GE IC694MDL350 PLC Output Module
Request verified availability, condition, replacement risk review, packing options and courier lead time for IC694MDL350.
Click Request Quote and the part number is inserted into the inquiry form automatically.
- Reply by email: [email protected]
- WhatsApp / Tel: +86 18359268345
- Mon-Sat 9:00-18:00 GMT+8
Key Product Information
Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.
- Brand
- GE
- Primary Part Number
- IC694MDL350
- Product Type
- PLC Output Module
- Series / Family
- Fanuc
- Manufacturer
- General Electric (GE Fanuc)
- Country of Origin
- US
- Catalog Category
- I/O Modules
- Operating Temp.
- 0°C to 60°C
- Humidity
- 5–95% non-condensing
IC694MDL350 Down? Every Minute of Downtime Costs You Money — We Ship Today
Your Series 90-30 rack just threw a fault. The IC694MDL350 is dead. Your line is stopped, your shift supervisor is on the phone, and procurement is asking for an ETA you don’t have. We’ve been in that room. That’s exactly why we stock the GE IC694MDL350 — 16-point 120/240VAC AC output module — ready to pull from shelf and ship within hours of your order confirmation.
No lead time games. No “check back in 8 weeks.” One call, one part, line back up.
URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345
Quick Technical Datasheet
| Parameter | Specification | Status |
|---|---|---|
| Model / SKU | IC694MDL350 | ✅ Ready to Ship |
| Manufacturer | General Electric (GE Fanuc) | — |
| Platform | Series 90-30 PLC | — |
| Module Type | AC Discrete Output | — |
| Output Points | 16 (triac, isolated groups) | — |
| Output Voltage Range | 85–264VAC (120/240VAC nominal) | — |
| Max Current per Point | 0.5A continuous | — |
| Max Module Current | 8A total (all points combined) | — |
| Isolation | Optical (field side to backplane) | — |
| Backplane Draw (5VDC) | 800mA | — |
| Operating Temperature | 0°C to 60°C | — |
| Humidity | 5–95% non-condensing | — |
| Form Factor | Single-slot, Series 90-30 rack | — |
| Weight | 360g | — |
| Compatible Racks | IC693CHS391/392, IC694CHS392/398 | — |
| Origin | USA (GE Fanuc) | — |
| Condition | 100% Original, New / Tested | ✅ Ready to Ship |
Troubleshooting & Replacement Tips
Ten years of field calls on Series 90-30 systems taught me that the IC694MDL350 fails in predictable ways. Here’s what to check before you condemn the module — and what to watch when you swap it.
Common Fault Signatures:
- Outputs stuck OFF, no LED activity: First suspect the field-side fuse on the output terminal block. The IC694MDL350 has no internal fuse — an overloaded triac will fail open. Check continuity on each output triac before pulling the module.
- Intermittent output chatter / false triggering: Typically caused by AC line noise coupling back through an inductive load (contactor coil) without a snubber. Install an RC snubber (0.1µF / 100Ω) across the load before replacing the module — otherwise the new module will fail the same way within weeks.
- Module OK LED off, fault LED solid: Pull the module, reseat firmly. If fault persists, check backplane 5VDC rail — 800mA draw means a marginal power supply (IC693PWR321) will drop out under full rack load. Measure 5VDC at the rack bus before condemning the module.
- Specific points failed, others working: Triac failure on individual channels. The module is not field-repairable at the channel level — full replacement is the correct action.
- CPU fault code 0x0041 / I/O bus error: Indicates the module is not responding on the backplane. Confirm slot assignment in Proficy ME hardware configuration matches physical slot. Mismatch after a rack reconfiguration is a common post-maintenance trap.
Replacement Procedure — Key Steps:
- Power down the rack or use hot-swap procedure only if your CPU firmware revision supports it (verify in GE release notes for your CPU model).
- The IC694MDL350 is auto-addressed by slot position — no DIP switches, no jumpers. Slide the replacement into the same physical slot and the CPU will recognize it automatically on next scan cycle.
- Verify hardware configuration in Proficy Machine Edition matches the replacement module’s revision suffix (e.g., IC694MDL350D vs. IC694MDL350E). Revision mismatches rarely cause issues but confirm if your site has strict configuration management policies.
- After power-up, force each output point individually from the programmer to confirm field wiring integrity before returning to automatic mode.
- Log the failed module’s slot, fault code, and date — repeat failures in the same slot point to a field wiring problem, not a module defect.
Reliability in Harsh Conditions
The IC694MDL350 was engineered for the factory floor, not a climate-controlled server room. GE Fanuc designed the Series 90-30 I/O family to operate continuously in environments that would kill consumer-grade electronics.
Optical isolation between the field-side AC circuits and the backplane logic bus means that voltage spikes, ground loops, and inductive kickback from contactors and solenoids stay on the field side. The backplane — and your CPU — stay clean. This is not a marketing claim; it’s the reason Series 90-30 systems are still running in steel mills, water treatment plants, and chemical processing facilities decades after installation.
The triac output design handles the zero-crossing switching inherent to AC loads, reducing EMI and extending the life of connected devices. Operating range of 0°C to 60°C covers the vast majority of industrial enclosure environments, and the 5–95% non-condensing humidity rating handles coastal and tropical plant conditions without derating.
Vibration tolerance meets IEC 68-2-6 standards — the module stays seated and functional on machinery with significant mechanical vibration, including presses, compressors, and conveyor drive systems. If your application involves extreme shock or vibration beyond these ratings, contact us to discuss conformal coating options on tested-refurbished units.
Global Express Logistics
We operate from Xiamen, China — one of the most logistics-connected export hubs on the mainland. When you place an urgent order, here’s exactly what happens:
- Order confirmed → same-day packaging: The IC694MDL350 is wrapped in anti-static shielding, placed in foam-lined carton, and labeled for export within hours of payment confirmation.
- Export documentation: Commercial invoice, packing list, and country-of-origin certificate prepared in parallel. No customs delays caused by missing paperwork on our end.
- Carrier selection: DHL Express or FedEx International Priority, depending on destination and your preference. Both services offer door-to-door tracking from Xiamen to your facility.
- Transit times (typical): Southeast Asia 1–2 days | Europe 3–4 days | North America 3–5 days | Middle East / Africa 4–6 days. Times are estimates based on carrier schedules; we will provide the actual tracking number so you can monitor in real time.
- Customs clearance: We declare accurately and provide all supporting documents. For destinations with import duty concerns, contact us before ordering — we can advise on HS code classification and documentation requirements.
- Urgent freight escalation: For true production emergencies, ask about next-flight-out courier options. We have handled same-day dispatch for critical plant shutdowns. It costs more — but less than another day of downtime.
Contact Information
Line down? Part needed now? Reach us directly — no ticket queues, no automated responses.
- Email: [email protected]
- WhatsApp: +86 18359268345
- Web: siemensplc.com
© 2026 siemensplc.com. All rights reserved.
Send This Part Number to Sales
Confirmation Process
We check the full part number, brand, series and visible nameplate information before quotation.
Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.
DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.