trip: Inspect the binary output module contacts for carbon tracking. On older units, the BO module degrades before the main CPU card. Isolate the BO module first before pulling the entire chassis.
  • No communication on RS-485 Modbus port: Verify termination resistor jumper setting on the rear communication card. The UR platform requires the last device on the RS-485 bus to have the 120Ω terminator enabled — a frequently missed step during replacement.

Replacement Checklist — Do This Before You Power Up the New Unit

  • Export the full settings file from EnerVista UR Setup before removing the old module. Even a failed unit can often be read via USB if the CPU is partially functional.
  • Note the firmware version on the label of the outgoing unit. The replacement must run the same major firmware revision or be upgraded before commissioning. Mismatched firmware between UR modules in a multi-relay scheme causes protection coordination errors.
  • Check the order code on the module label — the UR73FH order code encodes the I/O configuration (number of CT inputs, VT inputs, binary I/O count). Confirm the replacement matches your wiring schedule exactly.
  • After installation, perform a full settings upload via EnerVista and run the relay’s built-in self-test sequence. Verify all CT/VT inputs read correctly before re-enabling protection.
  • Re-commission IEC 61850 GOOSE subscriptions. These are not stored in the relay settings file — they live in the substation SCD file and must be re-pushed to the IED after replacement.

Reliability in Harsh Conditions

The UR73FH was engineered for environments that would kill consumer-grade electronics. GE designed the UR platform to meet IEC 60255 and IEEE C37.90 standards — the benchmarks for protection relay robustness in real substation conditions.

Vibration resistance is rated to IEC 60255-21-1 Class 2, covering the mechanical shock and seismic stress common in industrial switchgear rooms and outdoor GIS installations. The conformal-coated PCBs resist condensation and humidity ingress, making the module suitable for coastal substations and tropical climates where relative humidity regularly exceeds 90%. Operating temperature range of -20°C to +60°C covers everything from Siberian winter substations to Middle Eastern desert installations without derating.

EMC immunity is tested to IEC 61000-4 series — fast transient burst, surge, conducted RF, and radiated immunity — because a protection relay that trips on electrical noise is worse than no relay at all. The UR73FH’s isolated power supply design rejects common-mode interference from adjacent high-voltage equipment, a critical feature in GIS and AIS substations where switching transients are a daily reality.

Units in our stock are stored in climate-controlled, ESD-safe conditions. Every module is individually bagged in anti-static packaging with desiccant. We don’t stack them in a warehouse and hope for the best.

Global Express Logistics

Our dispatch hub is in Xiamen, Fujian Province — one of China’s primary export ports with direct DHL and FedEx gateway access. Here’s exactly how your order moves:

  • Order confirmed → same-day or next-morning dispatch for in-stock units. Cut-off time for same-day processing is 15:00 CST.
  • DHL Express Worldwide: Xiamen to most of Europe, Middle East, and Southeast Asia in 3–5 business days. North America typically 4–6 business days.
  • FedEx International Priority: Available as an alternative carrier for destinations where FedEx has stronger last-mile coverage (e.g., remote US locations, parts of Latin America).
  • Export documentation package included with every international shipment: commercial invoice, packing list, certificate of origin (CO), and HS code declaration (8536.49). We prepare these in-house — no delays waiting on a freight forwarder.
  • Tracking number sent to your email within 2 hours of carrier pickup. Real-time tracking link provided.
  • Customs clearance support: We can provide additional documentation (material safety data, technical spec sheets, end-user declarations) on request to facilitate smooth customs clearance in regulated markets including the EU, UK, and Australia.

If your plant is down and you need the fastest possible routing, contact us directly before placing the order. We will check the next available flight departure from Xiamen and quote you the fastest door-to-door option.

Contact Information

📧 Email: [email protected]
📱 WhatsApp: +86 18359268345
🌐 Web: siemensplc.com
© 2026 siemensplc.com. All rights reserved.

Ready to quote

Send This Part Number to Sales

[email protected]
RFQ workflow

Confirmation Process

Quality workflow ->
01Model confirmation

We check the full part number, brand, series and visible nameplate information before quotation.

02Availability reply

Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.

03Packing & courier

DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.