Siemens PLC sourcing desk · Multi-brand automation spares [email protected] +86 18359268345
ABB In Stock OK

ABB DSTD110A 57160001-TZ DCS Terminal Board

Request verified availability, condition, replacement risk review, packing options and courier lead time for 57160001-TZ.

Exact part57160001-TZ RFQ auto-fillPart number attached Export packingDHL / FedEx / UPS Sales replyEmail or WhatsApp
BrandABB Part Number57160001-TZ ConditionAvailability Check Lead TimeRFQ Confirmation DocumentsDatasheet / photos by RFQ ShippingExport packing available
Auto-filled RFQ 57160001-TZ

Click Request Quote and the part number is inserted into the inquiry form automatically.

Procurement Data

Key Product Information

Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.

Brand
ABB
Primary Part Number
57160001-TZ
Product Type
DCS Terminal Board
Series / Family
ADVANT
Manufacturer
ABB (Asea Brown Boveri)
Country of Origin
SE
Catalog Category
I/O Modules
Warranty
90-day DOA replacement guarantee
Model confirmed for inquiry 57160001-TZ Send quantity, destination and urgency. The RFQ form keeps this part number attached.
Request Quote
Product Overview

ABB DSTD110A 57160001-TZ: Stop the Clock on Your DCS Downtime — Ships Within 24 Hours

Your MASTERPIECE or ADVANT controller just lost a digital output channel. The solenoid valve isn’t responding. The motor starter won’t energize. The board is dead and production is standing still. Every hour you wait costs real money — in a refinery or power plant, that figure can exceed $50,000/hr. The DSTD110A terminal board is not a glamorous component, but when it fails, nothing downstream moves. We stock it. We test it. We ship it today.

The ABB DSTD110A (factory part number 57160001-TZ) is the field-wiring termination board for digital output I/O modules in the MASTERPIECE 200/1 and ADVANT AC-series DCS platforms. It sits between your I/O module connector and your field cable marshalling — handling screw-terminal landing, channel-to-channel isolation, and signal conditioning for discrete output signals driving solenoids, relays, motor starters, and indicator lamps. No firmware. No configuration. Hardware swap only. That’s exactly what you need when the clock is running.

URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345

Quick Technical Datasheet

Parameter Value
Manufacturer ABB (Asea Brown Boveri)
Part Number DSTD110A / 57160001-TZ
Module Category Digital Output Terminal Board
Compatible Platform MASTERPIECE 200/1 | ADVANT AC 110 / AC 160 / AC 410 / AC 450
Signal Type Discrete Digital Output (DO)
Board Function Field-wiring termination & marshalling for DO I/O modules
Firmware None — passive termination board
Mounting DIN rail / rack-mount per cabinet configuration
Weight ~400 g
Condition Surplus / Refurbished — bench-tested before dispatch
Stock Status ✔ Ready to Ship — Xiamen warehouse
Dispatch Lead Time Within 24 hours of order confirmation
Warranty 90-day DOA replacement guarantee

Troubleshooting & Replacement Tips

Common failure signatures that point to the DSTD110A:

  • DCS diagnostic shows DO channel fault or open-circuit alarm on a specific I/O module slot — but swapping the I/O module itself doesn’t clear the fault. The terminal board is the next suspect.
  • Intermittent output dropout on one or more channels under vibration or thermal cycling — classic sign of a cracked solder joint or fatigued screw terminal on the DSTD110A.
  • Field device (solenoid, relay) not energizing despite correct controller output command and confirmed 24 VDC supply at the cabinet — check continuity across the terminal board screw terminals first.
  • Visible burn marks, discoloration, or corrosion on the PCB near the field-wiring connector — immediate replacement required, do not attempt to clean and re-use.

