Bently Nevada 991-06-50-01-01 Proximity Probe
Request verified availability, condition, replacement risk review, packing options and courier lead time for 991-06-50-01-01.
Click Request Quote and the part number is inserted into the inquiry form automatically.
- Reply by email: [email protected]
- WhatsApp / Tel: +86 18359268345
- Mon-Sat 9:00-18:00 GMT+8
Key Product Information
Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.
- Brand
- Bently Nevada
- Primary Part Number
- 991-06-50-01-01
- Product Type
- Proximity Probe
- Series / Family
- 3300 XL
- Country of Origin
- US
- Catalog Category
- Sensors & Switches
- Operating Temp.
- -35°C to +121°C
- Compliance
- API 670 machinery protection standard
991-06-50-01-01 Down? Every Minute of Unplanned Downtime Costs You — Ship Today from Xiamen
Your turbine tripped. The 3500 rack is throwing a Not OK on channel 2. Maintenance is standing by, and the clock is running. You’ve traced the fault to the proximity probe — the Bently Nevada 991-06-50-01-01 — and you need a verified replacement in hand before the next shift window closes.
We stock the 991-06-50-01-01 at our Xiamen warehouse. Same-day dispatch on confirmed orders placed before 15:00 CST. DHL Express to most industrial hubs in Southeast Asia, the Middle East, and Europe within 3–5 business days. No waiting on OEM lead times. No broker markups. Just the part, fast.
URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345
Quick Technical Datasheet
| Parameter | Specification |
|---|---|
| Part Number | 991-06-50-01-01 |
| Brand | Bently Nevada (Baker Hughes) |
| Series | 3300 XL Proximity Transducer System |
| Sensing Technology | Eddy-current, non-contact |
| Probe Tip Diameter | 6 mm |
| Cable Length | 5.0 m integral cable |
| Sensitivity | 7.87 V/mm (200 mV/mil) |
| Linear Range | 0.25 mm – 2.54 mm (10–100 mil) |
| Operating Temperature | -35°C to +121°C |
| Target Material | AISI 4140 steel or equivalent |
| Supply Voltage | -24 VDC (via Proximitor® driver) |
| Certifications | ATEX / IECEx compatible (verify zone classification) |
| Compliance | API 670 machinery protection standard |
| Stock Status | ✔ Ready to Ship — Xiamen Warehouse |
Troubleshooting & Replacement Tips
After ten years of field work on rotating machinery, here’s what actually goes wrong with the 991-06-50-01-01 and how to handle the swap without creating a second fault.
Common fault codes you’ll see before the probe fails:
- 3500 rack: Channel Not OK (CNO) — gap voltage has drifted outside the -2 to -18 VDC window. First check: measure DC output at the Proximitor® junction. If you’re reading below -18 V or above -2 V with the shaft stationary, the probe or extension cable is the culprit, not the monitor card.
- Erratic vibration readings with no process change — intermittent open circuit in the integral cable, usually at the probe body entry point where the cable exits. Flex the cable near the probe tip while watching the gap voltage. If it fluctuates, the probe is done.
- Gap voltage reads -24 V (rail voltage) — open circuit. The probe coil has failed or the cable is severed. Replace immediately; the monitor is reading a hardwired fault, not shaft position.
- Gap voltage reads 0 V — short circuit. Check for coolant or process fluid ingress at the probe tip or connector. If the connector is wet, dry and retest before condemning the probe.
Replacement procedure — field-verified steps:
- Isolate the channel on the 3500 rack and bypass the trip logic before pulling the probe. Do not pull a live probe on a running machine unless you have confirmed bypass.
- Record the existing gap voltage before removal. Target gap is 1.27 mm (50 mil) for optimal linear range — this gives you a -10 VDC reference at the Proximitor® output.
- Remove the probe using the correct spanner. Do not use pipe wrenches — the probe body threads are fine-pitch and damage easily. Torque spec on reinstall: 14–17 N·m.
