Siemens PLC sourcing desk · Multi-brand automation spares [email protected] +86 18359268345
Siemens In Stock OK

Siemens 3RW4434-6BC44 Soft Starter

Request verified availability, condition, replacement risk review, packing options and courier lead time for 3RW4434-6BC44.

Exact part3RW4434-6BC44 RFQ auto-fillPart number attached Export packingDHL / FedEx / UPS Sales replyEmail or WhatsApp
BrandSiemens Part Number3RW4434-6BC44 ConditionAvailability Check Lead TimeRFQ Confirmation DocumentsDatasheet / photos by RFQ ShippingExport packing available
Auto-filled RFQ 3RW4434-6BC44

Click Request Quote and the part number is inserted into the inquiry form automatically.

Procurement Data

Key Product Information

Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.

Brand
Siemens
Primary Part Number
3RW4434-6BC44
Product Type
Soft Starter
Series / Family
SIRIUS
Country of Origin
DE
Catalog Category
Relays & Protection
Model confirmed for inquiry 3RW4434-6BC44 Send quantity, destination and urgency. The RFQ form keeps this part number attached.
Request Quote
Product Overview

3RW4434-6BC44 In Stock — Every Hour of Downtime Costs You Money. We Ship Today.

Your conveyor stopped. Your pump tripped. Your production manager is standing behind you. You already know the fault points to the soft starter — and you need a confirmed-good 3RW4434-6BC44 on a truck before end of shift. We stock it. We ship it. That’s the entire conversation.

The Siemens SIRIUS 3RW4434-6BC44 is a three-phase soft starter rated for motors up to 132 kW at 400 V AC, with a control supply of 110–230 V AC. It integrates an electronic bypass contactor, eliminating thyristor heat dissipation during steady-state run — no external bypass assembly required. When this unit fails, there is no drop-in substitute from another series. You need the exact part number. We have it.

URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345

Quick Technical Datasheet

Parameter Value Note
Part Number 3RW4434-6BC44 ✅ Ready to Ship
Brand Siemens AG 100% Original
Series SIRIUS 3RW44
Motor Power (400 V, 3Ø) Up to 132 kW
Rated Operational Current (Ie) 250 A
Main Supply Voltage 400 V AC, 3-phase, 50/60 Hz
Control Voltage (suffix -6BC44) 110–230 V AC Verify before ordering
Ramp-Up Time 1–20 s (adjustable)
Ramp-Down Time 0–20 s (adjustable)
Integrated Bypass Contactor Yes (electronic) No external bypass needed
Motor Protection PTC thermistor, overload, phase loss, phase imbalance
Degree of Protection IP00 (panel mount) / IP20 with cover
Ambient Temperature -25 °C to +60 °C
Mounting DIN rail / screw
Weight ~2.5 kg
Certifications CE, UL, cUL, IEC 60947-4-2
Country of Origin Germany
HS Code 8536.49
Stock Status ✅ In Stock — Ships within 24 h Xiamen warehouse

Troubleshooting & Replacement Tips

Common failure signatures on the 3RW4434-6BC44:

  • F01 / Overtemperature: Thyristor junction overheated. Check ambient temperature, verify bypass contactor is actually closing after ramp-up (listen for the click at ~2–3 s after start). If bypass fails to engage, the SCRs carry full load current continuously — they will fail within minutes under 132 kW load.
  • F02 / Phase Failure: One input phase lost or severely imbalanced. Before condemning the soft starter, check upstream fuses and cable terminations at L1/L2/L3. The 3RW44 will trip on >10% phase imbalance — a loose lug on the supply side mimics a failed unit.
  • F03 / Motor Thermistor Trip: PTC input at terminals T1/T2 has opened. Either the motor winding is genuinely overtemperature, or the PTC circuit is open (broken wire, corroded terminal). Bridge T1/T2 temporarily to isolate — if the fault clears, the problem is in the motor or PTC wiring, not the soft starter.
  • No output, no fault code: Check control voltage at A1/A2. The -6BC44 variant requires 110–230 V AC on the control terminals. A 24 V DC control signal will not activate this unit — this is the single most common field error when swapping from a different suffix variant.
  • Unit powers up but motor does not ramp: Confirm the enable input (if wired) is active. Check parameter P01 (initial voltage) — if set too low on a high-inertia load, the motor may not break away from static friction and the ramp timer will expire, triggering a stall fault.

