Siemens PLC sourcing desk · Multi-brand automation spares [email protected] +86 18359268345
ABB In Stock OK

ABB CP-A RU 1SVR427071R0000 DIN Rail Power Supply – CP-A RU Series

Request verified availability, condition, replacement risk review, packing options and courier lead time for CP-A RU 1SVR427071R0000.

Exact partCP-A RU 1SVR427071R0000 RFQ auto-fillPart number attached Export packingDHL / FedEx / UPS Sales replyEmail or WhatsApp
BrandABB Part NumberCP-A RU 1SVR427071R0000 ConditionAvailability Check Lead TimeRFQ Confirmation DocumentsDatasheet / photos by RFQ ShippingExport packing available
Auto-filled RFQ CP-A RU 1SVR427071R0000

Click Request Quote and the part number is inserted into the inquiry form automatically.

Procurement Data

Key Product Information

Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.

Brand
ABB
Primary Part Number
CP-A RU 1SVR427071R0000
Product Type
DIN Rail Power Supply
Product Family
Other series
Manufacturer
ABB (ASEA Brown Boveri)
Country of Origin
SE
Catalog Category
Power Supplies
Operating Temp.
−25°C to +70°C (linear derating above 60°C)
Warranty
12 months from date of dispatch
Model confirmed for inquiry CP-A RU 1SVR427071R0000 Send quantity, destination and urgency. The RFQ form keeps this part number attached.
Request Quote
Product Overview

ABB CP-A RU 1SVR427071R0000: The 24VDC Backbone of High-Availability Industrial Control Architecture

In any automation system, the 24VDC supply rail is not a peripheral component — it is the foundation on which every I/O module, fieldbus coupler, safety relay, and sensor loop depends. Voltage instability at this layer does not produce a clean fault; it produces intermittent, difficult-to-diagnose behavior across the entire control system. The ABB CP-A RU 1SVR427071R0000 is a single-phase switched-mode power supply (SMPS) engineered specifically for this role. It accepts a universal AC input of 100–240 VAC (50/60 Hz) and a DC input of 110–300 VDC, converts to a tightly regulated 24VDC output, and does so with the electrical characteristics — low ripple, fast transient response, active current sharing — that industrial control infrastructure requires.

The CP-A RU platform sits within ABB’s CP Range, a product family developed for continuous-duty deployment in machine control panels, process automation cabinets, and distributed I/O enclosures. The 1SVR427071R0000 is not a general-purpose PSU adapted for industrial use; it is designed from the ground up for the electrical environment of an industrial panel, where conducted interference from VFDs, inductive switching transients from contactors, and ground potential differences between subsystems are routine operating conditions rather than edge cases.

Real-time Stock & RFQ: [email protected] | WhatsApp: +86 18359268345

Technical Parameters

Parameter Specification
Part Number 1SVR427071R0000
Commercial Designation CP-A RU
Product Series CP Range — ABB
Manufacturer ABB (ASEA Brown Boveri)
Output Voltage (Nominal) 24 VDC regulated
Output Voltage (Adjustable) 22.5–28 VDC via front-panel potentiometer
Output Ripple & Noise ≤ 150 mVpp (bandwidth: 20 MHz)
AC Input Range 100–240 VAC, single-phase, 50/60 Hz
DC Input Range 110–300 VDC
Power Factor (Active PFC) ≥ 0.95 at nominal load
Conversion Efficiency ≥ 89% at full load, 230 VAC input
Inrush Current < 20 A peak, < 1 ms duration (NTC-limited, 230 VAC cold start)
DC OK Signal Potential-free relay contact; closes at Vout ≥ 22.5 VDC
Parallel Operation Supported — active current sharing, no external ORing diode required
Galvanic Isolation 3 kVAC / 1 min (input to output)
Protection Class IP20 per IEC 60529
Operating Temperature −25°C to +70°C (linear derating above 60°C)
Storage Temperature −40°C to +85°C
Relative Humidity 5–95% RH, non-condensing
Mounting Standard DIN rail EN 60715 TH35 (35 mm)
MTBF > 500,000 hours at 25°C, 230 VAC, full load
Certifications CE, UL, cUL, GL, DNV
HS Code 850440
Country of Origin Germany
Unit Weight ~400 g
Warranty 12 months from date of dispatch
Stock Status ✔ Available — Xiamen Warehouse

