- Operating Temp.
- 0 °C to +60 °C
Siemens 6EP1334-1LB00 — Stop the Clock on Your Downtime. Ship Today.
Every minute your line is down, you’re bleeding money. The Siemens 6EP1334-1LB00 SITOP PSU100L 24 VDC / 10 A power supply is one of the most common single points of failure in SIMATIC S7 control panels — and when it goes, it takes everything with it. We stock it. We ship it today. From Xiamen to your dock, DHL Express, no excuses.
This is not a generic listing. This is a field-sourced, 100% original Siemens unit, pulled from verified supply chains, inspected before it leaves our warehouse. If your maintenance team is standing in front of a dead panel right now, this is the page they need.
URGENT REQUIREMENT? Contact: [email protected] | WhatsApp: +86 18359268345
Quick Technical Datasheet
| Parameter | Specification |
|---|---|
| Part Number | 6EP1334-1LB00 |
| Series | SITOP PSU100L |
| Brand | Siemens AG |
| Input Voltage | 120 / 230 VAC wide-range, auto-select |
| Input Frequency | 50 / 60 Hz |
| Output Voltage | 24 VDC (adjustable 22.8 – 26.4 V) |
| Output Current | 10 A continuous |
| Output Power | 240 W |
| Efficiency | ≥ 89% |
| Ripple & Noise | ≤ 150 mV peak-to-peak |
| Protection | Overload / Short-circuit / Overvoltage |
| Mounting | 35 mm DIN rail |
| Dimensions (W×H×D) | 55 × 125 × 125 mm |
| Weight | approx. 0.8 kg |
| Operating Temperature | 0 °C to +60 °C |
| Storage Temperature | −40 °C to +85 °C |
| Protection Degree | IP20 |
| Certifications | CE, UL, cUL, ATEX Zone 2 |
| MTBF | > 500,000 hours |
| Origin | Germany |
| Stock Status | ✅ Ready to Ship — Xiamen Warehouse |
Troubleshooting & Replacement Tips
After handling hundreds of PSU100L failures in the field, here’s what actually matters when you’re doing a hot swap under pressure:
Common Failure Signatures
- DC OK LED off, no output voltage: Classic internal capacitor failure or blown primary fuse. Don’t waste time probing — swap the unit.
- Output voltage present but unstable (flickering HMI, random CPU resets): Output capacitor degradation. The PSU is dying slowly. Replace before it takes the CPU with it.
- Overload LED latched on: Check downstream load first — a shorted 24 VDC field device will keep tripping the PSU. Disconnect loads in segments to isolate the fault before condemning the supply.
- Intermittent DC OK signal triggering S7 CPU STOP: The DC OK relay contact (terminals 11/12) may be chattering. Verify wiring integrity and contact resistance before replacing the PSU.
- Unit warm to touch but no output: Thermal shutdown triggered by blocked ventilation or ambient above 60 °C. Clear airflow, let it cool 10 minutes, then retest before ordering a replacement.
Replacement Procedure — Step by Step
- Step 1 — Isolate: De-energize the panel. Lock out / tag out per your site procedure. Confirm 0 VAC at input terminals with a calibrated meter — do not trust the breaker alone.
- Step 2 — Document: Photograph terminal wiring before disconnecting anything. The PSU100L uses screw terminals; label each wire if your panel drawing is not current.
- Step 3 — Remove: Loosen input terminals (L, N, PE) and output terminals (+ and −). Slide the DIN rail latch down and tilt the unit off the rail. No tools required beyond a flat-blade screwdriver.
- Step 4 — Inspect: Check the DIN rail clip on the new unit before mounting. Verify the output voltage trim pot is at center position (factory default = 24.0 V). Do not adjust unless your system requires a non-standard setpoint.
- Step 5 — Mount & Wire: Clip onto rail, reconnect PE first, then L and N, then DC output + and −. Torque to 0.5–0.6 Nm on input terminals, 0.5 Nm on output terminals. Do not overtighten — the terminal blocks are plastic-bodied.
