Siemens PLC sourcing desk · Multi-brand automation spares [email protected] +86 18359268345
ABB In Stock OK

ABB CI810A 3BSE013262R1 Communication Interface Module

Request verified availability, condition, replacement risk review, packing options and courier lead time for CI810A 3BSE013262R1.

Exact partCI810A 3BSE013262R1 RFQ auto-fillPart number attached Export packingDHL / FedEx / UPS Sales replyEmail or WhatsApp
BrandABB Part NumberCI810A 3BSE013262R1 ConditionAvailability Check Lead TimeRFQ Confirmation DocumentsDatasheet / photos by RFQ ShippingExport packing available
Auto-filled RFQ CI810A 3BSE013262R1

Click Request Quote and the part number is inserted into the inquiry form automatically.

Procurement Data

Key Product Information

Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.

Brand
ABB
Primary Part Number
CI810A 3BSE013262R1
Product Type
Communication Interface Module
Series / Family
AC800M
Manufacturer
ABB
Country of Origin
SE
Catalog Category
Communication
Operating Temp.
0°C to +55°C
Humidity
5% to 95% RH, non-condensing
Model confirmed for inquiry CI810A 3BSE013262R1 Send quantity, destination and urgency. The RFQ form keeps this part number attached.
Request Quote
Product Overview

ABB CI810A 3BSE013262R1 — Stop the Bleeding: Every Hour of DCS Downtime Costs You Real Money

Your AC800M controller just threw a communication fault. The PROFIBUS segment is dead. Production is halted. You’ve already pulled the CI810A and confirmed it’s the culprit — now you need a replacement module on-site, fast, not in six weeks. That’s exactly why this page exists.

We stock the ABB CI810A (Part No. 3BSE013262R1) in Xiamen, China, with same-day DHL/FedEx dispatch available for orders confirmed before 15:00 CST. No broker delays, no customs surprises — just a verified, original ABB module in your hands within 48–72 hours to most global destinations.

URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345

Quick Technical Datasheet

Parameter Specification
Manufacturer ABB
Model CI810A
Part Number 3BSE013262R1
Series AC800M DCS
Module Function PROFIBUS DP Master Communication Interface
Fieldbus Protocol PROFIBUS DP (IEC 61158 / EN 50170)
Max Slave Devices 125 per segment
Baud Rate 9.6 kbit/s – 12 Mbit/s (auto-detect)
Compatible Controllers PM861A, PM864A, PM866A (AC800M family)
Mounting AC800M backplane slot
Power Supply Via controller backplane (no external PSU required)
Operating Temperature 0°C to +55°C
Storage Temperature -40°C to +70°C
Humidity 5% to 95% RH, non-condensing
Certifications CE, UL, RoHS
Country of Origin Sweden
Stock Status ✔ Ready to Ship — Xiamen Warehouse

Troubleshooting & Replacement Tips

Ten years of field work teaches you that a CI810A failure rarely announces itself cleanly. Here’s what you’ll actually encounter and how to handle it:

Common Fault Indicators:

  • AC800M event log shows “PROFIBUS DP: Bus fault” or “CI810A: Communication error” — check the module’s BF (Bus Fault) LED first. Solid red = segment-level issue; flashing = individual slave dropout.
  • Sudden loss of all I/O on a PROFIBUS segment while the CPU itself remains healthy — classic CI810A hardware failure signature, not a cable fault.
  • Module not recognized after a power cycle — backplane connector oxidation or internal firmware corruption. Swap the module before chasing the bus.
  • Intermittent slave timeouts at high baud rates (6–12 Mbit/s) — can indicate a failing CI810A oscillator circuit. Drop baud rate temporarily to confirm; if stability returns, the module is degrading.

