GE IC695PBM300CA PROFIBUS DP Master Module
Request verified availability, condition, replacement risk review, packing options and courier lead time for IC695PBM300CA.
Click Request Quote and the part number is inserted into the inquiry form automatically.
- Reply by email: [email protected]
- WhatsApp / Tel: +86 18359268345
- Mon-Sat 9:00-18:00 GMT+8
Key Product Information
Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.
- Brand
- GE (Emerson)
- Primary Part Number
- IC695PBM300CA
- Product Type
- PROFIBUS Communication Module
- Series / Family
- PACSystems
- Manufacturer
- GE / Emerson (PACSystems)
- Country of Origin
- US
- Catalog Category
- Communication
- Operating Temp.
- 0°C to +60°C
- Humidity
- 5% – 95% RH, non-condensing
GE IC695PBM300CA — Stop the Clock on Your Downtime. Ship Today from Xiamen.
Every minute your PROFIBUS network is down, the losses compound. A failed IC695PBM300CA doesn’t just drop one slave — it takes your entire DP network offline. Drives stop responding. Remote I/O goes dark. Your HMI throws a cascade of alarms you can’t clear until the master is back. We’ve seen it happen at 2 AM on a Sunday, and we’ve shipped the replacement by Monday morning. That’s exactly what this page is for.
We stock the GE IC695PBM300CA PROFIBUS DP Master Module for PACSystems RX3i at our Xiamen warehouse. Verified original hardware. Same-day dispatch on confirmed orders. DHL/FedEx express to your plant floor — anywhere in the world.
URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345
Quick Technical Datasheet
| Parameter | Specification | Status |
|---|---|---|
| Part Number | IC695PBM300CA | ✅ Ready to Ship |
| Manufacturer | GE / Emerson (PACSystems) | |
| Series | PACSystems RX3i (IC695 family) | |
| Module Function | PROFIBUS DP Master (Class 1) | |
| Protocol Standard | EN 50170 / IEC 61158 PROFIBUS DP | |
| Max DP Slaves | 125 devices per network segment | |
| Baud Rate Range | 9.6 kbps – 12 Mbps (auto-negotiated) | |
| Bus Connector | DB9 female (9-pin D-sub), pin 3 = B-line, pin 8 = A-line | |
| Backplane Interface | RX3i Universal Backplane (IC695CHS007/012/016) | |
| Configuration Tool | GE Proficy Machine Edition (PME) 8.x+ | |
| Operating Temperature | 0°C to +60°C | |
| Storage Temperature | −40°C to +85°C | |
| Humidity | 5% – 95% RH, non-condensing | |
| Weight | ~400 g | |
| Certifications | CE, UL, cUL | |
| Revision | CA (mature, field-validated release) | |
| Origin | United States |
Troubleshooting & Replacement Tips
After ten years of emergency callouts, here’s what actually goes wrong with the IC695PBM300CA and what you need to know before you swap it out.
Common Failure Signatures
- Fault Code 0x0083 / Module Not Responding: The RX3i CPU logs this when the PBM300CA stops heartbeating on the backplane. Nine times out of ten it’s a hard module failure — not a network issue. Swap the module first before chasing cable faults.
- All Slaves Offline Simultaneously: If every DP slave drops at the same instant (not sequentially), the master has failed or lost backplane power. Check the module’s STATUS LED — solid red with no green activity means the module is dead.
- Intermittent Slave Dropouts at High Baud Rate: If you’re running 12 Mbps and seeing random slave losses, the CA revision can be sensitive to cable stub lengths exceeding 0.3 m. Drop to 1.5 Mbps temporarily to confirm it’s a cable topology issue, not a module fault.
- PME Hardware Config Mismatch After Swap: If the replacement module triggers a Hardware Mismatch fault in PME, verify the firmware revision matches what’s stored in the project. Download the hardware configuration again from PME after seating the new module.
- Bus Termination Errors: The IC695PBM300CA does not have internal bus termination. Confirm that the first and last physical nodes on your PROFIBUS segment have termination resistors enabled (typically via the connector’s built-in termination switch). Missing termination at 1.5 Mbps+ will cause erratic slave behavior within minutes of startup.
Step-by-Step Hot-Swap Procedure
- Place the RX3i CPU in STOP mode. Do not power down the entire rack if other modules are live — the RX3i backplane supports module-level isolation.
