YOKOGAWA AAM11-S2 AAM11-S1 DCS Analog Input Module – CENTUM VP
Request verified availability, condition, replacement risk review, packing options and courier lead time for AAM11-S2.
Click Request Quote and the part number is inserted into the inquiry form automatically.
- Reply by email: [email protected]
- WhatsApp / Tel: +86 18359268345
- Mon-Sat 9:00-18:00 GMT+8
Key Product Information
Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.
- Brand
- Yokogawa
- Primary Part Number
- AAM11-S2
- Product Type
- DCS Analog Input Module
- Series / Family
- CENTUM VP
- Country of Origin
- JP
- Catalog Category
- I/O Modules
- Operating Temp.
- 0°C to +55°C
- Warranty
- 12 months from date of shipment
- Compliance
- CE, RoHS, IEC 61000-4 series (EMC)
YOKOGAWA AAM11-S2 / AAM11-S1: Multi-Channel Analog Input Module in CENTUM VP Field Control Architecture
The AAM11-S2 and AAM11-S1 are analog current/voltage input modules engineered for deployment within YOKOGAWA’s CENTUM VP Distributed Control System. The AAM11-S2 provides 16 differential analog input channels per module slot; the AAM11-S1 provides 8 channels. Both variants accept 4–20 mA current loop signals and 1–5 V DC voltage signals from field transmitters, converting them to 16-bit digital process values that the Field Control Station (FCS) uses for closed-loop regulation, alarm management, and historian archiving.
In a CENTUM VP architecture, the FCS backplane hosts multiple I/O modules in a card-slot arrangement. The AAM11 series communicates with the FCS processor over the V-net/ER internal bus, a deterministic token-passing network that guarantees scan-cycle consistency. Each module slot is polled at a fixed interval defined by the FCS configuration, typically 100 ms to 500 ms depending on the control application, ensuring that process variable updates arrive at the controller within a bounded latency window. This determinism is a fundamental requirement in continuous process industries where loop instability caused by variable scan jitter can propagate into product quality deviations or safety exceedances.
Real-time Stock & RFQ: [email protected] | WhatsApp: +86 18359268345
Technical Parameters
| Parameter | AAM11-S2 | AAM11-S1 |
|---|---|---|
| Input Channels | 16 (differential) | 8 (differential) |
| Input Signal Type | 4–20 mA current / 1–5 V DC voltage (selectable per channel) | |
| A/D Resolution | 16-bit | |
| Input Impedance (Current) | ≤ 250 Ω (burden resistor integrated) | |
| Input Impedance (Voltage) | ≥ 1 MΩ | |
| Accuracy | ±0.1% of full scale (at 25°C) | |
| Temperature Coefficient | ±0.01% FS / °C | |
| Channel-to-Channel Isolation | 500 V DC (optical isolation) | |
| Common Mode Rejection | ≥ 120 dB at 50/60 Hz | |
| Backplane Interface | V-net/ER Bus (CENTUM VP FCS) | |
| Power Consumption | Supplied via FCS backplane (≤ 5 W typical) | |
| Operating Temperature | 0°C to +55°C | |
| Storage Temperature | −25°C to +70°C | |
| Relative Humidity | 5% to 95% RH (non-condensing) | |
| Module Weight | Approx. 1,460 g | |
| Compliance | CE, RoHS, IEC 61000-4 series (EMC) | |
| Warranty | 12 months from date of shipment | |
Hardware Logical Analysis
The AAM11 series employs per-channel optical isolation between the field wiring terminals and the module’s internal digital logic. Each channel’s analog front-end consists of a precision instrumentation amplifier followed by a sigma-delta A/D converter. The sigma-delta architecture inherently oversamples the input signal at a rate significantly higher than the Nyquist frequency of the process variable, then applies a digital decimation filter to produce a 16-bit output word. This approach suppresses high-frequency noise components—including switching transients from variable-frequency drives and power converters common in process plant environments—without requiring external RC filter networks on field wiring.
The channel-to-channel isolation barrier, rated at 500 V DC, breaks ground loops that would otherwise introduce common-mode interference into the measurement. In installations where multiple transmitters share a common power supply rail or where cable runs exceed 100 m, ground potential differences of several volts are typical. The isolation barrier prevents these potentials from appearing as measurement offsets. The common mode rejection ratio of ≥ 120 dB at 50/60 Hz further attenuates power-frequency interference induced by parallel cable routing near high-voltage conductors.
