Siemens PLC sourcing desk · Multi-brand automation spares [email protected] +86 18359268345
Request Quote
Schneider Electric In Stock OK

Schneider Electric BMXNOM0200 CANopen Master Module

Request verified availability, condition, replacement risk review, packing options and courier lead time for BMXNOM0200.

Exact partBMXNOM0200 RFQ auto-fillPart number attached Export packingDHL / FedEx / UPS Sales replyEmail or WhatsApp
BrandSchneider Electric Part NumberBMXNOM0200 ConditionAvailability Check Lead TimeRFQ Confirmation DocumentsDatasheet / photos by RFQ ShippingExport packing available
Auto-filled RFQ BMXNOM0200

Click Request Quote and the part number is inserted into the inquiry form automatically.

Procurement Data

Key Product Information

Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.

Brand
Schneider Electric
Primary Part Number
BMXNOM0200
Product Type
PLC Communication Module
Series / Family
Modicon M340
Country of Origin
FR
Catalog Category
Communication
Operating Temp.
0°C to +60°C
Model confirmed for inquiry BMXNOM0200 Send quantity, destination and urgency. The RFQ form keeps this part number attached.
Request Quote
Product Overview

BMXNOM0200 Down? Every Minute of CANopen Network Silence Costs You Money — We Ship Same Day

Your M340 rack just threw a red ERR light on the NOM slot. Servo drives are in fault. The CANopen network is dead. Downstream I/O islands are not responding. You have already checked the obvious — power is good, backplane is seated, CPU is running. The BMXNOM0200 is the problem, and you need a replacement on-site before the next shift starts. That is exactly the situation we built this stock for.

We maintain ready-to-ship inventory of the Schneider Electric BMXNOM0200 CANopen NMT master communication module at our Xiamen warehouse. No lead time negotiation. No waiting on distributor allocation. If you contact us before 3 PM CST, your unit ships the same business day via DHL Express or FedEx International Priority — tracked door-to-door, with full export documentation included.

URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345

Quick Technical Datasheet

Parameter Specification
Part Number BMXNOM0200
Brand Schneider Electric
Series Modicon M340
Module Function CANopen NMT Master Communication Module
Fieldbus Protocol CANopen (DS301, DS401)
Max. Slave Nodes 127 per module
Supported Baud Rates 10 kbps / 20 / 50 / 125 / 250 / 500 kbps / 1 Mbps
Physical Connector 9-pin Sub-D (DB9), male
Backplane Interface Modicon M340 X-Bus (no external power wiring)
Operating Temperature 0°C to +60°C
Storage Temperature -25°C to +70°C
Relative Humidity 10% to 95% RH, non-condensing
Protection Rating IP20
Certifications CE, UL, cUL, CSA
Configuration Software EcoStruxure Control Expert (Unity Pro) v13.0+
Weight Approx. 500 g
Stock Status ✅ Ready to Ship — Xiamen Warehouse

Troubleshooting & Replacement Tips

Confirming the BMXNOM0200 has failed — not the network: Before pulling the module, isolate the fault. Disconnect the DB9 CANopen cable from the module. If the CPU continues running and other rack modules stay healthy, the bus wiring or a slave device is not the culprit — the NOM module itself has failed. Common failure signatures: ERR LED solid red at power-on, COM LED never illuminates, Control Expert shows the module in “Not Present” or “Communication Error” state despite correct rack seating.

Step-by-step hot-swap procedure:

  1. Place the CPU in STOP mode via Control Expert or the physical keyswitch. Do not cut rack power unless your safety procedure requires it — the M340 backplane supports module removal under power, but confirm with your site SOP first.
  2. Disconnect the DB9 CANopen cable. Label it if multiple NOM modules are present in the rack.
  3. Press the module release latch and slide the BMXNOM0200 out of its slot. Note the slot number — the replacement must go back into the exact same slot position, as the CPU project references slot addressing.
  4. Insert the new BMXNOM0200. Ensure the backplane connector is fully engaged — you will feel a positive click. Secure the front latch.
  5. Reconnect the DB9 cable. Verify termination resistors (120 Ω) are present at both physical ends of the CANopen bus — a missing terminator is the single most common cause of a “new module, same fault” scenario.
  6. Set CPU to RUN. In Control Expert, navigate to the NOM module properties and verify the CANopen network scan completes without errors. All slave nodes should return to Operational state within 2–5 seconds of NMT Start command.