- Document the current slot position. The IC695PBM300CA must return to the same slot number — the PROFIBUS network configuration in PME is slot-bound.
- Disconnect the DB9 PROFIBUS cable. Label it before removal if multiple cables are present.
- Release the module latch and extract the IC695PBM300CA. Inspect the backplane connector pins for damage or corrosion.
- Seat the replacement module firmly until the latch clicks. Verify the module’s PWR LED illuminates green within 5 seconds.
- Reconnect the DB9 cable. Confirm termination is correct at both ends of the segment.
- In PME, go to Hardware Configuration → Download to Controller. This re-pushes the PROFIBUS slave GSD configurations to the new module.
- Set CPU to RUN mode. Monitor the PROFIBUS diagnostic screen in PME for 60 seconds — all configured slaves should transition from Not Responding to OK within two bus scan cycles.
- If any slave remains offline, check that slave’s node address matches the GSD configuration. The IC695PBM300CA does not auto-assign node addresses — each slave must have its rotary switch or DIP switch set to the address defined in PME.
Firmware Note: The CA revision firmware is not field-upgradeable via standard PME procedures. If your project requires a specific firmware version, confirm the revision label on the module’s side sticker before installation. Mixing CA and CB/CC revisions in a redundant master setup is not supported.
Reliability in Harsh Conditions
The IC695PBM300CA was designed for the kind of environments where automation hardware earns its keep — not climate-controlled server rooms, but foundry floors, offshore platforms, and chemical processing units where the air smells like something you’d rather not breathe.
The module’s conformal-coated PCB provides a measurable barrier against airborne contaminants: sulfur compounds, cutting fluid mist, and humidity spikes that would corrode an unprotected board within months. In our handling and inspection process, we verify that the coating is intact on every unit before it leaves our warehouse — a cracked or peeling conformal coat on a used module is an immediate rejection criterion.
Vibration tolerance is rated to IEC 60068-2-6 standards, covering the 5–150 Hz frequency range at 1 g acceleration — sufficient for most pump skids, compressor stations, and conveyor drive panels. For applications with severe shock loads such as press brakes or stamping lines, ensure the RX3i rack is mounted on vibration-isolating standoffs rather than directly to the machine frame.
Thermal cycling is where many counterfeit or refurbished modules fail first. Solder joint fatigue from repeated heat-up/cool-down cycles causes intermittent backplane contact faults that are nearly impossible to diagnose without swapping the module. Our stock is sourced from controlled environments with documented storage history — not pulled from decommissioned equipment and re-labeled.
Operating ceiling of +60°C is adequate for most panel enclosures with proper ventilation. If your cabinet ambient exceeds 50°C, add forced-air cooling before the module, not after — thermal damage is cumulative and irreversible.
Global Express Logistics
Our dispatch hub is in Xiamen, China — one of the most connected export ports in Asia, with direct DHL and FedEx gateway access. Here’s how a typical emergency order moves:
- Order Confirmed (Day 0): Payment or PO received before 15:00 CST triggers same-day pick, inspection, and ESD packaging. You receive a tracking number by 18:00 CST.
- Export Clearance (Day 0–1): Commercial invoice, packing list, and HS code documentation (HS 8537.10) prepared and submitted. No delays from incomplete paperwork — we handle this daily.
- DHL Express / FedEx International Priority (Day 1–3): Transit time to most of Europe, North America, Southeast Asia, and the Middle East is 2–4 business days from Xiamen. Australia and South America typically 3–5 days.
- Customs Clearance Support: We provide accurate declared values and product descriptions that clear customs without holds. If your country requires an import license for automation components, notify us at order time — we’ll adjust documentation accordingly.
- Delivery Confirmation: Full tracking shared via email and WhatsApp. We monitor shipments actively and flag any carrier delays before they become your problem.
For orders requiring freight forwarding to a 3PL, bonded warehouse, or project site in a remote location, contact us directly — we’ve shipped to offshore rigs, mine sites, and remote substations. We know how to make it work.
Contact Information
📧 Email: [email protected]
📱 WhatsApp: +86 18359268345
🌐 Web: siemensplc.com
© 2026 siemensplc.com. All rights reserved.
Send This Part Number to Sales
Confirmation Process
We check the full part number, brand, series and visible nameplate information before quotation.
Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.
DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.