Siemens PLC sourcing desk · Multi-brand automation spares [email protected] +86 18359268345
Request Quote
Schneider Electric In Stock OK

Schneider Electric LC1D18M7C AC Contactor – TeSys D Series

Request verified availability, condition, replacement risk review, packing options and courier lead time for LC1D18M7C.

Exact partLC1D18M7C RFQ auto-fillPart number attached Export packingDHL / FedEx / UPS Sales replyEmail or WhatsApp
BrandSchneider Electric Part NumberLC1D18M7C ConditionAvailability Check Lead TimeRFQ Confirmation DocumentsDatasheet / photos by RFQ ShippingExport packing available
Auto-filled RFQ LC1D18M7C

Click Request Quote and the part number is inserted into the inquiry form automatically.

Procurement Data

Key Product Information

Core fields for model confirmation and RFQ routing. Detailed product narrative remains below.

Brand
Schneider Electric
Primary Part Number
LC1D18M7C
Product Type
AC Contactor
Product Family
Other series
Country of Origin
FR
Catalog Category
Relays & Protection
Warranty
12 months from dispatch date
Model confirmed for inquiry LC1D18M7C Send quantity, destination and urgency. The RFQ form keeps this part number attached.
Request Quote
Product Overview

LC1D18M7C — 18A Three-Pole AC Contactor in the TeSys D Motor Control Platform

The Schneider Electric LC1D18M7C is a 18A frame, three-pole electromechanical contactor belonging to the TeSys D series — a globally standardized motor control platform engineered to IEC 60947-4-1 and EN 60947-4-1. The M7C suffix designates a 220V AC, 50/60 Hz control coil, making this variant the default specification for motor starter panels operating on standard single-phase control voltage in Asia-Pacific, European, and Middle Eastern industrial installations. This unit controls squirrel-cage induction motors up to 7.5 kW at 400V AC (AC-3 duty) and up to 4 kW at 220V AC, covering the majority of auxiliary machinery, pump, fan, and conveyor drive applications encountered in process and discrete manufacturing environments.

The LC1D18M7C occupies a well-defined position in the low-voltage switchgear hierarchy: downstream of the branch circuit protective device (MCCB or fuse combination unit) and upstream of the motor terminals, with an integrated 1 NO auxiliary contact that closes simultaneously with the three main poles. This auxiliary output feeds the PLC digital input module or pilot lamp circuit to provide closed-loop confirmation of contactor state — a fundamental requirement in any IEC 62061 or ISO 13849 safety-rated motor control circuit.

Real-time Stock & RFQ: [email protected] | WhatsApp: +86 18359268345

Technical Parameters

Parameter Value
Part Number / SKU LC1D18M7C
Brand Schneider Electric
Series TeSys D
Rated Operational Current (AC-3) 18 A
Conventional Thermal Current (Ith) 32 A
Motor Power @ 400V AC (AC-3) 7.5 kW
Motor Power @ 220V AC (AC-3) 4 kW
Main Poles 3 (L1/T1, L2/T2, L3/T3)
Integrated Auxiliary Contact 1 NO
Control Coil Voltage 220V AC, 50/60 Hz
Coil Inrush Power ~70 VA
Coil Sealed Power ~7 VA
Rated Insulation Voltage (Ui) 690 V
Rated Impulse Withstand Voltage (Uimp) 6 kV
Utilization Category AC-3 (squirrel-cage motors)
Mechanical Endurance 10,000,000 operations
Electrical Endurance (AC-3) 1,000,000 operations
Mounting 35 mm DIN rail (EN 60715) or screw panel
Terminal Conductor Range 1–10 mm² (screw clamp)
Degree of Protection IP20 (front face)
Operating Temperature Range -40°C to +60°C
Storage Temperature -60°C to +80°C
Vibration Resistance IEC 60068-2-6 compliant
Standards IEC 60947-4-1, EN 60947-4-1, UL 508, CSA C22.2 No. 14
Width 45 mm
Weight (with packaging) ~1,210 g
Country of Origin China (CN)
Warranty 12 months from dispatch date

Hardware Logical Analysis

The LC1D18M7C employs a double-break contact geometry on each main pole. Each phase conductor passes through two series-connected silver-alloy contact pairs, which halves the arc voltage per break point and distributes thermal energy across a larger contact surface area. At 18A AC-3 duty, this architecture extends contact erosion life significantly compared to single-break designs of equivalent frame size.

The electromagnetic actuator uses a laminated silicon-steel E-I core with a shading ring on the stationary pole face. The shading ring — a short-circuited copper band embedded in the core — generates a phase-shifted flux component that prevents the armature from releasing during the zero-crossing of the 50/60 Hz AC supply. Without this mechanism, the contactor would chatter at twice the supply frequency, generating acoustic noise and accelerating contact wear. The shading ring design is passive and requires no additional control circuitry, contributing to the unit’s 10-million-cycle mechanical endurance rating.

EMC performance is addressed at the coil circuit level. The A1–A2 coil terminals accept a LAD8N RC suppressor module (or varistor type LAD8FV), which clamps the inductive voltage spike generated when the coil de-energizes. Without suppression, this transient can reach 10–20× the supply voltage and couple into adjacent signal wiring or PLC output cards. The suppressor module mounts directly on the contactor body without additional panel space, keeping the suppression path as short as physically possible to minimize radiated emission.