Replacement procedure — field-tested steps:

  1. Isolate the affected I/O module slot. Place the controller in manual or inhibit the affected DO group via the DCS engineering station before touching any hardware. Never hot-swap a terminal board without confirming the output state is safe.
  2. Label every field wire before disconnecting. Photograph the terminal board wiring from multiple angles. The DSTD110A uses numbered screw terminals — cross-reference against your as-built loop drawings before pulling a single wire.
  3. Disconnect the I/O module ribbon/connector first, then remove field wiring from the terminal board screw terminals in sequence. Keep the wires bundled and tagged.
  4. Seat the replacement DSTD110A. This is a passive board — no DIP switches, no address jumpers, no firmware to load. Confirm the board revision matches your I/O module pairing if your site has mixed revisions in the same cabinet.
  5. Re-land field wiring to the correct terminal numbers. Torque screw terminals to spec (typically 0.5–0.6 Nm for 1.5 mm² conductors). A loose terminal is the most common cause of intermittent DO faults post-replacement.
  6. Reconnect the I/O module, restore the slot, and force-test each output channel from the DCS engineering station before returning the loop to automatic. Verify field device response at the actuator, not just at the controller diagnostic screen.
  7. Clear any latched fault alarms in the DCS and confirm the channel health status returns to normal. Log the replacement in your site maintenance management system (CMMS) with the old board’s serial number.

Configuration note: The DSTD110A itself carries no configurable parameters — it is a passive termination board. However, if your site runs mixed I/O module revisions (e.g., DSDO110A vs. DSDO110B), confirm the terminal board revision compatibility in the ABB module pairing matrix before installation. Mismatched revisions in some cabinet configurations can cause channel mapping offsets.

Reliability in Harsh Conditions

The DSTD110A was engineered for continuous-process environments where “harsh” is the baseline, not the exception. ABB designed the MASTERPIECE/ADVANT I/O termination layer to operate without complaint in conditions that would degrade consumer-grade electronics within weeks.

  • Thermal cycling: Rated for operation across a wide industrial temperature range. In power generation and petrochemical applications, cabinet temperatures routinely swing 30–40°C between cold startup and full-load operation. The DSTD110A’s industrial-grade PCB substrate and component selection handle this without delamination or solder fatigue under normal service life.
  • Vibration: Installed in compressor buildings, pump stations, and turbine halls where structural vibration is constant. The board’s rigid mounting and conformal-coated PCB (on later revisions) resist vibration-induced connector fretting and trace cracking.
  • Humidity and contamination: In pulp & paper and chemical plants, airborne moisture, process gases, and particulate contamination are unavoidable. The DSTD110A’s screw-terminal design minimizes exposed contact surface area, and conformal coating on the PCB provides a barrier against condensation and corrosive atmospheres.
  • EMI/RFI immunity: The passive termination architecture means the board introduces no active switching noise into the field wiring. Combined with the ADVANT system’s inherent EMI shielding design, the DSTD110A maintains signal integrity even in high-noise environments adjacent to VFDs, large motors, and high-voltage switchgear.

Every unit we ship has been inspected for physical damage, corrosion, and component integrity. Boards showing any sign of thermal stress, PCB delamination, or terminal damage are rejected — not refurbished and resold. What you receive has been bench-verified against a known-good reference system.

Global Express Logistics

We operate from Xiamen, China — one of the most logistics-connected export hubs on the eastern seaboard, with direct access to DHL, FedEx, and UPS international express networks. When your plant is down, air freight is not a luxury — it is the only rational choice, and we are set up to execute it fast.

  • Order cutoff: Orders confirmed before 14:00 CST are packed and handed to the carrier the same business day.
  • Packaging: Anti-static ESD bag, foam-lined rigid carton, moisture-barrier outer wrap. The board arrives in the same condition it left our warehouse.
  • Transit times (express air): Southeast Asia 1–2 days | Middle East 2–3 days | Europe 3–4 days | North America 3–5 days | South America / Africa 4–6 days.
  • Documentation: Commercial invoice, packing list, and country-of-origin certificate provided as standard. CITES/dual-use export declarations handled where applicable. We have shipped to over 40 countries without customs clearance issues.
  • Tracking: AWB number provided within 2 hours of dispatch. Real-time tracking link sent directly to your procurement contact.
  • Emergency freight: For critical shutdowns, we can arrange next-flight-out courier on request. Contact us directly on WhatsApp for fastest response.

Contact Information

Email: [email protected]
WhatsApp: +86 18359268345
Web: siemensplc.com
© 2026. All rights reserved.

Ready to quote

Send This Part Number to Sales

[email protected]
RFQ workflow

Confirmation Process

Quality workflow ->
01Model confirmation

We check the full part number, brand, series and visible nameplate information before quotation.

02Availability reply

Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.

03Packing & courier

DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.