Schneider Electric BMXDDI1602 Digital Input Module
Request verified availability, condition, replacement risk review, packing options and courier lead time for BMXDDI1602.
Click Request Quote and the part number is inserted into the inquiry form automatically.
- Reply by email: [email protected]
- WhatsApp / Tel: +86 18359268345
- Mon-Sat 9:00-18:00 GMT+8
Key Product Information
Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.
- Brand
- Schneider Electric
- Primary Part Number
- BMXDDI1602
- Product Type
- PLC Digital Input Module
- Series / Family
- Modicon M340
- Country of Origin
- FR
- Catalog Category
- I/O Modules
- Operating Temp.
- 0 °C to +60 °C
- Warranty
- 12 months from dispatch
BMXDDI1602 — Stop the Clock on Your Downtime: 16-Channel 24VDC Digital Input Module, Stocked and Ready to Dispatch
Every hour a Modicon M340 rack sits idle costs real money. The Schneider Electric BMXDDI1602 is a 16-channel 24VDC discrete input module — one of the most frequently replaced I/O cards in M340-based control systems. When this card fails, your line stops. We stock it. We ship it fast. From Xiamen, China, to your plant floor via DHL or FedEx, typically within 24–48 hours of order confirmation.
This page is written for the engineer on the ground who needs the right part, the right data, and zero ambiguity. No fluff. Just the information you need to confirm compatibility, pull the old card, configure the new one, and get your process running again.
URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345
Quick Technical Datasheet
| Parameter | Specification | Status |
|---|---|---|
| Part Number | BMXDDI1602 | ✔ Ready to Ship |
| Brand | Schneider Electric | 100% Original |
| Series | Modicon M340 (BMX) | — |
| Module Type | Discrete (Digital) Input | — |
| Number of Channels | 16 | — |
| Rated Input Voltage | 24 VDC | — |
| Input Type | Sink / Source (IEC Type 1 & Type 2) | — |
| Nominal Input Current | 7 mA per channel | — |
| Logic 1 Threshold | ≥ 15 VDC | — |
| Logic 0 Threshold | ≤ 5 VDC | — |
| Input Filter (configurable) | 0.5 ms / 1 ms / 3 ms / 8 ms | — |
| Channel-to-Bus Isolation | 500 VAC | — |
| Backplane Interface | Modicon M340 X-Bus | — |
| Terminal Block | 20-pin removable screw terminal | — |
| Operating Temperature | 0 °C to +60 °C | — |
| Storage Temperature | -25 °C to +70 °C | — |
| Relative Humidity | 5% to 95% non-condensing | — |
| Protection Rating | IP20 | — |
| Certifications | CE, UL, cUL, IEC 61131-2, RoHS | — |
| Weight | Approx. 200 g | — |
| Warranty | 12 months from dispatch | Covered |
Troubleshooting & Replacement Tips
Most common failure signatures for BMXDDI1602:
- ERR LED solid red on module: Internal hardware fault detected. The module has failed its self-diagnostic at power-up. Replacement is the only corrective action — no firmware recovery path exists for this fault state.
- I/O LED flashing but no data in Unity Pro: X-Bus communication fault. First reseat the module firmly — M340 backplane connectors are susceptible to micro-fretting corrosion in high-vibration environments. If reseating fails, the backplane connector on the module itself may be damaged. Replace the module.
- Channels reading logic 1 with no field signal present: Internal pull-up circuit failure or field wiring short to 24V. Disconnect field wiring first. If channels still read high with terminals open, the module input circuitry has failed.
- Intermittent channel dropouts on specific inputs: Check input filter setting in Unity Pro (Module Properties → Input Filter). A 0.5 ms filter on a noisy field device (mechanical relay, inductive proximity sensor without suppression) will cause false transitions. Increase filter to 3 ms or 8 ms before condemning the module.
- Module not recognized after rack power cycle: Verify slot assignment in Unity Pro hardware configuration matches physical slot position. M340 modules use automatic slot addressing — the CPU reads slot position at startup. If the module was moved to a different slot without updating the software configuration, it will appear as an unrecognized device.
Step-by-step replacement procedure:
- Export and save the current Unity Pro / EcoStruxure Control Expert project before any hardware change.
- De-energize the 24VDC field supply feeding the BMXDDI1602 input commons. Do not rely solely on the PLC power-off — field wiring may be independently powered.