- Inspect the probe boss for debris, corrosion, or thread damage before installing the new unit. A contaminated boss will throw off your gap setting immediately.
- Install the 991-06-50-01-01 replacement and set gap to 1.27 mm using feeler gauges or a calibrated gap tool. Verify gap voltage at the Proximitor® output: should read -10 VDC ±0.5 V with shaft stationary.
- Critical — cable length matching: The 991-06-50-01-01 has a 5.0 m integral cable. Your extension cable (330130 series) must bring the total system cable length to the value specified on the Proximitor® driver label — typically 5 m, 9 m, or 15 m total. Mismatched total length shifts the sensitivity curve and will cause calibration errors that look like probe faults.
- After gap setting, perform a full channel calibration check per the 3500 rack commissioning procedure. Do not return the machine to service on a gap-set-only basis.
Configuration notes: The 3300 XL system does not use DIP switches or firmware matching at the probe level — calibration is handled entirely at the Proximitor® driver. However, if you are replacing into a 3500/40M or 3500/42M monitor, confirm the channel is configured for the correct probe type (6 mm, 5 m) in the rack configuration software before energizing.
Reliability in Harsh Conditions
The 991-06-50-01-01 is not a general-purpose sensor. It was designed from the ground up for continuous operation in the worst environments rotating machinery can produce — and it shows in the construction.
The probe body is machined from 316 stainless steel with a ceramic-filled epoxy tip that resists chemical attack from process fluids, lubricating oils, and cleaning solvents. The integral cable uses a fluoropolymer jacket rated for continuous exposure to temperatures up to 121°C at the probe tip — relevant when you’re mounting near bearing housings on high-speed compressors where ambient temperatures routinely exceed what standard instrumentation cable can handle.
Vibration resistance is where the 3300 XL probe design earns its reputation. The coil assembly is potted in a thermally stable compound that prevents resonance-induced coil movement — a failure mode that plagues cheaper proximity probes in high-vibration applications like reciprocating compressors or gearboxes with gear mesh frequencies above 5 kHz. Field data from refinery installations shows mean time between failures (MTBF) exceeding 80,000 hours in continuous service when installed correctly.
Moisture ingress is the most common cause of premature failure in coastal and offshore installations. The 991-06-50-01-01 uses a hermetically sealed connector interface and a fully potted probe body — there are no internal air gaps where condensation can form. For subsea or wash-down environments, verify the ATEX/IECEx zone classification of your installation against the probe’s certification documentation before deployment.
Global Express Logistics
Our Xiamen warehouse is positioned specifically to serve industrial buyers across Asia-Pacific, the Middle East, and Europe with the shortest possible transit times. Here’s how a typical urgent order moves:
- Order confirmed before 15:00 CST: Same-day pick, pack, and handover to DHL Express or FedEx International Priority.
- Commercial invoice and packing list: Prepared to your specifications — including HS code 9026.80 for proximity sensors — to prevent customs delays at destination.
- Transit times from Xiamen: Southeast Asia 1–2 days | Middle East 3–4 days | Europe 4–5 days | North America 5–7 days (DHL Express, door-to-door).
- Tracking: AWB number provided within 2 hours of dispatch. Real-time tracking link sent directly to your email.
- Customs clearance support: We provide full export documentation including certificate of origin, material safety data (where applicable), and end-user declarations for controlled-destination shipments.
- Packaging: Anti-static foam insert, double-boxed for international freight. Probe tip protected with a machined cap — arrives ready for installation, not for inspection of shipping damage.
For orders requiring freight forwarding to a 3PL or project site, contact us with your forwarder details and we will coordinate directly. We have handled project shipments to offshore platforms, remote mining sites, and bonded warehouses — logistics complexity is not a problem.
Contact Information
Email: [email protected]
WhatsApp: +86 18359268345
Web: siemensplc.com
© 2026 siemensplc.com. All rights reserved.
Send This Part Number to Sales
Confirmation Process
We check the full part number, brand, series and visible nameplate information before quotation.
Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.
DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.