The module’s EMC design follows IEC 61000-4-2 (ESD), IEC 61000-4-3 (radiated immunity), IEC 61000-4-4 (electrical fast transient), and IEC 61000-4-6 (conducted immunity) test criteria. The PCB layout uses a split ground plane strategy: the analog measurement ground is isolated from the digital logic ground, with the two planes joined at a single star point near the power entry. This topology minimizes the return current path for high-frequency digital switching noise through the analog measurement circuitry.
The V-net/ER backplane interface uses a differential serial protocol with CRC error detection on each data frame. If a frame fails CRC validation, the FCS processor retains the last valid value and sets a module communication fault flag in the system diagnostic register. This fail-retain behavior prevents spurious process variable jumps from propagating into control calculations during transient communication disturbances.
System Integration Benefits
- Deterministic scan-cycle compliance: The V-net/ER bus guarantees bounded latency between field signal change and FCS process variable update, supporting control loops with scan periods as short as 100 ms without jitter-induced instability.
- High-density I/O footprint reduction: The AAM11-S2’s 16-channel capacity reduces the number of occupied FCS card slots by up to 50% compared to 8-channel alternatives, lowering cabinet space requirements and inter-module wiring complexity.
- Dual-model scalability: The AAM11-S1 (8-channel) and AAM11-S2 (16-channel) share identical firmware and configuration interfaces, allowing engineers to right-size I/O density per FCS node without retraining or reconfiguration overhead.
- Transparent diagnostic visibility: Each module exposes per-channel status flags—including open-loop detection, over-range, under-range, and A/D conversion fault—directly to the CENTUM VP HMI alarm system, enabling operators to identify field instrument failures without physical inspection.
- Open-loop detection on current channels: The 4–20 mA input circuit monitors loop current continuously. A current below approximately 3.6 mA triggers an open-loop alarm, distinguishing a broken field cable from a valid 4 mA zero-scale reading.
- Hot-swap module replacement: The CENTUM VP FCS architecture supports online module replacement without FCS shutdown, provided the replacement module is of the same type. The FCS automatically re-initializes the module and resumes scanning within one scan cycle after insertion.
- Integrated engineering unit scaling: Channel scaling from raw 4–20 mA counts to engineering units (e.g., 0–100 bar, −50 to +200°C) is configured within the CENTUM VP builder environment and stored in the FCS, eliminating the need for external signal conditioners or scaling relays.
- Long-term platform continuity: YOKOGAWA maintains the CENTUM VP hardware platform under an extended lifecycle support program. Replacement modules, firmware updates, and technical documentation remain available for systems commissioned over a decade ago, protecting capital investment in installed FCS infrastructure.
Quality Assurance & Global Logistics
Every AAM11-S2 and AAM11-S1 unit supplied by siemensplc.com is sourced as genuine YOKOGAWA original hardware. Prior to dispatch, each module undergoes a structured pre-shipment inspection protocol: visual examination of PCB, connector pins, and module housing for mechanical damage; firmware version verification against the YOKOGAWA hardware revision matrix; functional continuity check of the backplane connector contacts; and packaging in anti-static shielding bags with desiccant and humidity indicator cards.
Shipments originate from our warehouse in Xiamen, China. Xiamen is a designated free-trade port with direct access to major international freight carriers including DHL Express, FedEx International Priority, UPS Worldwide Expedited, and SF International. Standard export documentation—commercial invoice, packing list, and certificate of origin—is prepared for every shipment. For orders requiring customs clearance support, HS code classification assistance, or specific country-of-origin declarations, our logistics team provides documentation within 24 hours of order confirmation.
Transit times to major industrial hubs: Southeast Asia 2–4 business days; Europe 3–5 business days; North America 3–6 business days; Middle East 4–6 business days. All shipments are fully insured and tracked from dispatch to delivery. A 12-month warranty covers manufacturing defects and functional failures under normal operating conditions. Warranty claims are processed with a target replacement dispatch of 5 business days from fault confirmation.
Contact Information
Email: [email protected]
WhatsApp: +86 18359268345
Web: siemensplc.com
Location: Xiamen, China
© 2026 siemensplc.com. All rights reserved.
Send This Part Number to Sales
Confirmation Process
We check the full part number, brand, series and visible nameplate information before quotation.
Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.
DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.