- Step 6 — Commission: Energize with loads disconnected. Verify 24.0 VDC ±0.5 V at output terminals. Confirm DC OK LED is solid green. Reconnect loads progressively. Monitor for 5 minutes before returning to automatic operation.
- No DIP switches, no firmware, no addressing required. The PSU100L is a passive supply — plug and play once wired correctly.
Configuration Notes
- Output voltage is adjustable via front-panel trim pot — factory set to 24.0 V. Only adjust if your system explicitly requires a different setpoint (e.g., long cable runs requiring voltage compensation).
- The DC OK relay output (terminals 11/12, normally open) can be wired to a CPU digital input for predictive fault detection. If your existing installation uses this feature, verify the new unit’s relay wiring matches.
- For parallel redundant configurations using a SITOP redundancy module (6EP1961-2BA11), ensure both PSUs are trimmed to identical output voltages before enabling the redundancy module.
Reliability in Harsh Conditions
The PSU100L was not designed for a clean server room. It was designed for the kind of environment where your panel is next to a press, a furnace, or a coastal compressor station. Here’s what it handles without complaint:
- Vibration: Tested to IEC 60068-2-6 (sinusoidal) and IEC 60068-2-27 (shock). The DIN rail mounting provides mechanical damping; the internal components are conformal-coated on production variants. In high-vibration applications (presses, compressors), verify the DIN rail end-stops are tight — a loose PSU will fail prematurely regardless of brand.
- Temperature: Rated 0 °C to +60 °C continuous. Derating applies above 45 °C — output current must be reduced by approximately 2.5% per degree above 45 °C. At 60 °C, maximum continuous output is approximately 6.25 A. If your panel regularly exceeds 50 °C ambient, size up to the 20 A variant or add forced ventilation.
- Humidity: Rated to 95% RH non-condensing. In coastal or high-humidity environments, ensure the panel door seal is intact. Condensation on PCB traces is the primary cause of premature PSU failure in tropical installations — not the unit itself.
- EMC: Compliant with EN 61000-6-2 (industrial immunity) and EN 61000-6-4 (industrial emissions). The wide-range input includes active PFC, which reduces harmonic disturbance on shared supply circuits — relevant in facilities with large VFD loads on the same distribution panel.
- ATEX Zone 2: Certified for use in areas with occasional explosive atmosphere risk. Verify your installation zone classification before specifying — Zone 1 requires a different product family.
Global Express Logistics
Our warehouse is in Xiamen, Fujian — one of China’s primary industrial export hubs with direct access to DHL, FedEx, and UPS international gateways. Here’s how your order moves:
- Order confirmed before 15:00 CST: Same-day dispatch. Tracking number issued within 2 hours of pickup.
- DHL Express Worldwide: Xiamen → most European destinations in 2–3 business days. Southeast Asia in 1–2 days. North America in 3–4 days.
- FedEx International Priority: Available on request for destinations where FedEx has stronger coverage (Middle East, South Asia, Latin America).
- Documentation: Commercial invoice, packing list, and certificate of origin issued with every shipment. HS code 8504.40 (static converters). ECCN EAR99 — no export license required for most destinations.
- Customs clearance: We declare accurate values and descriptions. No under-declaration. If your import team needs specific documentation (EUR.1, Form A, or country-specific certificates), advise at time of order.
- Emergency freight: For critical plant-down situations, contact us directly via WhatsApp for same-day courier booking and priority handling. We have handled emergency shipments to offshore platforms, remote mining sites, and island facilities — if there’s a flight, we’ll get it on it.
Contact Information
Your line cannot wait. Reach us now:
- Email: [email protected]
- WhatsApp: +86 18359268345
- Web: siemensplc.com
© 2026 siemensplc.com. All rights reserved.
Send This Part Number to Sales
Confirmation Process
We check the full part number, brand, series and visible nameplate information before quotation.
Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.
DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.