Siemens PLC sourcing desk · Multi-brand automation spares [email protected] +86 18359268345
Request Quote
Weidmuller In Stock OK

WEIDMULLER 8581180000 Signal Isolating Converter

Request verified availability, condition, replacement risk review, packing options and courier lead time for 8581180000.

Exact part8581180000 RFQ auto-fillPart number attached Export packingDHL / FedEx / UPS Sales replyEmail or WhatsApp
BrandWeidmuller Part Number8581180000 ConditionAvailability Check Lead TimeRFQ Confirmation DocumentsDatasheet / photos by RFQ ShippingExport packing available
Auto-filled RFQ 8581180000

Click Request Quote and the part number is inserted into the inquiry form automatically.

Procurement Data

Key Product Information

Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.

Brand
Weidmuller
Primary Part Number
8581180000
Product Type
Signal Conditioner
Product Family
Other series
Manufacturer
WEIDMULLER
Country of Origin
Germany
Model Function
Frequency / Pulse Signal Galvanic Isolating Converter
Catalog Category
Industrial Automation Spares
Compliance
CE, RoHS, IEC 61010-1, EN 61000 EMC series
Model confirmed for inquiry 8581180000 Send quantity, destination and urgency. The RFQ form keeps this part number attached.
Request Quote
Product Overview

WEIDMULLER 8581180000 ACT20X – Stop the Clock on Your Downtime

Every minute a production line sits idle costs real money. When your frequency signal chain fails — flow meter readings drop out, encoder feedback goes dark, your PLC throws a cascade of faults — the pressure to restore operation is immediate. The WEIDMULLER 8581180000 ACT20X Frequency Signal Isolating Converter is a precision DIN-rail module that sits at the heart of these signal chains, and when it fails, there is no workaround. You need an exact replacement, verified original, in your hands fast.

We stock the 8581180000 in Xiamen and ship globally via DHL Express and FedEx International Priority. Most orders clear customs and arrive at European, Middle Eastern, and Southeast Asian destinations within 3–5 business days. North American delivery typically runs 4–6 business days. We have done this hundreds of times. We know what an unplanned shutdown costs, and we built our logistics around that reality.

URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345

Quick Technical Datasheet

Parameter Specification
Manufacturer WEIDMULLER
Full Part Number 8581180000
Product Series ACT20X Signal Conditioner
Function Frequency / Pulse Signal Galvanic Isolating Converter
Isolation Type 3-way galvanic isolation (Input / Output / Power Supply)
Mounting 35 mm DIN rail (EN 60715)
Housing Material Compact modular thermoplastic enclosure
Country of Origin Germany
Weight 118.7 g
Compliance CE, RoHS, IEC 61010-1, EN 61000 EMC series
Stock Status ✔ Ready to Ship – Xiamen warehouse

Full electrical datasheet (input/output frequency range, supply voltage, isolation voltage, accuracy class) available on request. Contact us before ordering if you need to confirm compatibility with your existing signal chain.

Troubleshooting & Replacement Tips

The 8581180000 fails in predictable ways. Knowing the failure signature before you pull the module saves time on the bench and prevents misdiagnosis.

Common failure indicators:

  • Zero or frozen frequency output: The output side of the isolator has lost signal continuity. Check the output terminals first with a frequency counter before condemning the module — a broken field wire mimics this fault exactly.
  • Erratic or noisy output frequency: Usually caused by ground loop ingress on the input side, or a failing internal DC/DC converter in the isolation barrier. If shielding and grounding checks pass, the module is the culprit.
  • No output, power LED off: Confirm 24 VDC supply voltage at the power terminals under load. A sagging PSU rail (below ~21.6 V) will cause the ACT20X to drop out without damaging it — restore supply voltage and the module typically recovers.
  • Output frequency offset or gain error: The ACT20X series uses internal potentiometers (ZERO and SPAN) for calibration. Before replacing the module, verify these have not drifted or been inadvertently adjusted. Document the original settings with a multimeter before removal.

