- Brand
- Siemens
- Primary Part Number
- 6GK1503-2CC00
- Product Type
- Optical Link Module
- Series / Family
- SIMATIC
- Country of Origin
- DE
- Catalog Category
- Communication
- Operating Temp.
- 0 °C to +60 °C
- Warranty
- 12 months from date of shipment
Siemens 6GK1503-2CC00 PROFIBUS Optical Link Module — Fiber Segment Conversion in High-EMI Industrial Networks
The Siemens 6GK1503-2CC00 is a PROFIBUS Optical Link Module (OLM) designed to convert RS-485 electrical bus signals into multimode glass-fiber optical signals, enabling noise-immune, long-distance PROFIBUS DP/FMS network segments in demanding industrial environments. Positioned within the SINEC L2 product family, this module addresses the fundamental challenge of signal integrity degradation over copper in high electromagnetic interference (EMI) zones — including drive cabinets, welding cells, and high-voltage switchgear rooms — by eliminating the conductive path between bus segments entirely.
In a PROFIBUS control loop, the OLM occupies the physical layer boundary between copper and fiber media. Each 6GK1503-2CC00 unit terminates one RS-485 electrical segment and bridges it to two ST-connector multimode fiber ports, allowing the module to participate in both line and redundant ring topologies. The integrated redundancy manager function enables automatic reconfiguration of a fiber ring within the PROFIBUS-specified reconfiguration time, maintaining deterministic bus cycle times even during a single fiber break event.
📦 Real-time Stock & RFQ: [email protected] | WhatsApp: +86 18359268345
Technical Parameters
| Parameter | Value |
|---|---|
| Part Number | 6GK1503-2CC00 |
| Product Family | SINEC L2 / PROFIBUS OLM |
| Electrical Interface | RS-485, Sub-D 9-pin (1 × port) |
| Optical Interface | 2 × ST fiber connectors (multimode) |
| Fiber Type | Multimode glass fiber, 62.5/125 µm or 50/125 µm |
| Optical Wavelength | 850 nm |
| Max. Fiber Segment Length | 3,000 m (per segment, multimode) |
| Supported Baud Rates | 9.6 kbps – 12 Mbps (auto-detection) |
| Supply Voltage | 24 V DC (permissible range: 18–32 V DC) |
| Power Consumption | ≤ 3.5 W |
| Operating Temperature | 0 °C to +60 °C |
| Storage Temperature | −40 °C to +70 °C |
| Relative Humidity | 5 % to 95 % (non-condensing) |
| Protection Class | IP20 |
| Mounting | 35 mm DIN rail (EN 60715) |
| Dimensions (W × H × D) | 45 × 110 × 75 mm |
| Weight | 340 g |
| Certifications | CE, UL, cUL; ATEX Zone 2 available on -2CC10 variant |
| Country of Origin | Germany |
| Warranty | 12 months from date of shipment |
Hardware Logical Analysis
The 6GK1503-2CC00 implements full galvanic isolation between its RS-485 electrical port and the optical transmit/receive circuitry. The isolation barrier — rated to withstand transient voltages typical of industrial bus environments — prevents ground loop currents and common-mode noise from propagating across segment boundaries. This is particularly relevant in installations where PROFIBUS segments span separate electrical panels or buildings with differing ground potentials.
The optical transmitter uses an 850 nm LED source matched to the attenuation characteristics of 62.5/125 µm multimode fiber. The receiver incorporates an avalanche photodiode (APD) front-end with automatic gain control (AGC), maintaining a consistent signal threshold across the full 3,000 m segment length without requiring manual optical power adjustment. The AGC circuit compensates for fiber aging and connector contamination within the specified optical power budget.
Baud rate detection is handled by a dedicated synchronization circuit that monitors the RS-485 signal timing on the electrical port and locks to the active baud rate within the first valid PROFIBUS telegram. This eliminates the need for DIP-switch baud rate configuration — a common source of commissioning errors in multi-vendor installations — and allows the module to adapt automatically if the master’s baud rate is changed during system reconfiguration.
The redundancy manager logic embedded in the 6GK1503-2CC00 monitors optical signal presence on both fiber ports continuously. Upon detection of a fiber break or optical power loss below threshold, the redundancy manager isolates the affected segment and reconfigures the ring topology within the PROFIBUS-specified reconfiguration window, preserving bus cycle determinism for connected slaves. This logic operates independently of the PLC master, requiring no software intervention or parameter change.
EMC design follows IEC 61000-4 series test levels for conducted and radiated immunity, with the module’s metal housing providing shielding continuity for the RS-485 cable shield connection at the Sub-D connector. The power supply input includes transient suppression to IEC 61000-4-5 (surge) and IEC 61000-4-4 (burst) requirements, consistent with industrial cabinet installation environments.
System Integration Benefits
- Galvanic isolation eliminates ground loop interference: The optical barrier between RS-485 and fiber ports removes the conductive path responsible for common-mode noise injection, a primary cause of CRC errors on long copper PROFIBUS runs.
- 3,000 m per fiber segment extends plant topology: Enables inter-building PROFIBUS links and large-footprint process plant layouts without repeaters or signal boosters on the fiber span.
- Auto baud-rate detection reduces commissioning time: No manual DIP-switch configuration required; the module locks to the active baud rate from 9.6 kbps to 12 Mbps within the first bus cycle.
- Integrated ring redundancy manager maintains deterministic response: Automatic ring reconfiguration upon fiber break preserves PROFIBUS cycle time without PLC master intervention or parameter download.
- Transparent to PROFIBUS protocol stack: The OLM operates at the physical layer only; no address configuration, no protocol overhead, and no impact on DP cycle time calculation.
- Compatible with full SIMATIC ecosystem: Direct integration with S7-300, S7-400, S7-1500 (via CP modules), ET 200M/S/SP distributed I/O, SINAMICS drives, and WinCC SCADA without additional gateways.
- Supports line, tree, and redundant ring topologies: A single module type covers all standard PROFIBUS fiber topologies, simplifying spare parts inventory and engineering documentation.
- Diagnostic LED indicators provide local fault visibility: Separate LEDs for power, RS-485 activity, and optical port status allow field technicians to isolate faults at the module level without laptop tools or bus analyzers.
Quality Assurance & Global Logistics
Every 6GK1503-2CC00 unit supplied by siemensplc.com is sourced as genuine Siemens hardware, traceable to authorized distribution channels. Prior to shipment, each module undergoes a structured inspection protocol: visual examination of housing, label, and connector integrity; verification of serial number against Siemens product traceability records; and functional power-on testing confirming LED status, optical port continuity, and RS-485 signal response.
Units are shipped from our warehouse in Xiamen, China, with access to major international freight lanes including DHL Express, FedEx International Priority, and UCP air freight consolidation. Standard in-stock orders are dispatched within 1–3 business days. Export documentation — including commercial invoice, packing list, and certificate of origin — is prepared to comply with customs requirements for industrial electronics in target markets across Europe, Southeast Asia, the Middle East, and the Americas.
A 12-month warranty applies from the date of shipment, covering manufacturing defects and functional failures under normal operating conditions. Warranty claims are processed with a direct replacement or credit note; no return-to-manufacturer delays. Technical documentation including the Siemens product datasheet, manual reference (6GK1503-2CC00 BA), and test report is available upon request at the time of order.
Contact Information
Email: [email protected]
WhatsApp: +86 18359268345
Web: siemensplc.com
Location: Xiamen, China
© 2026 siemensplc.com. All rights reserved.
Send This Part Number to Sales
Confirmation Process
We check the full part number, brand, series and visible nameplate information before quotation.
Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.
DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.