Siemens PLC sourcing desk · Multi-brand automation spares [email protected] +86 18359268345
GE In Stock OK

GE IC695CPE400-AAAA PLC CPU Module

Request verified availability, condition, replacement risk review, packing options and courier lead time for IC695CPE400-AAAA.

Exact partIC695CPE400-AAAA RFQ auto-fillPart number attached Export packingDHL / FedEx / UPS Sales replyEmail or WhatsApp
BrandGE Part NumberIC695CPE400-AAAA ConditionAvailability Check Lead TimeRFQ Confirmation DocumentsDatasheet / photos by RFQ ShippingExport packing available
Auto-filled RFQ IC695CPE400-AAAA

Click Request Quote and the part number is inserted into the inquiry form automatically.

Procurement Data

Key Product Information

Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.

Brand
GE
Primary Part Number
IC695CPE400-AAAA
Product Type
PLC CPU Module
Series / Family
PACSystems
Country of Origin
US
Catalog Category
PLCs & Controllers
Operating Temp.
0°C to 60°C
Model confirmed for inquiry IC695CPE400-AAAA Send quantity, destination and urgency. The RFQ form keeps this part number attached.
Request Quote
Product Overview

GE IC695CPE400-AAAA: Stop the Bleeding — Get Your RX3i CPU Back Online Today

Every minute your PACSystems RX3i rack sits idle, the losses compound. A failed IC695CPE400-AAAA CPU module doesn’t just halt one machine — it can cascade across an entire production cell, triggering downstream stoppages, missed SLAs, and penalty clauses that dwarf the cost of the part itself. We stock the IC695CPE400-AAAA at our Xiamen warehouse specifically because we’ve seen what a 72-hour lead time from a slow distributor costs a plant manager at 2 AM.

This is not a listing page. This is a recovery tool. If your RX3i CPU is down, you need a verified, tested, original GE IC695CPE400-AAAA in your hands — not a quote, not a backorder confirmation, not a “we’ll check availability” email. We ship same-day on orders confirmed before 15:00 CST. DHL Express and FedEx International Priority are our default carriers. Most destinations in Southeast Asia, the Middle East, and Europe receive delivery within 48–72 hours of dispatch.

URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345

Quick Technical Datasheet

Parameter Specification
Part Number IC695CPE400-AAAA
Brand / Manufacturer GE (General Electric Automation)
Platform / Series PACSystems RX3i
Processor 1.1 GHz Intel Celeron M
User RAM 64 MB
Flash Storage 64 MB
Ethernet Ports 2 × 10/100 Mbps (SRTP, Modbus TCP, EGD)
Serial Ports 1 × RS-232, 1 × RS-485
USB 1 × USB 2.0
Compatible Backplanes IC695CHS007 / IC695CHS012 / IC695CHS016
Operating Temperature 0°C to 60°C
Programming Software Proficy Machine Edition (PME) 9.0+
Certifications UL, CE, cUL
Stock Status ✔ Ready to Ship – Xiamen Warehouse

Troubleshooting & Replacement Tips

After handling dozens of IC695CPE400-AAAA field swaps, these are the failure modes and gotchas that actually bite engineers on-site:

1. CPU Fault LED solid red — don’t assume the CPU is dead. Before condemning the module, check the backplane slot contacts for oxidation and reseat the CPU firmly. A partial seating on the IC695CHS012 backplane is a known cause of spurious CPU faults, especially in high-vibration environments. Clean the gold fingers with isopropyl alcohol (99%) and a lint-free swab before installing the replacement.

2. Firmware version mismatch after swap. The IC695CPE400-AAAA ships from GE with a specific firmware baseline. If your replacement unit carries a different firmware revision than the failed unit, PME may throw a “CPU firmware mismatch” error on first connect. Resolve this by connecting via USB first (not Ethernet), opening the Hardware Configuration in PME, and performing a firmware update before downloading the application program. Do not attempt to download the program before firmware is matched — this can corrupt the flash.

3. IP address conflict on dual-Ethernet ports. The IC695CPE400-AAAA has two independent Ethernet ports (LAN1 and LAN2). After replacement, both ports default to DHCP unless a static IP was stored in the CPU’s non-volatile memory. If your plant network uses static addressing, you must reconfigure both ports via the PME Hardware Configuration tool before going live. Failure to do this is the #1 cause of “CPU not found on network” calls we receive post-swap.

4. Battery-backed RAM loss. The IC695CPE400-AAAA uses a lithium coin cell (CR2032) to retain the program in RAM during power loss. A replacement unit’s battery may be partially discharged from shelf storage. Replace the battery before commissioning, and verify the battery voltage is above 2.8V using the CPU diagnostics in PME. A low battery will not prevent operation but will cause program loss on the next power cycle.

