Key Product Information
Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.
- Brand
- Siemens
- Primary Part Number
- 3ES7307-1EA01-0AA0
- Product Type
- PLC Power Supply Module
- Product Family
- Other series
- Country of Origin
- DE
- Catalog Category
- Power Supplies
- Operating Temp.
- 0 °C to +60 °C
- Warranty
- 12 months
SIEMENS 3ES7307-1EA01-0AA0 PS307 5A — Stop the Clock on Unplanned Downtime
Every minute a production line sits idle costs money. When the PS307 power supply fails, the entire S7-300 rack loses its 24 VDC backbone — CPUs, I/O modules, and communication processors all go dark simultaneously. The SIEMENS 3ES7307-1EA01-0AA0 is the direct OEM replacement for that exact failure scenario. We stock this module in Xiamen and ship same-day via DHL Express or FedEx International Priority. From order confirmation to your loading dock, typical transit time to Europe is 3–5 business days; Southeast Asia, 1–2 days.
This is not a compatible substitute or a refurbished pull. Every unit dispatched from our warehouse carries an intact Siemens holographic label, original packaging, and a traceable batch number. If your maintenance team needs to verify authenticity on arrival, the module’s firmware revision and production date are readable via STEP 7 or TIA Portal hardware diagnostics.
URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345
Quick Technical Datasheet
| Parameter | Value | Note |
|---|---|---|
| Order Number | 3ES7307-1EA01-0AA0 | ✅ Ready to Ship |
| Series | SIMATIC S7-300 | — |
| Input Voltage (AC) | 120 / 230 VAC, auto-ranging | 47–63 Hz |
| Input Current (max) | 0.45 A @ 230 VAC / 0.9 A @ 120 VAC | — |
| Output Voltage (DC) | 24 VDC ±1% | Stabilized, short-circuit proof |
| Output Current (rated) | 5 A | 120 W continuous |
| Output Power | 120 W | — |
| Backplane Bus Supply | 5 VDC / 0.8 A (internal) | For S7-300 rack logic |
| Inrush Current Limiting | Yes (NTC-based) | Protects upstream MCB |
| Isolation (Input→Output) | 4 kV AC, 1 min | EN 61131-2 compliant |
| Degree of Protection | IP20 | Panel-mount, DIN rail |
| Operating Temperature | 0 °C to +60 °C | Horizontal mounting |
| Storage Temperature | −40 °C to +70 °C | — |
| Relative Humidity | 10–95%, non-condensing | — |
| Dimensions (W × H × D) | 50 × 125 × 120 mm | 2-slot width on S7-300 rail |
| Weight | approx. 500 g | — |
| Mounting | S7-300 DIN rail, slot 1 (fixed) | — |
| Certifications | CE, UL, cUL, FM | — |
| Warranty | 12 months | From dispatch date |
Troubleshooting & Replacement Tips
The PS307 5A is a slot-1-fixed module — it does not participate in the S7-300 backplane data bus, so there is no address assignment or DIP-switch configuration required. However, field engineers frequently encounter the following failure modes and replacement pitfalls:
Fault Code SF / BF on CPU after PSU swap: This is almost always caused by residual capacitor charge on the backplane. After removing the failed PS307, wait 10 seconds before inserting the replacement. The CPU’s internal watchdog interprets a fast power cycle as a hardware fault and latches the SF LED. A clean power-on sequence clears it.
Output voltage reads 23.4 VDC under load: The 3ES7307-1EA01-0AA0 has a ±1% regulation spec. If you measure below 23.76 VDC at the 24 V terminals under full 5 A load, the unit is either counterfeit or has a degraded output stage. Genuine units hold 24.0 ± 0.24 VDC from 0 A to 5 A.
Replacement procedure (step-by-step):
- Switch off the upstream 230 VAC supply breaker. Verify with a multimeter — do not rely on the PSU’s green LED alone.
