Yokogawa NCP00039-E Contact Output Module
Request verified availability, condition, replacement risk review, packing options and courier lead time for NCP00039-E.
Click Request Quote and the part number is inserted into the inquiry form automatically.
- Reply by email: [email protected]
- WhatsApp / Tel: +86 18359268345
- Mon-Sat 9:00-18:00 GMT+8
Key Product Information
Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.
- Brand
- Yokogawa
- Primary Part Number
- NCP00039-E
- Product Type
- DCS Contact Output Module
- Series / Family
- CENTUM VP
- Manufacturer
- Yokogawa Electric Corporation
- Country of Origin
- JP
- Catalog Category
- I/O Modules
- Operating Temp.
- 0°C to 55°C
- Humidity
- 5% to 95% RH non-condensing
Yokogawa NCP00039-E — Stop the Clock on Your Downtime. Ship Today from Xiamen.
Your CENTUM VP field control station just threw a fault. The contact output module is dead. Every minute the line sits idle, you’re bleeding money — production loss, penalty clauses, maintenance overtime. You don’t need a catalog. You need the part, now.
The Yokogawa NCP00039-E is a relay contact output module engineered for the CENTUM VP and CS 3000 DCS platforms. We stock it in Xiamen. We ship it today via DHL Express. Most destinations in Asia receive it within 24–48 hours. Europe and the Americas: 3–5 business days. No minimum order. No bureaucratic lead times.
URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345
Quick Technical Datasheet
| Parameter | Specification |
|---|---|
| Part Number | NCP00039-E |
| Manufacturer | Yokogawa Electric Corporation |
| Module Type | Contact Output Module (Relay Dry Contact) |
| Compatible DCS | CENTUM VP / CS 3000 (FCS nest-mount) |
| Output Type | Relay contact — Form A (NO) / Form C (NO+NC) |
| Output Channels | 16 channels per module |
| Contact Rating | 250 VAC / 2 A resistive; 30 VDC / 2 A |
| Isolation | Channel-to-channel and channel-to-bus optical isolation |
| Bus Interface | V-net / ER Bus (CENTUM VP internal system bus) |
| Mounting | Nest-mount, FCS I/O slot (NCP-series slot) |
| Operating Temperature | 0°C to 55°C |
| Storage Temperature | -25°C to 70°C |
| Humidity | 5% to 95% RH non-condensing |
| Power Consumption | ≤ 8 W (from nest backplane) |
| Certifications | CE, UL, ATEX (zone 2 with appropriate barrier) |
| Firmware | Matches CENTUM VP R5.xx / R6.xx — confirm revision before ordering |
| Stock Status | ✅ Ready to Ship — Xiamen Warehouse |
Troubleshooting & Replacement Tips
Ten years of field work teaches you that most NCP00039-E failures fall into three categories. Know them before you pull the card.
1. Relay Coil Burnout (Most Common)
Symptom: CENTUM VP System View shows DO channel in fault state; field device does not actuate despite command. Alarm code IOM-E1042 or IOM-E1043 appears in the FCS event log. Root cause is almost always inductive load switching without adequate surge suppression on the field side — solenoid valves and motor contactors are the usual culprits. Before installing the replacement, fit RC snubbers or MOVs across every inductive load on that module’s channels. Skipping this step will kill the new card within weeks.
2. Bus Communication Loss (Intermittent Fault)
Symptom: Module appears in System View but channels toggle between normal and IOP (Input/Output Problem) state. Error code IOM-E2001. This is rarely the module itself — check the nest backplane connector pins for oxidation and the V-net cable termination resistors (120 Ω) at both ends of the segment. Re-seat the module with power off. If the fault persists after reseating, swap the module to a known-good nest slot to isolate nest vs. module fault.
3. Firmware Mismatch After Replacement
Symptom: Module powers up, LED status shows normal, but CENTUM VP Builder reports Module Type Mismatch or refuses to download. This happens when the replacement card carries a different hardware revision suffix. The -E suffix denotes a specific hardware revision; earlier NCP00039 (no suffix) or NCP00039-D cards may not be recognized by R6.xx FCS firmware without a firmware patch. Always cross-check the FCS firmware version in System View → Station Properties before ordering.