5. Fault table entries after first power-up. It is normal for a freshly installed IC695CPE400-AAAA to log several fault table entries on first boot — particularly “I/O module not found” faults if the I/O configuration was stored in the old CPU’s flash. Clear the fault table, perform a hardware configuration download, and cycle power. If faults persist after a clean download, check each I/O module’s slot assignment against the hardware configuration.

Common Fault Codes:

  • 0x0001 – CPU Hardware Fault: Usually a backplane seating issue or failed internal power rail. Reseat first; replace if fault persists after reseating.
  • 0x0010 – Memory Parity Error: Indicates RAM corruption. A full memory clear (via PME > Target > Clear) followed by a fresh program download resolves this in most cases.
  • 0x0080 – Ethernet Port Fault: Check cable integrity and switch port configuration. Autonegotiation failures between the CPU and managed switches are common — force 100 Mbps / Full Duplex on the switch port if autoneg fails.
  • 0x0200 – Firmware Checksum Error: The firmware image in flash is corrupted. Perform a firmware recovery via USB using the GE Firmware Upgrade Utility before attempting any program download.

Reliability in Harsh Conditions

The IC695CPE400-AAAA was engineered for environments where consumer-grade electronics simply fail. GE’s PACSystems RX3i platform was designed to IEC 61131-2 environmental standards, and the CPE400 CPU module reflects that pedigree in every design decision.

The module’s conformal-coated PCB provides protection against humidity and condensation — a critical feature in coastal industrial facilities, paper mills, and food processing plants where ambient moisture regularly exceeds 85% RH. The coating prevents the dendritic growth and corrosion that kills unprotected boards within months in these environments.

Vibration resistance is validated to IEC 60068-2-6 (sinusoidal) and IEC 60068-2-64 (random), covering the frequency ranges typical of compressor rooms, press lines, and mobile equipment installations. The backplane connector system uses a high-retention-force design that maintains electrical contact under continuous vibration loads that would loosen standard DIN-rail connectors.

Thermal management is handled through a combination of passive heatsinking and forced convection from the backplane’s internal airflow path. The 0°C to 60°C operating range covers the vast majority of industrial cabinet installations, and the module has demonstrated reliable operation at the upper limit in extended thermal cycling tests. For installations in high-ambient environments (e.g., outdoor cabinets in tropical climates), ensure cabinet cooling maintains internal temperature below 55°C with a 5°C margin.

EMC immunity is certified to EN 61000-4 series standards, including 4 kV contact discharge (ESD), 2 kV/m radiated immunity, and 2 kV fast transient/burst. In practice, this means the IC695CPE400-AAAA will continue operating correctly in the presence of VFD switching noise, arc welding interference, and high-voltage bus switching — the real-world EMC threats that cause nuisance resets in lesser hardware.

Global Express Logistics

Our Xiamen warehouse is positioned specifically for rapid international dispatch. Xiamen Gaoqi International Airport (XMN) offers direct cargo connections to major hubs in Europe, the Middle East, Southeast Asia, and North America, enabling us to move parts faster than suppliers located in inland Chinese cities.

Our standard export process for the IC695CPE400-AAAA:

  • Order confirmation before 15:00 CST: Same-day packing and export documentation preparation.
  • Export documentation: Commercial invoice, packing list, and certificate of origin prepared to destination country requirements. For EU shipments, EUR.1 movement certificates are available on request.
  • Carrier selection: DHL Express (default for most destinations), FedEx International Priority (preferred for North America and select Middle East routes), or TNT/UPS on request. We select the fastest available service for your destination at time of booking.
  • Typical transit times: Southeast Asia 1–2 days, Middle East 2–3 days, Europe 2–4 days, North America 3–5 days.
  • Tracking: AWB number provided within 2 hours of carrier pickup. Real-time tracking link sent via email and WhatsApp.
  • Customs clearance support: HS code 8537.10 declared. We provide all documentation required for customs clearance in your country. For destinations with import licensing requirements for industrial control equipment, contact us in advance to confirm compliance.

For genuinely critical situations — plant down, safety system offline, production line stopped — contact us directly on WhatsApp. We will personally coordinate with the carrier to expedite handling and provide updates at every stage.

Contact Information

📧 Email: [email protected]
📱 WhatsApp: +86 18359268345
🌐 Web: siemensplc.com

© 2026 siemensplc.com. All rights reserved.

Ready to quote

Send This Part Number to Sales

[email protected]
RFQ workflow

Confirmation Process

Quality workflow ->
01Model confirmation

We check the full part number, brand, series and visible nameplate information before quotation.

02Availability reply

Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.

03Packing & courier

DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.