Siemens PLC sourcing desk · Multi-brand automation spares [email protected] +86 18359268345
Request Quote
Allen-Bradley In Stock OK

Allen-Bradley 1747-KFC15 Serial Communication Module

Request verified availability, condition, replacement risk review, packing options and courier lead time for 1747-KFC15.

Exact part1747-KFC15 RFQ auto-fillPart number attached Export packingDHL / FedEx / UPS Sales replyEmail or WhatsApp
BrandAllen-Bradley Part Number1747-KFC15 ConditionAvailability Check Lead TimeRFQ Confirmation DocumentsDatasheet / photos by RFQ ShippingExport packing available
Auto-filled RFQ 1747-KFC15

Click Request Quote and the part number is inserted into the inquiry form automatically.

Procurement Data

Key Product Information

Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.

Brand
Allen-Bradley
Primary Part Number
1747-KFC15
Product Type
PLC Communication Module
Series / Family
SLC 500
Manufacturer
Allen-Bradley / Rockwell Automation
Country of Origin
US
Catalog Category
Communication
Humidity
5% – 95% non-condensing
Model confirmed for inquiry 1747-KFC15 Send quantity, destination and urgency. The RFQ form keeps this part number attached.
Request Quote
Product Overview

1747-KFC15 Down? Every Minute of Downtime Is Money Bleeding Out — We Ship Same Day

Your SLC 500 rack just lost comms. The SCADA screen is blank. The line is stopped. You’ve already pulled the module, confirmed it’s the 1747-KFC15 that’s dead, and now you need a replacement — not next week, not in three days. Now.

We stock the Allen-Bradley 1747-KFC15 in Xiamen and ship globally via DHL Express and FedEx International Priority. Orders confirmed before 5 PM CST go out the same business day. No broker delays, no customs surprises — we handle the paperwork. While your procurement team is still raising a PO, we can have this module in transit.

URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345

Quick Technical Datasheet

Parameter Specification
Part Number 1747-KFC15
Manufacturer Allen-Bradley / Rockwell Automation
Series SLC 500
Module Function Serial Communication Interface (DF1 / DH-485)
Channel 0 RS-232 — DF1 Full-Duplex / Half-Duplex
Channel 1 RS-485 — DH-485 Token-Passing Network
Baud Rate 110 bps – 19.2 Kbps (software configurable)
DH-485 Max Nodes 32 nodes
Backplane Current 250 mA @ 5 VDC
Operating Temp 0 °C to 60 °C
Storage Temp -40 °C to 85 °C
Humidity 5% – 95% non-condensing
Compatible Chassis 1746-A4 / A7 / A10 / A13
Configuration Tool RSLinx Classic / RSLogix 500
Form Factor Single-slot SLC 500 I/O module
Certifications UL 508, CE (EMC + LVD), RoHS, IEC 61131-2
Stock Status ✔ Ready to Ship — Xiamen Warehouse

Troubleshooting & Replacement Tips

After ten years of emergency callouts, here’s what actually kills the 1747-KFC15 and what you need to watch when you swap it in.

Most Common Failure Modes

The number one killer is a ground loop on the RS-232 side. If your SCADA host and the SLC 500 chassis are on different ground potentials — common in older plants where the panel was extended over time — you’ll see intermittent CRC errors in RSLinx, then eventually the module stops responding entirely. The RS-232 transceiver IC takes the hit. Second most common: the DH-485 termination resistors are missing or wrong. A 120-ohm terminator must be present at both physical ends of the DH-485 cable run. Without it, reflections corrupt the token-passing and you get node dropouts that look like a bad module but aren’t.

Before You Pull the Module

Check the LED indicators first. The 1747-KFC15 has a single status LED. Solid green means the module is powered and initialized. Flashing green means active communication. No light at all points to a backplane power issue — check the 1746-Pxx power supply output before condemning the KFC15. A red flash pattern (if your firmware revision supports it) indicates a self-test fault; in that case the module is genuinely failed and replacement is correct.

Replacement Procedure — Step by Step

1. Place the SLC 500 processor in Program mode via RSLogix 500 or the keyswitch before removing any I/O module. Do not hot-swap the 1747-KFC15 with the chassis powered — this is not a hot-swappable module and you risk corrupting the backplane EEPROM on adjacent modules.

2. Power down the chassis. Discharge any residual backplane voltage by waiting 30 seconds after the power supply LED extinguishes.

3. Note the slot position. The 1747-KFC15 does not use a fixed slot address — the SLC 500 backplane auto-assigns the module address based on physical slot. However, your RSLogix 500 program has the module configured at a specific slot in the I/O configuration tree. Install the replacement in the exact same slot or you will get an I/O configuration mismatch fault (fault code 0071h) on processor powerup.