- Disconnect the 24 VDC load terminals (L+ and M) before removing the module to prevent arc flash on the output bus.
- Slide the module off the DIN rail by pressing the orange release tab at the bottom.
- Insert the replacement 3ES7307-1EA01-0AA0. Confirm the backplane connector seats fully — a partial engagement causes intermittent 5 VDC bus faults.
- Reconnect load terminals, restore AC supply, and verify 24.0 VDC output before powering the CPU.
- In STEP 7 / TIA Portal, perform a hardware configuration download if the CPU was replaced simultaneously. The PS307 itself requires no firmware or parameter download.
Common fault codes linked to PSU degradation: STOP mode with event ID 16#A503 (internal power supply fault), or repeated warm restarts logged in the CPU diagnostic buffer under event class 16#39 (power supply voltage out of tolerance). Both clear after a genuine PSU replacement.
Reliability in Harsh Conditions
The 3ES7307-1EA01-0AA0 is designed to IEC 61131-2 environmental class 3C3 / 3S2. In practice, this translates to the following verified operating margins:
Vibration: Tested to 10–58 Hz at 0.075 mm amplitude and 58–150 Hz at 1 g, per IEC 60068-2-6. The module’s internal transformer is potted with thermally conductive epoxy, eliminating winding movement under sustained vibration — a common failure point in lower-grade PSUs used in mobile machinery and compressor skids.
Shock: 15 g, 11 ms half-sine pulse per IEC 60068-2-27. The DIN rail locking mechanism is rated for the same shock envelope, preventing module ejection during seismic events or heavy equipment startup transients.
Thermal cycling: The output capacitor bank is rated for 105 °C, providing a calculated MTBF of >100,000 hours at 40 °C ambient. In steel mill and cement plant installations where ambient temperatures routinely reach 55 °C, this margin is the difference between a 2-year and a 5-year service interval.
Humidity and condensation: The PCB conformal coating meets IEC 60068-2-30 damp heat cycling. In coastal and tropical installations — common in Southeast Asian petrochemical plants — this prevents the creepage failures that destroy uncoated boards within 18 months.
EMC immunity: Burst immunity 2 kV (IEC 61000-4-4), surge immunity 1 kV line-to-line / 2 kV line-to-earth (IEC 61000-4-5). The module passes EN 55011 Class A conducted and radiated emissions, making it suitable for installation adjacent to variable-frequency drives without additional shielding.
Global Express Logistics
Our warehouse is located in Xiamen, Fujian Province — one of China’s primary export hubs with direct access to Xiamen Gaoqi International Airport (XMN) and Xiamen Port. This geography gives us consistent next-flight-out capability for DHL Express and FedEx International Priority shipments.
Typical transit times from Xiamen:
- Southeast Asia (Singapore, Thailand, Vietnam, Malaysia): 1–2 business days
- Middle East (UAE, Saudi Arabia, Qatar): 2–3 business days
- Europe (Germany, Netherlands, UK, Poland): 3–5 business days
- North America (USA, Canada, Mexico): 3–5 business days
- South America (Brazil, Chile, Argentina): 5–7 business days
- Africa (South Africa, Nigeria, Egypt): 4–6 business days
All shipments include: commercial invoice with HS code 8537.10 pre-filled, packing list, certificate of origin (Form E available for ASEAN destinations), and tracking number issued within 2 hours of dispatch. For orders requiring urgent customs clearance, we provide a detailed product description letter on company letterhead at no additional charge.
Export compliance: all Siemens automation products shipped from our facility comply with applicable export control regulations. We do not ship to sanctioned destinations.
Contact Information
📧 Email: [email protected]
💬 WhatsApp: +86 18359268345
🌐 Web: siemensplc.com
📍 Location: Xiamen, China
© 2026 siemensplc.com. All rights reserved.
Send This Part Number to Sales
Confirmation Process
We check the full part number, brand, series and visible nameplate information before quotation.
Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.
DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.