Replacement Procedure (Field-Verified):

  • Step 1 — Firmware check before you pull anything. In Control Builder M, note the current CI810A firmware version (typically visible under Hardware Configuration → Module Properties). Your replacement must run the same or higher firmware. CI810A firmware is not field-upgradeable without ABB tools — order accordingly.
  • Step 2 — Export the PROFIBUS configuration. In Control Builder M, export the DP master configuration (GSD files, slave addresses, I/O mapping). This takes 5 minutes and saves hours of re-commissioning.
  • Step 3 — Power down the controller rack. The CI810A is NOT hot-swap capable in all firmware revisions. Unless your site has confirmed hot-swap support under your specific firmware build, shut down the PM8xx CPU cleanly via Control Builder M before pulling the module.
  • Step 4 — Seat the replacement module firmly. The backplane connector requires deliberate pressure. A partially seated CI810A will power up but fail to communicate — a common cause of “new module, same fault” callbacks.
  • Step 5 — Verify node address assignment. The CI810A does not use DIP switches for addressing — its PROFIBUS master address is set in software via Control Builder M. Confirm the address matches your network configuration before going live.
  • Step 6 — Reload and verify. Download the application to the controller, force a PROFIBUS bus scan, and verify all slave green-lights in the diagnostic view before handing back to operations.

Firmware Compatibility Matrix (Critical): CI810A hardware revision R1 (3BSE013262R1) is compatible with AC800M controller firmware v4.x through v6.x. If your site runs firmware v6.1+, verify against ABB Technical Note 3BSE036351 before ordering. Mismatched firmware will result in the module being detected but non-functional.

Reliability in Harsh Conditions

The CI810A was not designed for a climate-controlled server room. ABB engineered this module for the realities of industrial plant environments — and it shows in the construction.

The PCB assembly uses conformal coating as standard, providing resistance to condensation, airborne contaminants, and corrosive atmospheres common in chemical and petrochemical plants. The backplane connector is gold-plated to resist oxidation in humid coastal or offshore environments — a detail that matters when your DCS cabinet is 50 meters from the sea.

Vibration tolerance meets IEC 60068-2-6 test specifications, making the CI810A suitable for installation near rotating machinery, compressors, and pump skids without additional isolation mounts. In mining and heavy industry applications where cabinet vibration is a constant, this is not a trivial specification.

Thermal management is passive — no fans, no moving parts. The module dissipates heat through the backplane and enclosure, eliminating the fan-failure failure mode that plagues lesser designs. Operating range of 0°C to +55°C covers the vast majority of industrial cabinet environments globally, including tropical climates without air conditioning.

EMC performance is validated to EN 55011 Class A and IEC 61000-4 series immunity standards. In practice, this means the CI810A maintains communication integrity in the presence of VFD switching noise, high-voltage bus bars, and welding equipment — environments where cheaper communication modules simply drop frames.

Global Express Logistics

Our Xiamen warehouse operates a same-day dispatch cut-off of 15:00 CST (UTC+8) for orders with confirmed payment. Here’s exactly what happens after you place your order:

  • T+0 (Order Confirmed): Module pulled from shelf, serial number photographed, anti-static packaging applied, humidity indicator card inserted. Commercial invoice, packing list, and certificate of origin prepared.
  • T+0 (Same Day): Shipment handed to DHL Express or FedEx International Priority — carrier selected based on your destination for fastest transit. Tracking number issued within 2 hours of pickup.
  • T+1 to T+3: Delivery to most destinations in Southeast Asia, Japan, South Korea, Australia, Middle East, and Europe. North America typically T+2 to T+4 depending on customs clearance speed.

All shipments include full export documentation compliant with Chinese customs regulations. HS Code 8537.10 is declared for PLC/DCS communication modules. For destinations requiring import permits or end-user certificates, contact us before ordering — we handle this routinely for customers in regulated markets.

DDP (Delivered Duty Paid) terms are available for most destinations — you pay one price, we handle import duties and clearance. No surprise brokerage fees on delivery.

For genuine plant emergencies, call or WhatsApp +86 18359268345 directly. We can arrange courier pickup outside business hours for critical situations.

Contact Information

Email: [email protected]
WhatsApp: +86 18359268345
Web: siemensplc.com
© 2026 siemensplc.com. All rights reserved.

Ready to quote

Send This Part Number to Sales

[email protected]
RFQ workflow

Confirmation Process

Quality workflow ->
01Model confirmation

We check the full part number, brand, series and visible nameplate information before quotation.

02Availability reply

Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.

03Packing & courier

DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.