Allen-Bradley 1771-NC15 Analog Input Module – PLC-5 1771 Series
Request verified availability, condition, replacement risk review, packing options and courier lead time for 1771-NC15.
Click Request Quote and the part number is inserted into the inquiry form automatically.
- Reply by email: [email protected]
- WhatsApp / Tel: +86 18359268345
- Mon-Sat 9:00-18:00 GMT+8
Key Product Information
Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.
- Brand
- Allen-Bradley
- Primary Part Number
- 1771-NC15
- Product Type
- PLC Analog Input Module
- Series / Family
- PLC-5
- Manufacturer
- Allen-Bradley / Rockwell Automation
- Country of Origin
- US
- Catalog Category
- I/O Modules
- Operating Temp.
- 0 °C to +60 °C
- Warranty
- 12 months from date of shipment
Allen-Bradley 1771-NC15: Thermocouple & Millivolt Analog Input Interface for PLC-5 Control Architectures
In high-temperature process environments — continuous casting, refinery distillation columns, heat-treatment furnaces — the integrity of the analog signal chain is not a secondary concern. It is the control loop itself. The Allen-Bradley 1771-NC15 is a dedicated thermocouple and millivolt analog input module engineered for the 1771 I/O backplane, the foundational I/O architecture of Rockwell Automation’s PLC-5 programmable controller family. Its function is precise: convert low-level electrochemical signals from thermocouple junctions into 16-bit digital words that the PLC-5 processor can act upon within its deterministic scan cycle.
Unlike general-purpose analog input modules that target 4–20 mA or ±10 V ranges, the 1771-NC15 is purpose-built for the microvolt-to-millivolt signal domain. Thermocouple outputs are inherently low-amplitude — a Type K thermocouple produces approximately 41 µV/°C — and any noise ingress, ground loop, or impedance mismatch at the input stage translates directly into temperature measurement error. The 1771-NC15 addresses this through a differential input architecture with high common-mode rejection, hardware cold junction compensation, and isolated signal conditioning circuitry that preserves signal fidelity from field terminal to backplane data word.
The module occupies a single slot in any standard 1771 I/O chassis and communicates with the PLC-5 processor via the 1771 parallel backplane bus. Data transfer follows the block-transfer read (BTR) protocol native to the PLC-5 instruction set, meaning no custom driver or firmware modification is required for integration into existing PLC-5 programs. The processor reads the module’s data table through a BTR instruction, and the 1771-NC15 returns a structured data block containing converted engineering-unit values, channel status bits, and diagnostic flags — giving the control program full visibility into both process values and module health.
Real-time Stock & RFQ: [email protected] | WhatsApp: +86 18359268345
Technical Parameters
| Parameter | Specification |
|---|---|
| Part Number | 1771-NC15 |
| Manufacturer | Allen-Bradley / Rockwell Automation |
| Module Family | 1771 PLC-5 I/O Series |
| Module Type | Analog Input — Thermocouple / Millivolt |
| Input Signal Range | Thermocouple (J, K, T, E, R, S, B types); Millivolt (±100 mV) |
| Resolution | 16-bit (including sign bit) |
| Cold Junction Compensation | Hardware-based, internal reference junction |
| Input Impedance | >1 MΩ differential |
| Common-Mode Rejection | >120 dB at 50/60 Hz |
| Backplane Interface | 1771 parallel I/O bus (Block Transfer Read/Write) |
| Chassis Compatibility | 1771-A1B, A2B, A3B, A4B I/O chassis |
| Processor Compatibility | PLC-5/10, 5/15, 5/20, 5/25, 5/30, 5/40, 5/60, 5/80 |
| Operating Temperature | 0 °C to +60 °C |
| Storage Temperature | −40 °C to +85 °C |
| Relative Humidity | 5% to 95% non-condensing |
| Power Consumption | Supplied via 1771 backplane (refer to chassis power budget) |
| Isolation | Optical isolation between field inputs and backplane logic |
| Certifications | UL Listed, CE Marked |
| Form Factor | Single-slot 1771 I/O module |
| Warranty | 12 months from date of shipment |
Hardware Logical Analysis
The 1771-NC15’s input stage employs a fully differential amplifier topology with a programmable gain stage ahead of the analog-to-digital converter. This architecture is not incidental — it is a deliberate response to the electrical environment in which thermocouple circuits operate. Industrial field wiring runs alongside power cables, variable-frequency drives, and inductive loads, all of which inject common-mode noise onto the signal pair. The differential input rejects this noise by amplifying only the voltage difference between the two conductors, while the common-mode rejection ratio exceeding 120 dB at line frequency ensures that even 10 V of common-mode interference produces less than 10 µV of equivalent input error — well below the resolution threshold for any supported thermocouple type.
