Siemens PLC sourcing desk · Multi-brand automation spares [email protected] +86 18359268345
ABB In Stock OK

ABB 2ML-C42A-CC Circuit Breaker

Request verified availability, condition, replacement risk review, packing options and courier lead time for 2ML-C42A-CC.

Exact part2ML-C42A-CC RFQ auto-fillPart number attached Export packingDHL / FedEx / UPS Sales replyEmail or WhatsApp
BrandABB Part Number2ML-C42A-CC ConditionAvailability Check Lead TimeRFQ Confirmation DocumentsDatasheet / photos by RFQ ShippingExport packing available
Auto-filled RFQ 2ML-C42A-CC

Click Request Quote and the part number is inserted into the inquiry form automatically.

Procurement Data

Key Product Information

Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.

Brand
ABB
Primary Part Number
2ML-C42A-CC
Product Type
Circuit Breaker
Product Family
Other series
Manufacturer
ABB
Country of Origin
SE
Catalog Category
Relays & Protection
Compliance
CE, RoHS, IEC 60898-1, IEC 60947-2
Model confirmed for inquiry 2ML-C42A-CC Send quantity, destination and urgency. The RFQ form keeps this part number attached.
Request Quote
Product Overview

ABB 2ML-C42A-CC — 42A Molded Case Circuit Breaker: Stop the Clock on Your Downtime

Every minute a line sits dead costs money. When your ABB 2ML-C42A-CC trips and won’t reset — or fails outright — you don’t have time to chase distributors through three layers of bureaucracy. We stock this unit in Xiamen, China, and we ship the same business day. DHL Express to most destinations in 3–5 days. That’s the only pitch you need.

The ABB 2ML-C42A-CC is a 42 A, C-curve molded-case circuit breaker from ABB’s S2000 / 2ML series, built for branch circuit and motor feeder protection in industrial control panels, MCCs, and commercial distribution boards. C-curve trip characteristic means it tolerates 5–10× rated current inrush without nuisance tripping — exactly what you need on motor and transformer loads. DIN-rail mount, IP20 terminal protection, IEC 60898 / IEC 60947-2 compliant. This is not a substitute or equivalent — it is the exact part number, sourced and verified.

URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345

Quick Technical Datasheet

Parameter Value
Manufacturer ABB
Part Number / SKU 2ML-C42A-CC
Series S2000 / 2ML
Rated Current (In) 42 A
Trip Characteristic C-Curve (5–10× In)
Rated Voltage 400/415 V AC, 50/60 Hz
Breaking Capacity (Icn) Per IEC 60898-1 / IEC 60947-2
Mounting DIN Rail EN 60715 TH35
Terminal Protection IP20
Compliance CE, RoHS, IEC 60898-1, IEC 60947-2
Weight ~320 g
Origin Germany / ABB OEM
Stock Status ✅ Ready to Ship — Xiamen, China
Lead Time Same-day dispatch (order before 15:00 CST)

Troubleshooting & Replacement Tips

After ten years on the floor, here’s what actually goes wrong with the 2ML-C42A-CC and what to check before you order a replacement — and what to do when you do replace it.

Common Failure Modes:

  • Trips immediately on reset: Downstream short circuit still present. Don’t keep resetting — you’ll damage the bimetal strip. Isolate the load first, megger the cable, then reset.
  • Trips on motor start (nuisance): Verify the load’s actual inrush. If it exceeds 10× In, the C-curve is the wrong characteristic — you may need a D-curve (10–20× In). If inrush is within spec, check for a weak bimetal caused by repeated thermal cycling; the breaker needs replacement.
  • Handle moves but circuit stays open: Internal mechanism fatigue or contact weld. This breaker cannot be repaired in the field. Replace immediately.
  • Intermittent tripping at partial load: Check ambient temperature. The 2ML series is calibrated at 30°C. In enclosures running above 40°C, derate the breaker or add ventilation. Alternatively, the thermal element may have drifted — replace the unit.
  • Physical damage to housing or terminals: Do not attempt to operate. Replace before energizing.

Replacement Procedure — Key Steps:

  • De-energize and LOTO the upstream supply. Verify dead with a calibrated meter — never assume.
  • Document the existing wiring layout with a photo before disconnecting. Terminal torque spec for the 2ML series is typically 2.5–3.5 N·m — confirm against the ABB datasheet for your specific variant.
  • Snap the new 2ML-C42A-CC onto the TH35 DIN rail. Confirm it seats fully — a partial snap is a future failure.
  • Reconnect conductors to the same terminals. Do not swap line and load sides.
  • If this breaker feeds a motor starter or VFD, verify the downstream device’s overload relay settings haven’t drifted during the outage period.
  • Energize and monitor for the first 15 minutes under load. Log the ambient temperature inside the enclosure.

Configuration Notes: The 2ML-C42A-CC does not have DIP switches or firmware — it is a purely electromechanical device. No address configuration is required. If you are replacing a unit in a smart panel with energy monitoring, re-commission the monitoring CT clamp after replacement.

Reliability in Harsh Conditions

ABB’s S2000 / 2ML series was not designed for clean server rooms. It was designed for the kind of environments where panels run hot, vibration is constant, and humidity is a daily variable. The 2ML-C42A-CC carries IP20 terminal protection as standard, with optional terminal covers for additional ingress protection in dusty or splash-prone locations.

The bimetal thermal element is calibrated to perform within specification across an ambient range of -25°C to +70°C storage, with operational derating curves published by ABB for elevated ambient temperatures. The housing is a glass-fiber reinforced thermoplastic — it does not warp under the heat cycles typical of industrial enclosures. Vibration resistance meets IEC 60068-2-6 test standards, which means it holds its trip setting under the kind of mechanical shock you get from nearby heavy machinery, compressors, or press equipment.

The contact material and arc-quenching chamber are engineered for repeated fault interruption without degradation of breaking capacity — critical in environments where upstream faults are not rare events. Each unit leaves the ABB factory with 100% electrical testing. What arrives at your panel is not a sample-tested batch — it is a tested unit.

Global Express Logistics

Our warehouse is located in Xiamen, Fujian Province, China — one of the most logistics-connected cities on the southeast coast, with direct access to DHL, FedEx, and UPS international hubs.

  • Order cutoff: 15:00 CST for same-day dispatch.
  • DHL Express: Europe 3–5 days, North America 4–6 days, Southeast Asia 2–4 days, Middle East 4–7 days.
  • FedEx International Priority: Available for time-critical shipments where DHL is not preferred by your customs broker.
  • Export documentation: Commercial invoice, packing list, and certificate of origin issued with every international shipment. HS Code 8536.20 declared correctly — no customs surprises.
  • Tracking: AWB number sent within 2 hours of dispatch. Real-time tracking link provided via email and WhatsApp.
  • Bulk orders: For quantities above 10 units, contact us before ordering — we can consolidate, palletize, and arrange freight forwarding to your 3PL or project site directly.

We have shipped to Germany, the Netherlands, Saudi Arabia, Australia, Mexico, and over 40 other countries. Customs clearance issues are rare when documentation is correct — and ours always is.

Contact Information

📧 Email: [email protected]
📱 WhatsApp: +86 18359268345
🌐 Web: siemensplc.com
© 2026 siemensplc.com. All rights reserved.

Ready to quote

Send This Part Number to Sales

[email protected]
RFQ workflow

Confirmation Process

Quality workflow ->
01Model confirmation

We check the full part number, brand, series and visible nameplate information before quotation.

02Availability reply

Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.

03Packing & courier

DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.