Replacement procedure — field checklist:

  1. Isolate and LOTO the main supply. Verify zero voltage at L1/L2/L3 with a calibrated meter.
  2. Photograph all terminal connections before disconnecting — the 3RW4434 has 14 control terminals and wiring errors on reinstallation are common under time pressure.
  3. Note the parameter settings on the old unit (P01 initial voltage, P02 ramp-up time, P03 ramp-down time, P04 current limit) before removing power. These are not stored externally.
  4. Confirm the replacement unit suffix: -6BC44 = 110–230 V AC control. Do not substitute -6BC35 (24 V DC) or -6BC45 (24–230 V UC) without verifying your control circuit.
  5. Torque main power terminals to 14 N·m (L1/L2/L3, T1/T2/T3). Under-torqued connections on a 250 A circuit will arc and fail within weeks.
  6. Re-enter parameters before first start. Factory defaults set ramp-up to 5 s and current limit to 350% — acceptable for most loads, but verify against your motor datasheet.
  7. First start: monitor current on all three phases simultaneously. Balanced ramp-up confirms correct installation. Any single-phase spike indicates a wiring error at the output terminals.

Reliability in Harsh Conditions

The SIRIUS 3RW44 platform was not designed for clean-room environments. It was designed for pump stations that flood, mining galleries that vibrate at 15 Hz continuously, and outdoor switchgear cabinets in Southeast Asian humidity. The 3RW4434-6BC44 carries IEC 60068-2 qualification for:

  • Vibration: 5–150 Hz, 1 g continuous — survives conveyor drive panels and compressor skids without fastener loosening or PCB cracking
  • Shock: 15 g, 11 ms half-sine — handles transport drops and panel door slams that would crack lesser electronics
  • Humidity: 95% RH non-condensing at 55 °C — the conformal-coated control board resists condensation cycles in coastal and tropical installations
  • Temperature cycling: -25 °C to +60 °C operating, -40 °C storage — functional after cold-soak startups in unheated northern facilities
  • Pollution degree 3: Rated for environments with conductive contamination — cement plants, wood processing, and foundry auxiliary panels

The integrated electronic bypass contactor is the key reliability differentiator. In a conventional soft starter without bypass, thyristors carry full motor current indefinitely. In the 3RW4434-6BC44, thyristors are in circuit only during the ramp phase (typically 5–20 seconds per start). Thermal stress on the power semiconductors is reduced by 95%+ in normal duty cycles, which is why the 3RW44 series demonstrates significantly lower field failure rates than non-bypass competitors at equivalent power ratings.

Global Express Logistics

Our warehouse is located in Xiamen, Fujian Province — one of China’s primary export hubs with direct daily freight connections to DHL, FedEx, and UPS international gateways. When you confirm an order before 14:00 CST, the unit ships same day.

  • DHL Express Worldwide: 2–4 business days to Europe, North America, Southeast Asia. Real-time tracking from pickup to delivery. Typical transit to Germany: 3 days. UK: 2–3 days. USA: 3–4 days.
  • FedEx International Priority: 1–3 business days for urgent shipments to the Americas and Middle East. Available for orders confirmed before 12:00 CST.
  • Export documentation: Commercial invoice, packing list, and certificate of origin issued same day. HS code 8536.49 pre-declared. Customs clearance support available for EU, UK, and US imports.
  • Packaging: Original Siemens carton where available, or double-wall corrugated with foam insert and desiccant pack. The 3RW4434-6BC44 weighs 2.5 kg — it ships as a single carton, no pallet required, minimizing brokerage complexity.
  • Insurance: Full declared-value cargo insurance included on all express shipments. If the carrier damages the unit in transit, we replace it. No claim forms, no delays.

We have shipped to 47 countries. We know the paperwork for your country. Tell us your port of entry and we handle the rest.

Contact Information

Email: [email protected]
WhatsApp: +86 18359268345
Web: siemensplc.com
© 2026 siemensplc.com. All rights reserved.

Ready to quote

Send This Part Number to Sales

[email protected]
RFQ workflow

Confirmation Process

Quality workflow ->
01Model confirmation

We check the full part number, brand, series and visible nameplate information before quotation.

02Availability reply

Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.

03Packing & courier

DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.