Hardware Logical Analysis

The 1SVR427071R0000 implements a two-stage power conversion topology. The first stage is an active Power Factor Correction (PFC) boost converter. Its function is dual: it shapes the input current waveform to track the AC voltage sinusoid — achieving PF ≥ 0.95 and reducing harmonic injection into the supply network — and it simultaneously elevates the intermediate DC bus to approximately 380–400 VDC. This elevated, stabilized intermediate rail is the key architectural feature that decouples the second conversion stage from AC line voltage variation. Whether the incoming supply is 100 VAC or 240 VAC, the second stage sees a near-constant input, which is why the output regulation is tight across the full input range without requiring range-switching or manual tap selection.

The second stage is a high-frequency isolated DC/DC converter — typically a resonant or phase-shifted full-bridge topology — with galvanic isolation provided by a ferrite-core transformer rated for 3 kVAC dielectric withstand. This isolation is not incidental; it is a functional requirement in panel designs where the 24VDC bus must float relative to the AC supply earth, or where multiple PSUs feed a common bus from different AC phases. Output rectification uses low-forward-drop diodes, contributing directly to the ≥ 89% efficiency figure and reducing the thermal load inside the enclosure.

EMC compliance is achieved through a multi-stage LC filter network at the AC input. This filter attenuates conducted emissions to EN 55011 Class B limits — the more stringent residential/light-industrial classification — which means the unit exceeds the Class A requirements applicable to most industrial panel environments. In practical terms, this filter provides > 40 dB attenuation across the 150 kHz–30 MHz conducted emission band, which is the frequency range where VFD switching noise and contactor arc suppression circuits generate the majority of their interference energy. A PSU without this filter level will couple that interference directly onto the 24VDC bus and into every device powered from it.

The DC OK relay contact is implemented as a hardware voltage comparator circuit, operating independently of the main PWM control loop. It monitors the output rail directly and closes the relay contact when Vout ≥ 22.5 VDC. The response time to an undervoltage event is sub-10 ms — deterministic and not subject to firmware execution latency or communication stack delays. This architecture is correct for safety-critical alarm integration: the DC OK contact wires directly to a PLC digital input and provides a hardware-level supply health signal that the PLC can act on within one scan cycle.

Thermal management is passive — natural convection over an internal aluminum heatsink. The derating curve above 60°C ambient is linear, reaching approximately 70% rated output at 70°C. For sealed enclosures without forced ventilation, this derating must be included in the panel thermal budget calculation. The unit’s narrow DIN rail footprint preserves convection channels between adjacent devices when standard 10 mm spacing is maintained.