Firmware matching: The BMXNOM0200 firmware version must be compatible with your Control Expert project version. If you are replacing an older unit, open Control Expert → Hardware Catalog → BMXNOM0200 properties and compare the firmware revision. Mismatched firmware will cause the module to appear in the rack but refuse to enter Operational state. Use Schneider’s firmware update tool (available via the SE support portal) to align versions before going live.

EDS file re-import not required: The CANopen slave EDS configurations are stored in the CPU project, not in the NOM module itself. Replacing the BMXNOM0200 does not require re-importing EDS files or reconfiguring slave node addresses — the project downloads to the new module automatically on the next CPU program transfer.

Common fault codes to know:

  • %MWx (NOM status word) Bit 0 = 1: Module in initialization — normal at startup, abnormal if persistent beyond 10 seconds.
  • Bit 3 = 1 (Bus Off): CAN controller has detected excessive errors and removed itself from the bus. Root cause is almost always a wiring fault, missing terminator, or a slave device pulling the bus low. Swap the module only after ruling these out.
  • Bit 5 = 1 (Heartbeat timeout): One or more slave nodes stopped sending heartbeat messages. Check slave device power and node ID conflicts before assuming the master module is at fault.
  • Module LED: RUN off, ERR solid: Internal self-test failure. Module replacement is confirmed.

Reliability in Harsh Conditions

The BMXNOM0200 is not a office-grade component dressed up in an industrial enclosure. It is designed and tested to operate continuously in environments that would kill consumer electronics within hours. Schneider Electric subjects the Modicon M340 module range to IEC 61131-2 environmental compliance testing, which includes sinusoidal vibration across 5–150 Hz frequency sweeps, random vibration profiles simulating transport and in-service mechanical shock, and thermal cycling between operating extremes to stress solder joints and connector contacts.

In practice, this means the BMXNOM0200 holds up in steel mill auxiliary panels where floor vibration is constant, in outdoor switchgear cabinets in Southeast Asian humidity where condensation is a daily reality, and in food processing environments where washdown cycles create rapid thermal gradients. The IP20 rating covers the module face — the backplane connection is sealed by the rack housing itself, protecting the X-Bus contacts from airborne contamination.

Units we ship from Xiamen are stored in climate-controlled conditions, individually sealed in anti-static moisture barrier bags with desiccant packs. Every unit is inspected for connector pin integrity, label authenticity, and housing condition before packaging. We do not ship modules that show any sign of prior installation, pin damage, or label tampering.

Global Express Logistics

Our Xiamen warehouse sits 40 minutes from Xiamen Gaoqi International Airport (XMN), one of South China’s primary cargo hubs with daily freighter connections to Frankfurt, Dubai, Chicago, and Singapore. This geography is not accidental — it is why we can commit to same-day dispatch for orders confirmed before 3 PM CST.

Standard export flow for a BMXNOM0200 order:

  1. Order confirmed → unit pulled from shelf, inspected, photographed, and packed in double-wall carton with foam insert and anti-static inner bag.
  2. Commercial invoice, packing list, and certificate of origin prepared. HS Code 8537.10 applied for customs classification. For EU destinations, EUR.1 movement certificate available on request.
  3. Shipment booked with DHL Express or FedEx International Priority depending on destination and customer preference. Both carriers provide door-to-door tracking with customs clearance included in the service.
  4. Tracking number sent to customer within 2 hours of carrier pickup. Typical transit times: Europe 3–5 business days, Southeast Asia 2–3 days, Middle East 3–4 days, Americas 4–6 days.
  5. For critical downtime situations, we can arrange same-day airport-to-airport cargo with customer-arranged customs broker at destination — contact us directly to discuss.

All shipments include full export documentation. We have shipped to over 40 countries and are familiar with import requirements for industrial automation components in the EU, GCC, ASEAN, and North American markets. Duties and taxes at destination are the buyer’s responsibility unless otherwise agreed in writing.

Contact Information

📧 Email: [email protected]
💬 WhatsApp: +86 18359268345
🌐 Web: siemensplc.com
© 2026 siemensplc.com. All rights reserved.

Ready to quote

Send This Part Number to Sales

[email protected]
RFQ workflow

Confirmation Process

Quality workflow ->
01Model confirmation

We check the full part number, brand, series and visible nameplate information before quotation.

02Availability reply

Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.

03Packing & courier

DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.