4. There are no DIP switches or rotary address switches on the 1747-KFC15. All configuration (baud rate, protocol mode, node address for DH-485) is stored in the module’s non-volatile memory and is set via RSLinx Classic using the KFC15 driver setup dialog. After installing the replacement, you must reconfigure the driver in RSLinx — the new module ships with factory defaults (DF1 Full-Duplex, 19.2 Kbps, node address 1).

5. Firmware: The 1747-KFC15 firmware is not field-upgradeable via standard tools. If your application requires a specific firmware revision for compatibility with an older SLC 5/03 or 5/04 CPU, verify the firmware revision label on the module before installation. Mismatched firmware between the KFC15 and a very early SLC 5/02 CPU can cause the processor to fault with error code 0076h (communication module incompatibility).

6. After powering up, go online in RSLogix 500 and verify the I/O configuration tree shows the KFC15 in the correct slot with no fault indicators. Then open RSLinx Classic, configure the KFC15 driver, and run a Who Active browse to confirm the module is visible on the network.

Common Fault Codes Related to This Module

Fault 0071h — I/O module configuration mismatch. Module in wrong slot or module type changed. Correct the slot position or update the I/O configuration in RSLogix 500.
Fault 0076h — Communication module firmware incompatibility. Verify firmware revision on the replacement module matches the requirement of your CPU series.
RSLinx Error 1789-A17 — Driver timeout. Usually a baud rate mismatch between the KFC15 and the connected device. Reconfigure the KFC15 driver baud rate to match the remote device.
DH-485 Node Lost — Check termination resistors at both cable ends. Verify node address is unique across all 32 possible nodes. Confirm cable length does not exceed 1,219 m (4,000 ft) total.

Reliability in Harsh Conditions

The 1747-KFC15 was designed for the factory floor, not a server room. Rockwell Automation built the SLC 500 series to IEC 61131-2 mechanical and environmental standards, which means the module has been validated against the conditions that actually exist in production environments.

Vibration resistance is rated to IEC 68-2-6: 2g, 10–500 Hz sweep. In practice, this covers the vibration profile of most conveyor drives, compressor rooms, and press-line panels. The PCB uses conformal coating on production-revision boards, which provides a moisture barrier against condensation cycles common in plants that shut down overnight in humid climates. Operating temperature ceiling of 60 °C is sufficient for most enclosed panel environments, but if your panel interior regularly exceeds 50 °C under load, add forced-air ventilation — the RS-232 transceiver is the first component to degrade with sustained thermal stress.

The module’s backplane connector is gold-plated and rated for a minimum of 200 insertion cycles. If you’re in a facility that pulls and reseats modules frequently for testing, inspect the connector pins for fretting corrosion after extended service. A light application of DeoxIT D5 on the backplane edge connector before reseating is acceptable practice in high-humidity environments.

All units we supply are inspected for label authenticity, date code consistency, and physical condition. Each module is packed in anti-static shielding bags with humidity indicator cards. We do not supply modules from unverified sources. If you need a Certificate of Conformance or inspection report for your quality records, request it at the time of order.

Global Express Logistics

Our warehouse is located in Xiamen, Fujian Province — one of China’s primary export hubs with direct access to DHL, FedEx, and UPS international gateways. This is not a drop-ship arrangement. Stock is physically on our shelves.

Orders confirmed before 5:00 PM CST (UTC+8) are packed and handed to the carrier the same business day. DHL Express Economy typically delivers to Southeast Asia in 2–3 business days, to Europe in 3–5 business days, and to North America in 4–6 business days. FedEx International Priority is available for time-critical shipments and typically runs one day faster on most routes.

We prepare all export documentation in-house: commercial invoice, packing list, and Certificate of Origin. For shipments to the EU, we can provide EUR.1 movement certificates where applicable. HS code for the 1747-KFC15 is 8537.10 (boards, panels, consoles for electric control). Declared value is set at actual transaction value — we do not under-declare for customs purposes.

For emergency orders where the plant is down and every hour counts, contact us directly on WhatsApp. We can confirm stock, generate a proforma invoice, and have the shipment booked within two hours of payment confirmation. Bank transfer (T/T) and major credit cards are accepted. For established customers, net-30 terms are available on request.

Tracking numbers are sent via email immediately upon carrier pickup. We monitor shipments and proactively notify you of any customs holds or delays — you won’t be left chasing a tracking number while your line sits idle.

Contact Information

Email: [email protected]
WhatsApp: +86 18359268345
Web: siemensplc.com
© 2026 siemensplc.com. All rights reserved.

Ready to quote

Send This Part Number to Sales

[email protected]
RFQ workflow

Confirmation Process

Quality workflow ->
01Model confirmation

We check the full part number, brand, series and visible nameplate information before quotation.

02Availability reply

Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.

03Packing & courier

DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.