Replacement Procedure (Condensed Field Steps):
- Place the affected I/O module in Manual mode via CENTUM VP HIS before removal — do not pull a live card without placing outputs in safe state first.
- Power down the nest slot (use the nest slot breaker if available; otherwise power down the entire FCS — confirm with your safety plan).
- Note the slot address (nest number + slot number) from the label on the existing module before extraction.
- Insert the NCP00039-E into the identical slot. The module is keyed; it will not seat in an incompatible slot type.
- Power up. CENTUM VP FCS will auto-recognize the module within 30–60 seconds if firmware matches.
- Verify all 16 channel LEDs cycle through self-test (green flash sequence).
- Return channels from Manual to Auto mode one by one. Confirm field device response before releasing to process.
- Log the replacement in your maintenance management system with the new module serial number for traceability.
No DIP switch or rotary address setting is required on the NCP00039-E — slot address is auto-assigned by the FCS nest backplane. This is a common misconception from engineers migrating from older CENTUM CS 3000 hardware where manual addressing was required.
Reliability in Harsh Conditions
Process plants are not server rooms. The NCP00039-E is built for environments that would destroy consumer-grade electronics within days.
The module’s PCB is conformally coated to IPC-CC-830 standard, providing resistance to condensation, salt fog, and airborne chemical contaminants common in petrochemical and coastal installations. Relay contacts are gold-flashed on silver alloy — this combination maintains low contact resistance even after years of low-current switching cycles where pure silver contacts would sulfide and fail.
Vibration resistance is validated to IEC 60068-2-6: 10–150 Hz, 1 g continuous. In practice, this covers the vibration spectrum generated by large reciprocating compressors and centrifugal pumps mounted on the same structural steel as the control room. The module’s nest-mount mechanical design eliminates the connector fretting failures seen in card-edge designs under sustained vibration.
Thermal cycling performance is validated to IEC 60068-2-14: -25°C to +70°C, 100 cycles. The module’s power supply section uses industrial-grade capacitors rated for 105°C, not the 85°C parts found in commercial-grade alternatives. In high-ambient-temperature installations — Middle East process plants, for example — this difference in component rating directly translates to years of additional service life.
EMC immunity is certified to IEC 61000-4 series, including 4 kV contact discharge (ESD), 2 kV fast transient burst (EFT), and 2 kV surge immunity. In substations and plants with frequent switching of large loads, these immunity levels are not theoretical — they are the difference between a stable control system and one that nuisance-trips weekly.
Global Express Logistics
Our Xiamen warehouse operates 6 days a week. Orders confirmed before 15:00 CST ship same day. Here is exactly what happens after you send your purchase order:
- Hour 0–2: Order confirmation and stock verification. We photograph the module serial number and send you the image before packing — you know exactly which unit is going into the box.
- Hour 2–4: Export documentation prepared. Commercial invoice, packing list, and HS code declaration (HS 8537.10) completed. For orders requiring a Certificate of Origin, allow one additional business day.
- Hour 4–6: DHL Express or FedEx International Priority pickup. Tracking number sent to your email within 30 minutes of carrier collection.
- Day 1–2: Delivery to most Southeast Asia, Japan, South Korea, and Australia destinations.
- Day 2–3: Delivery to Middle East, India, and Eastern Europe.
- Day 3–5: Delivery to Western Europe, North America, and South America.
All shipments are fully insured at declared value. For high-value orders, we recommend DHL Express with signature required. Sea freight consolidation is available for multi-unit orders where lead time permits — contact us for a freight quote.
Import duties and taxes are the buyer’s responsibility. We declare actual transaction value — we do not under-declare for customs purposes. For buyers in the EU, we can provide EORI-compatible documentation. For buyers in the US, we provide HTS code 8537.10.9170 on all commercial invoices.
Contact Information
Email: [email protected]
WhatsApp: +86 18359268345
Web: siemensplc.com
© 2026 siemensplc.com. All rights reserved.
Send This Part Number to Sales
Confirmation Process
We check the full part number, brand, series and visible nameplate information before quotation.
Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.
DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.