Replacement procedure — field checklist:

  1. De-energise the panel section. Confirm LOTO (Lockout/Tagout) is applied.
  2. Photograph the existing wiring before disconnecting — terminal numbering on ACT20X modules is consistent across the series, but field wiring labels are not always reliable.
  3. Note the ZERO and SPAN potentiometer positions on the outgoing module using a fine-tip marker or caliper measurement from the fully CCW stop.
  4. Disconnect field wiring. Release the DIN rail latch and remove the module.
  5. Seat the replacement 8581180000 on the rail. Reconnect wiring per your photograph.
  6. Apply power. Verify 24 VDC supply LED illuminates.
  7. Inject a known reference frequency from a signal generator or the live field device. Confirm output frequency at the downstream PLC input card matches expected value.
  8. Adjust ZERO and SPAN only if measured output deviates from the documented pre-fault calibration. Make incremental adjustments — one full turn of the pot produces a significant span shift.
  9. Log the replacement in your maintenance management system with the module serial number and date code from the label.

Firmware / addressing note: The 8581180000 is a passive signal conditioning module with no firmware, no fieldbus address, and no software configuration. There is no commissioning software required. Calibration is entirely hardware-based via the onboard potentiometers. This makes field replacement straightforward compared to intelligent I/O modules.

Reliability in Harsh Conditions

Industrial signal conditioning modules earn their keep in environments that would destroy consumer electronics in hours. The WEIDMULLER ACT20X platform was designed from the ground up for exactly these conditions.

Vibration is a constant in pump stations, compressor rooms, and conveyor drive panels. The ACT20X housing uses a positive DIN rail latch mechanism that prevents the module from walking off the rail under sustained vibration — a failure mode that has caused more than one unexplained signal dropout in poorly designed panels. Internal PCB assemblies are conformally coated to resist moisture ingress in high-humidity environments such as water treatment facilities and coastal installations.

Thermal performance is equally critical. Control panels in outdoor enclosures or near heat-generating equipment routinely see internal temperatures exceeding 50°C. The ACT20X series is rated for continuous operation across an extended industrial temperature range, and the low self-heating of the isolation circuitry means the module does not contribute significantly to panel thermal load — an important consideration when calculating enclosure ventilation requirements.

EMC immunity is non-negotiable in environments with variable frequency drives, large contactors, and high-current bus bars. The 8581180000 is tested to EN 61000 series standards for conducted and radiated immunity, and the 3-way galvanic isolation inherently breaks the ground loops that are the primary coupling path for VFD-generated common-mode noise. In practice, this means the module continues to deliver clean frequency output even when installed in panels with significant electrical noise — a real-world performance characteristic that cheaper non-isolated signal conditioners cannot match.

Global Express Logistics

Our Xiamen warehouse operates Monday through Saturday. Orders confirmed before 14:00 CST are processed and handed to the carrier the same day. Here is what the logistics chain looks like from our dock to your panel room:

  • Day 0 (Order confirmed): Unit pulled from stock, inspected, packed in anti-static packaging with original manufacturer labeling intact. Commercial invoice and packing list prepared. Export declaration filed with Chinese customs.
  • Day 1: DHL Express or FedEx International Priority pickup. Tracking number issued to you within 2 hours of handover.
  • Days 2–3: Clears Chinese export customs. In-transit scan at Hong Kong or Shanghai hub.
  • Days 3–5 (Europe / Middle East / Southeast Asia): Delivery to your facility. DHL and FedEx both offer pre-noon delivery options for critical shipments — request this at order time.
  • Days 4–6 (North America / Australia): Delivery to your facility. US Customs clearance is typically same-day for commercial shipments under the de minimis threshold.

We prepare all export documentation including commercial invoice with accurate HS code declaration, packing list, and certificate of origin on request. For regulated industries requiring a WEIDMULLER certificate of conformity or traceability documentation, advise us at order time and we will include it in the shipment.

For genuinely critical shutdowns where standard express is not fast enough, contact us directly on WhatsApp. We have arranged same-day courier handover to international freight forwarders for shipments where every hour counts.

Contact Information

Email: [email protected]
WhatsApp: +86 18359268345
Web: siemensplc.com

© 2026 siemensplc.com. All rights reserved.

Ready to quote

Send This Part Number to Sales

[email protected]
RFQ workflow

Confirmation Process

Quality workflow ->
01Model confirmation

We check the full part number, brand, series and visible nameplate information before quotation.

02Availability reply

Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.

03Packing & courier

DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.