The auxiliary contact block interface on the front face accepts LAD4 series snap-on blocks, adding up to four additional contacts (NO or NC in any combination) without modifying the main contactor wiring. The auxiliary contact mechanism is mechanically linked to the main armature through a rigid actuator bridge, ensuring that auxiliary contact state is a direct and deterministic reflection of main pole state — a requirement for safety-rated feedback circuits under IEC 62061 SIL 2 architectures.

System Integration Benefits

  • Deterministic Coil Response Time: Operate time (coil energized to main contacts closed) is typically 15–25 ms at rated voltage; release time is 10–20 ms. These bounded switching delays allow PLC ladder logic to implement accurate interlock timers without empirical tuning on each installation.
  • Direct Thermal Overload Relay Coupling: The LRD series overload relays (LRD14, LRD16, LRD18) clip directly onto the LC1D18M7C lower terminal block. The mechanical coupling eliminates inter-device wiring, reduces panel assembly time, and ensures the overload relay trip bar acts directly on the contactor reset mechanism.
  • Modular Auxiliary Contact Expansion: LAD4N01, LAD4N11, LAD4N20, and LAD4N02 blocks snap onto the front face without tools. Each block adds up to two contacts, enabling multi-point feedback to SCADA, safety relay, or pilot lamp circuits from a single contactor body.
  • Standardized DIN-Rail Footprint: The 45 mm width and EN 60715 rail compatibility allow the LC1D18M7C to be positioned adjacent to circuit breakers, terminal blocks, and other TeSys D components on a common rail without custom brackets or adapters.
  • Dual-Frequency Coil Compatibility: The 220V AC M7C coil operates on both 50 Hz and 60 Hz grids without derating. This eliminates the need for separate SKUs when supplying panels destined for different regional markets.
  • IEC and UL Dual Certification: A single part number satisfies both IEC 60947-4-1 (international) and UL 508 (North American) listing requirements, simplifying BOM management for OEM machine builders exporting to multiple markets.
  • Diagnostic Transparency via Auxiliary Contact: The integrated 1 NO auxiliary contact provides a hard-wired, real-time status signal to the PLC. Unlike soft-status signals derived from drive parameters, this contact reflects actual mechanical pole position, enabling the control system to detect welded-contact faults that would otherwise remain invisible.
  • Low Sealed-State Power Dissipation: At ~7 VA sealed coil consumption, a panel with 20 LC1D18M7C contactors in continuous-duty service dissipates only 140 VA from coil circuits — reducing panel cooling load and contributing to lower operating costs over the equipment lifecycle.
  • Vibration and Shock Tolerance: IEC 60068-2-6 compliance qualifies the unit for mobile plant, marine, and offshore installations where panel vibration levels would cause nuisance tripping or contact bounce in lower-grade contactors.
  • Long-Term Parts Availability: The TeSys D platform has maintained dimensional and electrical compatibility across multiple product generations. Replacement units, auxiliary blocks, and overload relays remain interchangeable, protecting the end-user’s maintenance inventory investment.

Quality Assurance & Global Logistics

Every LC1D18M7C unit supplied through siemensplc.com is sourced from Schneider Electric’s authorized distribution network and ships in original OEM packaging complete with CE marking, UL listing label, and batch traceability code. Prior to dispatch from our Xiamen, China facility, each unit undergoes incoming inspection: coil resistance measurement against the published nominal value (±10% tolerance), main contact continuity verification across all three poles, and visual inspection of the contact surface, arc chute, and terminal hardware.

Counterfeit risk is mitigated through exclusive sourcing from traceable authorized channels. Holographic authenticity labels and QR-based batch verification are available on request for project-critical procurement. Units are stored in a climate-controlled warehouse maintained at 15–25°C and 40–70% RH, within the published storage temperature envelope, to preserve contact surface integrity and coil insulation quality.

Logistics from Xiamen to major international destinations: DHL Express (2–4 business days to Europe, North America, Southeast Asia), FedEx International Priority (2–3 business days to the US), and SF Express International for regional Asia-Pacific delivery. Full export documentation — commercial invoice, packing list, certificate of origin (CO), and MSDS where required — is prepared for every shipment. Customs HS code 8536.49 applies to this product category. Bulk project orders above 50 units qualify for consolidated air freight with reduced per-unit logistics cost.

A 12-month warranty covers manufacturing defects under normal operating conditions. Warranty claims are processed with replacement dispatch within 5 business days of confirmed fault verification. Technical support for installation, wiring, and application questions is available via email and WhatsApp at no additional charge.

Contact Information

Email: [email protected]
WhatsApp: +86 18359268345
Web: siemensplc.com
Location: Xiamen, China
© 2026 siemensplc.com. All rights reserved.

Ready to quote

Send This Part Number to Sales

[email protected]
RFQ workflow

Confirmation Process

Quality workflow ->
01Model confirmation

We check the full part number, brand, series and visible nameplate information before quotation.

02Availability reply

Sales confirms stock path, condition option, quantity and realistic lead time for export dispatch.

03Packing & courier

DHL, FedEx, UPS or buyer courier arrangements can be reviewed with packing requirements.