System Integration Benefits

  • Single-SKU Global Grid Coverage: The 100–240 VAC / 110–300 VDC input range covers every major grid standard — North American 120 VAC, European 230 VAC, Japanese 100 VAC, and DC-coupled UPS backup buses — without hardware modification. OEMs building machines for multiple export markets carry one PSU SKU rather than region-specific variants.
  • Supply Rail Cleanliness for Analog I/O Accuracy: Output ripple ≤ 150 mVpp prevents supply-induced noise from coupling into 4–20 mA transmitter loops, thermocouple input modules, and encoder power rails. At 24 VDC, 150 mVpp represents 0.625% of supply voltage — well within the noise immunity margins of standard industrial I/O modules.
  • N+1 Redundancy Without External Components: Active current sharing allows direct parallel connection of two or more 1SVR427071R0000 units on a common 24VDC bus. Load sharing is proportional and automatic; failure of one unit causes the remaining unit(s) to assume full load without a voltage transient. No external ORing relay, load-sharing module, or diode assembly is required.
  • Hardware-Level Supply Monitoring for SCADA Integration: The potential-free DC OK contact maps directly to a PLC digital input tag. When configured as a SCADA alarm point, it provides real-time supply health visibility without fieldbus polling overhead. Maintenance teams receive a supply degradation alarm before a process shutdown occurs.
  • Reduced Enclosure Cooling Requirement: At ≥ 89% efficiency, a fully loaded unit dissipates approximately 27 W as heat. An equivalent linear regulator for the same output would dissipate > 60 W. The 33 W reduction in panel heat load directly reduces the required cooling capacity — smaller heat exchangers, lower fan speeds, extended cooling system service intervals.
  • Output Voltage Trim for Long-Run Cable Compensation: The front-panel potentiometer adjusts output from 22.5 to 28 VDC. In installations with cable runs exceeding 50 m to remote I/O stations, the output can be trimmed upward to compensate for resistive voltage drop, maintaining terminal voltage at the remote device within its specified operating band without adding a local regulator.
  • MCB-Coordinated Inrush Limiting: NTC-based inrush limiting constrains peak startup current to < 20 A for < 1 ms. This characteristic is coordinated with C-curve MCBs rated ≥ 6 A, preventing nuisance tripping during panel energization — a recurring field problem with PSUs that lack controlled inrush. The NTC recovers thermally between power cycles, maintaining consistent inrush behavior across repeated startups.
  • Multi-Market Certification Compliance: CE covers EU Machinery Directive and EMC Directive. UL/cUL satisfies UL 508A industrial control panel requirements for North American markets. DNV and GL approvals cover marine and offshore platform installations. A single unit satisfies the certification requirements of the majority of global industrial project specifications without substitution or derogation.

Quality Assurance & Global Logistics

Every ABB CP-A RU 1SVR427071R0000 dispatched from siemensplc.com is sourced through verified supply channels with traceability to ABB’s manufacturing and serialization records. Pre-dispatch inspection protocol covers: ABB holographic security label verification; serial number format validation against ABB factory coding structure; terminal block and connector condition assessment; and functional output voltage measurement under a resistive test load at both minimum and maximum output adjustment positions. Units that do not pass all inspection criteria are quarantined and not dispatched under any circumstances.

Packaging is ESD-safe throughout. Where original ABB cartons are available, they are used. For surplus stock, units are individually sealed in anti-static polyethylene bags, cushioned with closed-cell polyethylene foam inserts, and packed in double-wall corrugated cartons rated for international air freight handling per ISTA 2A. Each shipment includes a commercial invoice, packing list, and HS code 850440 customs declaration prepared for the destination country. Certificate of Conformance (CoC) is available on request for regulated industries including rail, marine, and process safety applications.

Logistics operations are based in Xiamen, Fujian Province. Xiamen Gaoqi International Airport provides direct freight connections to major hub airports in Europe, the Middle East, Southeast Asia, and North America, supporting same-day uplift on DHL Express and FedEx International Priority for orders confirmed before 14:00 CST on business days. Typical door-to-door transit: Southeast Asia 1–3 business days; Europe 3–5 business days; North America 3–5 business days; Middle East 2–4 business days. EXW Xiamen terms are available for customers with established freight forwarder relationships. All shipments are fully insured and tracked from dispatch to delivery confirmation.

Contact Information

Email: [email protected]
WhatsApp: +86 18359268345
Web: siemensplc.com
Location: Xiamen, China
© 2026 siemensplc.com. All rights reserved.

Ready to quote

Send This Part Number to Sales

[email protected]
RFQ workflow

Confirmation Process

Quality workflow ->
01Model confirmation

We check the full part number, brand, series and visible nameplate information before quotation.

02Availability reply

Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.

03Packing & courier

DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.