Cold junction compensation is implemented in hardware rather than software. A precision thermistor mounted at the module’s terminal block continuously measures the reference junction temperature. This value is used by the analog front-end to apply the inverse thermocouple polynomial correction before the signal reaches the ADC. Hardware compensation eliminates the latency and scan-cycle dependency that software-based compensation introduces, and it remains active regardless of processor program state — a critical distinction during processor fault conditions where software execution halts but field measurements must remain valid for safety monitoring.
The optical isolation barrier between the field input circuitry and the 1771 backplane logic serves two functions: it breaks ground loops that would otherwise form between field instrument grounds and the controller chassis ground, and it provides a defined withstand voltage boundary that protects the backplane from transient overvoltage events originating in the field wiring. The isolation boundary is rated to withstand the transient energy levels specified in IEC 61000-4-5 surge immunity testing, making the module suitable for deployment in environments with frequent switching transients from motor starters and solenoid valves on shared power distribution systems.
The backplane interface logic implements the 1771 block-transfer protocol with a dedicated co-processor that manages the BTR/BTW handshake independently of the analog conversion cycle. This means the analog-to-digital conversion runs at its own fixed rate — determined by the module’s internal clock and the number of active channels — while the backplane interface services data requests from the PLC-5 processor asynchronously. The result is that the processor’s program scan time does not directly gate the analog sampling rate, and the module can maintain consistent conversion timing even when the processor is executing long program scans or performing communication tasks.
System Integration Benefits
- Zero-modification backplane insertion: The 1771-NC15 conforms to the standard 1771 I/O module mechanical and electrical specification. It inserts into any open slot in a compatible chassis without chassis modification, adapter hardware, or firmware update to the PLC-5 processor.
- Native BTR/BTW protocol support: Integration requires only standard PLC-5 Block Transfer Read instructions. No custom function blocks, add-on instructions, or third-party drivers are needed, preserving existing program structure and reducing validation effort.
- Per-channel diagnostic status bits: The module’s data table includes open-circuit detection flags for each input channel. An open thermocouple drives the channel to a defined out-of-range value and sets the corresponding status bit, enabling the PLC-5 program to distinguish a genuine process excursion from a wiring fault without additional field instrumentation.
- Engineering-unit output scaling: Converted values are returned in tenths of a degree (°C or °F, configuration-dependent), eliminating the need for scaling rungs in the PLC-5 program and reducing the risk of scaling errors during commissioning or program modification.
- Multi-thermocouple type support within a single module: Individual channels can be configured for different thermocouple types, allowing a single 1771-NC15 to serve mixed-sensor installations without requiring separate modules for each thermocouple type.
- Deterministic scan-independent sampling: The module’s internal conversion clock operates independently of the PLC-5 program scan, ensuring consistent analog sampling intervals regardless of processor load — a requirement for accurate process trend data and alarm response timing.
- Chassis power budget compatibility: The module’s backplane power draw is within the budget of all standard 1771 chassis power supplies, including the 1771-P4 and 1771-P6, without requiring power supply derating in typical multi-module configurations.
- Long-term spare parts availability: The 1771 I/O form factor and backplane protocol are stable and well-documented. Replacement modules sourced from verified distributors are drop-in compatible without chassis reconfiguration, supporting MRO strategies for facilities with extended PLC-5 lifecycle commitments.
Quality Assurance & Global Logistics
Every Allen-Bradley 1771-NC15 unit supplied through siemensplc.com is sourced from verified supply channels and subjected to a structured pre-shipment inspection process. Visual examination covers board-level component condition, terminal block integrity, and manufacturer label authenticity against Rockwell Automation documentation standards. Functional verification — where unit condition permits — includes backplane power-on response and channel output confirmation. Units are packaged in ESD-protective anti-static bags with moisture barrier film, placed in rigid foam-lined cartons rated for international air freight handling.
Shipments originate from Xiamen, China, a major logistics hub with direct access to international express carriers including DHL, FedEx, and UPS. Standard international delivery to Europe, the Middle East, Southeast Asia, and North America is achieved within 3–7 business days from order confirmation. Expedited same-day dispatch is available for orders confirmed before the daily cutoff. All shipments include full tracking, commercial invoice, and packing list documentation. A 12-month warranty covers manufacturing defects and functional failure under normal operating conditions, with advance replacement available for critical production applications.
Contact Information
Email: [email protected]
WhatsApp: +86 18359268345
Web: siemensplc.com
Location: Xiamen, China
© 2026 siemensplc.com. All rights reserved.