- Photograph the terminal block wiring before disconnection. The 20-pin removable terminal block retains wiring — pull the block as a unit and transfer it directly to the new module.
- Press the module release latch and slide the BMXDDI1602 out of the rack slot. No tools required.
- Insert the replacement module into the same slot. The X-Bus connector is keyed — it seats in one orientation only. Apply firm, even pressure until the latch clicks.
- Reattach the terminal block. Verify all screw terminals are torqued to 0.5 N·m (4.4 in·lb) — loose terminals are the leading cause of intermittent input faults post-replacement.
- Power up the rack. The CPU performs automatic module recognition. No address DIP switches exist on this module — slot position is the address. No firmware download to the I/O module is required.
- In Unity Pro, go online and verify all 16 channels display correct logic states against known field conditions before returning the system to automatic mode.
Configuration note: The BMXDDI1602 carries no user-configurable DIP switches or jumpers. All parameters (input filter time, channel enable/disable, fallback behavior on CPU communication loss) are set exclusively in software via Unity Pro or EcoStruxure Control Expert. Ensure your software configuration file matches the replacement module’s slot position before going online.
Reliability in Harsh Conditions
The BMXDDI1602 is built to IEC 61131-2 environmental requirements — the baseline standard for industrial PLC hardware. In practice, this translates to the following verified performance envelopes:
- Vibration resistance: Tested to IEC 60068-2-6 (sinusoidal, 10–150 Hz, 1g). The module’s PCB is conformally coated and mechanically secured via the X-Bus backplane connector and front latch, eliminating resonance-induced connector fretting under continuous machine vibration.
- Shock resistance: IEC 60068-2-27 (15g, 11 ms half-sine). Suitable for installation on mobile equipment or in environments with frequent mechanical impact events.
- Thermal cycling: Rated for continuous operation at 60 °C ambient without derating. The module draws power from the backplane bus — no internal fan or active cooling required. Thermal design relies on conduction through the housing to the rack enclosure.
- Humidity and condensation: Conformal coating on the PCB provides protection against moisture ingress at IP20 enclosure level. For environments with condensation risk, the module must be installed in a sealed cabinet with appropriate anti-condensation heating.
- EMC immunity: Tested to IEC 61000-4-2 (ESD, 4 kV contact / 8 kV air), IEC 61000-4-4 (EFT, 2 kV), IEC 61000-4-5 (surge, 1 kV line-to-line). The 500 VAC channel-to-bus isolation barrier is the primary defense against surge events propagating from field wiring into the backplane.
- Altitude: Operational to 2,000 m without derating. Above 2,000 m, consult Schneider Electric for derating curves — reduced air density affects convective cooling capacity.
Global Express Logistics
Our dispatch operation is based in Xiamen, China — a major international freight hub with direct DHL, FedEx, and UPS gateway access. The logistics process for urgent replacement orders:
- Order confirmation to dispatch: Same-day dispatch for orders confirmed before 14:00 CST. Next-business-day dispatch for orders confirmed after cutoff.
- Export documentation: Commercial invoice, packing list, and certificate of origin prepared at dispatch. For orders requiring a Schneider Electric certificate of conformity, allow one additional business day.
- Carrier options: DHL Express (1–3 business days to Europe/North America), FedEx International Priority (1–3 business days), UPS Worldwide Express (2–3 business days). Economy air freight available for non-urgent orders.
- Customs clearance: HS Code 8537.10 applies to this module. We pre-declare the correct commodity code and declared value on all shipments to minimize customs hold risk at destination.
- Tracking: Tracking number provided within 2 hours of dispatch. Direct carrier tracking links sent via email.
- Packaging: ESD-safe anti-static bag, foam-lined rigid carton. Modules are not bulk-packed — each unit ships individually protected to prevent transit damage.
- Destinations served: Worldwide. We regularly ship to Germany, USA, Australia, UAE, Brazil, India, South Korea, and Southeast Asia. No destination surcharges for standard express services.
Contact Information
For stock confirmation, pricing, and urgent RFQ:
- Email: [email protected]
- WhatsApp: +86 18359268345
- Web: siemensplc.com
- Location: Xiamen, China
© 2026 siemensplc.com. All rights reserved.
Send This Part Number to Sales
Confirmation Process
We check the full part number, brand, series and visible nameplate information before quotation.
Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.
DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.